Plan Review Details - Permit 02102230
Plan Review Stops For Permit 02102230
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-27 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 15:07 Rev Time 0.25
Received By dpalmer Date 2002-11-27 Time 15:07 Sent To M
Notes
2002-11-27 00:00:00********** NOTES REDLINED FOR OCP FOR
 AHU TO BE A MIN 125%. 424-3
 SHOWS 10KW ON 2-P-25A??

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-04 Cont ID  
Sent By dpalmer Date 2002-11-04 Time 09:26 Rev Time 0.00
Received By dpalmer Date 2002-11-04 Time 09:26 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-30 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 15:08 Rev Time 0.33
Received By jleech Date 2002-11-30 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-18 Cont ID  
Sent By sgraham Date 2002-11-04 Time 16:03 Rev Time 0.33
Received By jleech Date 2002-11-18 Time 20:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-05 Cont ID  
Sent By rmcdouga Date 2002-12-05 Time 14:21 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-05 00:00:00BUILDING PROVISO
  
 1) PROVIDE A SOIL TEST REPORT, PER CITY
 OF WPB AMENDMENTS TO FBC 1804.2, SIGNED
 AND SEALED BY A SOIL ENGINEER INDICATING
 THE BEARING CAPACITY OF THE SOIL.
  
 2) SUBMIT SIGNED AND SEALED ENGINEERED
 DRAWINGS OF THE BUCKET CONNECTORS SHOWN
 IN DETAILS C AND D ON S2.
  
 3) PROVIDE PRODUCT APPROVALS FOR THE
 ARCHED TOP FIXED GLASS WINDOW.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By dpalmer Date 2002-11-04 Time 09:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***