Plan Review Details - Permit 02110849
Plan Review Stops For Permit 02110849
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-13 Cont ID  
Sent By jgomez Date 2002-12-11 Time 14:41 Rev Time 0.50
Received By btrobaug Date 2002-12-13 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-24 Time 13:07 Rev Time 0.00
Received By shernand Date 2003-04-24 Time 13:07 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 10:06 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-06 Cont ID  
Sent By pkrauss Date 2003-05-06 Time 09:51 Rev Time 0.20
Received By pkrauss Date 2003-05-06 Time 09:51 Sent To  
Notes
2003-05-06 00:00:00REVISION MECHANICAL PERMIT 02110980

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-09 Cont ID  
Sent By shernand Date 2003-04-24 Time 13:07 Rev Time 0.33
Received By hmoser Date 2002-12-09 Time 19:07 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-02 Cont ID  
Sent By sgraham Date 2002-11-18 Time 13:43 Rev Time 0.25
Received By jleech Date 2002-12-02 Time 19:10 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-11 Cont ID  
Sent By jgomez Date 2002-12-11 Time 13:45 Rev Time 2.00
Received By jgomez Date 2002-12-11 Time 13:45 Sent To E
Notes
2002-12-11 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. WILL NEED THE ELEVATION
 CERTIFICATE.
 3-2ND FLOOR FRAMING PLAN: SPECIFY
 DRAFSTOPPING LOCATION AT AREAS NOT TO
 EXCEED 500 S.F. AS REQUIRED BY SECTION
 2305.2.2 FBC 2001.
 4-SPECIFY SIZE OF ANCHOR BOLT AND WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SE. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-24SH AND 34SH WINDOWS DON'T PROVIDE
 THE 24" MIN. CLEAR HEIGHT OPENING AS
 REQUIRED BY SEC. 105.4.4 FBC 2001.
 ALSO, 24SH WINDOWS DON'T PROVIDE THE
 5.7 S.F. MIN. CLEAR OPENING. REVISE
 CLARIFY AS REQUIRED.
 6-DETAIL S21 DOESN'T WORK FOR WOOD COL.
 P1 LOCATED BET. GARAGE & STAIRWAY.
 REVISE/ CLARIFY AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-REVISE CONNECTOR TC-1 ON ROOF FRAMING
 PLAN AT FRONT ELEVATION. TC CONNECTORS
 ARE FOR WOOD TO CONCRETE. NEED WOOD TO
 WOOD CONNECTORS AT FRAMED WALL. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-18 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 10:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***