Plan Review Details - Permit 02110202
Plan Review Stops For Permit 02110202
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-28 Cont ID  
Sent By btrobaug Date 2003-01-28 Time 10:01 Rev Time 0.50
Received By btrobaug Date 2003-01-28 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-12 Cont ID  
Sent By dpalmer Date 2002-12-12 Time 08:23 Rev Time 0.30
Received By dpalmer Date 2002-12-12 Time 08:23 Sent To P
Notes
2002-12-12 00:00:00************** NOTES REDLINED ********
  
 1)NOTE: PLEASE NOTE, DRYER STILL SHOWN
 AS 1-P20A. PLEASE REVISE OCP FOR 5KW
 AT 240V
  
 2)NOTE: PLEASE ADD SD OR MOVE SD SHOWN,
 MUST BE IN IMEDIATE VICINITY OUTSIDE
 ALL BEDROOMS. NFPA-72 8-1.4
  
 PLEASE SUBMIT THE ABOVE AND ALL OPTIONS
 INSTALLED BEFORE ROUGH. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 18:13 Rev Time 0.25
Received By dpalmer Date 2002-11-14 Time 09:08 Sent To P
Notes
2002-11-14 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE NOTE, PLANS DO NOT
 CORRELATE WITH MASTER.02041264
  
 2)NOTE: PLEASE SEE MISSING ARC FAULT
 PER 210-12
  
 3)NOTE: PLEASE SEE MISSING BATH(S)
 CIRCUITS PER210-11-C3
  
 4)NOTE: PLEASE SEE DRYER SHOWN AT 1-POLE
 20A BRKR.
  
 PLEASE SEE OTHER CHANGES ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 14:57 Rev Time 0.00
Received By dpalmer Date 2002-12-27 Time 14:57 Sent To P
Notes
2002-12-27 00:00:00TO PLUMB INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 18:13 Rev Time 0.00
Received By btrobaug Date 2002-12-10 Time 18:13 Sent To E
Notes
2002-12-10 00:00:00TO DVP./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-25 Cont ID  
Sent By rbrown Date 2002-11-25 Time 16:24 Rev Time 0.00
Received By rbrown Date 2002-11-25 Time 16:24 Sent To  
Notes
2002-11-25 00:00:00PLANS SAME AS MASTER PERMIT # 02041264

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-02-03 Cont ID  
Sent By kstevens Date 2003-02-03 Time 17:34 Rev Time 0.50
Received By kstevens Date 2003-02-03 Time 17:34 Sent To  
Notes
2003-02-03 00:00:00REVISION OK - SANT. RISER DIAGRAM -
 FLOOR PLAN

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-06 Cont ID  
Sent By pschmitz Date 2003-01-06 Time 14:20 Rev Time 66.00
Received By pschmitz Date 2003-01-06 Time 14:22 Sent To B
Notes
2003-01-06 00:00:00REVISON, APPR PES.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-17 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 14:57 Rev Time 0.25
Received By kstevens Date 2002-12-17 Time 18:13 Sent To  
Notes
2002-12-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) COMMENT FROM PREVIOUS REVIEW NOT
 ADDRESSED.
 MASTER BATH SANITARY RISER DIAGRAM, SHT
 A-02 AND FLAT DRAWING SHEET A-03 DO NOT
 MEET CODE. SEPARATE RISERS ARE REQUIRED
 FOR EACH LAV.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2002-12-12 Time 08:23 Rev Time 0.25
Received By kstevens Date 2002-11-20 Time 18:41 Sent To R
Notes
2002-11-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) MASTER BATH SANITARY RISER DIAGRAM,
 SHEET A-02 AND FLAT DRAWING SHEET A-03
 DO NOT MEET CODE. SEPARATE RISERS ARE
 REQUIRED FOR EACH LAV. ALSO SHOWS 1-1/2"
 AT STACK ON SHEET A-03. ??
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-11-25 Cont ID  
Sent By kstevens Date 2002-11-20 Time 18:42 Rev Time 0.00
Received By rbrown Date 2002-11-25 Time 16:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By sgraham Date 2002-11-13 Time 08:19 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***