Plan Review Stops For Permit 02110163 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-02-04 00:00:00 | REV DATED 12/17/03 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-11-19 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-11-19 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-11-19 |
Time |
14:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-11-13 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-11-13 |
Time |
08:21 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-11-13 |
Time |
07:18 |
Sent To |
|
|
Notes |
2002-11-13 00:00:00 | THE DOOR EXITING "OPEN OFFICE 124" ON | | THE SOUTH SIDE OF THE TOILET ROOMS | | SHOWN AS "EXT" IS REQUIRED TO SWING IN | | THE DIRECTION OF EXIT TRAVEL.SEE FBC | | 1012.1.2 AND FBC 1012.1.4. | | | | THE DOOR AND SIDE LIGHT SHOWN AS 109 | | NEAR THE NORTH STAIR IS REQUIRED TO BE | | FIRE RATED.SEE FBC 1010.1. | | | | SHOW THE DESIGN WIND PRESSURE FOR THE | | NEW STORE FRONT DOOR.SEE FBC 1606.1.7. | | | | IF THE TEST REPORTS AND/OR NOTICE OF | | ACCEPTANCE REPORTS ARE NOT INCLUDED | | WITH THIS PERMIT APPLICATION, A | | SEPARATE PERMIT, PLANS AND FEES WILL BE | | REQUIRED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2003-02-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-04 |
Time |
14:27 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-02-04 |
Time |
14:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-11-21 |
Time |
05:41 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-11-21 |
Time |
05:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-11-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-11-19 |
Time |
10:22 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-11-19 |
Time |
10:20 |
Sent To |
|
|
Notes |
2002-11-19 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE RISER DIAGRAM AND | | PANEL SCHEDULE DO NOT CORRELATE FOR | | "H1B". PLEASE NOTE, ORIG SHEET SHOWS | | RISER AS "H2B. PLEASE NOTE RISER IS | | NOW CHANGED BUT PANEL SCHEDULE FOR TRANS | | -FORMER SHOWS ,, PANEL "LA" FED THRU | | TRANSFORMER "TB1". PLEASE SEE RISER | | DIAGRAM, PANEL LA IS SHOWN AS PART OF | | EXSITING SERVICE? X-FORMER IS ALSO | | SHOWN AS T1B? PLEASE NOTE RISER DIAGRAM | | SHOWS NEW TRANSFORMER " T1C" AND L1B, | | L1C, ETC. | | | | 2)NOTE: PLEASE NOTE, NOT #2 FROM FIRST | | REVIEW NEEDS TO BE ADDRESSED. PLEASE | | CLARIFY REQ`D RECEPT FOR A/C UNITS | | PER 210-63. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-11-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-11-13 |
Time |
06:27 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2002-11-13 |
Time |
06:27 |
Sent To |
|
|
Notes |
2002-11-13 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE, RISER DIAGRAM | | AND SUBMITTED PANEL SCHEDULES DO NOT | | CORRELATE. MISSING PANEL "H2B, MISSING | | "L2C", LOAD CALCULATIONS,CIRCUIT #`S | | WIRE SIZES ETC. | | PLEASE NOTE, THERE ARE PANEL SCHEDULES | | SUBMITTED NOT ON RISER? "H1B", PLEASE | | CLARIFY.215-5 | | PLEASE NOTE AT THIS TIME A COMPLETE | | REVIEW OF WIRE/OCP/LOADS CAN NOT BE DONE | | UNTIL RISER/PLANS/SCHEDULES CORRELATE. | | | | 2)NOTE: PLEASE NOTE/CLARIFY RECEPT REQ`D | | FOR A/C EQUIPMENT ON ROOFTOP. NEW/ EXIST | | ? 210-63 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2003-02-06 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-02-06 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-02-06 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-11-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-11-19 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-11-19 |
Time |
11:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-11-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-11-13 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-11-13 |
Time |
13:04 |
Sent To |
|
|
Notes |
2002-11-13 00:00:00 | 1) DOOR LEADING FROM OPEN OFFICE 124 | | SWINGS IN THE WRONG DDIRECTION. | | | | 2) DOOR 109 AND EXISTING STAIR DOOR | | APPEAR TO OPPOSE ONE ANOTHER. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-01-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-01-30 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2003-01-30 |
Time |
14:57 |
Sent To |
|
|
Notes |
2003-01-30 00:00:00 | TO COMM BOARD #19./WRT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-11-20 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-20 |
Time |
18:05 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-20 |
Time |
18:05 |
Sent To |
|
|
Notes |
2002-11-20 00:00:00 | TO COMM BOARD,# 31 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-11-21 |
Time |
15:31 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-11-21 |
Time |
15:23 |
Sent To |
|
|
Notes |
2002-11-21 00:00:00 | MECHANICAL PERMIT 02110170 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-11-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-11-13 |
Time |
12:51 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-11-13 |
Time |
10:34 |
Sent To |
|
|
Notes |
2002-11-13 00:00:00 | PROVISO:MECHANICAL PERMIT 02110170 | | | | PLEASE NOTE - PLAN SHEET M2.2, EXISTING | | DUCTWORK PENETRATING THE WALL AT OFFICE | | #211 & ALSO WHERE DUCT PENETRATES THE | | CORRIDOR, FIRE DAMPERS ARE NOT INDICATED | | IN THESE AREAS (THEY SHOULD BE EXISTING) | | SHOULD FIRE DAMPERS NOT BE IN PLACE THEY | | ARE REQUIRED. | | | | PROVIDE MANUFACTURER INSTALLATION | | INSTRUCTIONS FOR THE FIRE DAMPERS ON THE | | JOBSITE AT THE TIME OF INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2003-02-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-02-11 |
Time |
11:49 |
Rev Time |
0.10 |
Received By |
kstevens |
Date |
2003-02-11 |
Time |
11:49 |
Sent To |
|
|
Notes |
2003-02-11 00:00:00 | REVISION OK |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2003-02-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-02-06 |
Time |
07:41 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2003-02-05 |
Time |
18:53 |
Sent To |
|
|
Notes |
2003-02-06 00:00:00 | REVISION DENIED | | | | 1) PER TABLE 403.1 A DRINKING FOUNTAIN | | IS REQUIRED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-11-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-11-08 |
Time |
10:11 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-11-08 |
Time |
10:11 |
Sent To |
|
|
Notes |
|
|