Plan Review Details - Permit 02110801
Plan Review Stops For Permit 02110801
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-27 Cont ID  
Sent By btrobaug Date 2002-11-27 Time 11:57 Rev Time 0.50
Received By btrobaug Date 2002-11-27 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-18 Cont ID  
Sent By btrobaug Date 2002-11-18 Time 16:33 Rev Time 1.00
Received By btrobaug Date 2002-11-18 Time 13:54 Sent To  
Notes
2002-11-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 THE PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 2} PLEASE SUBMIT RISER DIAGRAMS WITH ALL
 PANELS,DISCONNECTS AND GROUNDING
 SYSTEMS TO BE USED.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} SHOW LOCATIONS OF DISCONNECTS,PANELS
 AND GROUNDING MEANS AT ALL LOCATIONS ,ON
 PLANS.
  
 5} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALCULATIONS PER 210-11(C)(1).
  
 6} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,ON PANEL SCHEDULE
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE,PER 210-12.
  
 8} PLEASE SUBMIT LOAD CALCAULATIONS PER
 220,215-5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659/8096 EXT.8392