Plan Review Details - Permit 02102229
Plan Review Stops For Permit 02102229
Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2003-04-21 Time 12:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-15 Time 13:40 Rev Time 0.25
Received By dpalmer Date 2003-04-08 Time 14:24 Sent To  
Notes
2003-04-08 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW/REDLINED.
 PLEASE SIZE AWG/OCP FOR AHU #2. 10KW W/
 #10 AND 2P-25.
  
 2)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-27 Cont ID  
Sent By sthyng Date 2003-04-01 Time 09:32 Rev Time 0.25
Received By dpalmer Date 2002-11-27 Time 16:02 Sent To M
Notes
2002-11-27 00:00:00********** NOTES ********
 PLANS REDLINED, OCP FOR AHU SHOWN AT 2P
 -25A FOR 10KW LOAD. NEEDS TO BE SIZED
 AT 125% MIN PER 424-3

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-15 Cont ID  
Sent By shernand Date 2003-04-15 Time 13:40 Rev Time 0.00
Received By shernand Date 2003-04-15 Time 13:40 Sent To E
Notes
2003-04-15 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-01 Cont ID  
Sent By sthyng Date 2003-04-01 Time 09:32 Rev Time 0.00
Received By sthyng Date 2003-04-01 Time 09:32 Sent To E
Notes
2003-04-01 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-13 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 18:21 Rev Time 0.00
Received By btrobaug Date 2002-12-13 Time 18:21 Sent To R
Notes
2002-12-13 00:00:00ROB M./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-04 Cont ID  
Sent By dpalmer Date 2002-11-04 Time 09:26 Rev Time 0.00
Received By dpalmer Date 2002-11-04 Time 09:25 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-30 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 16:02 Rev Time 0.33
Received By jleech Date 2002-11-30 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-18 Cont ID  
Sent By sgraham Date 2002-11-04 Time 16:03 Rev Time 0.33
Received By jleech Date 2002-11-18 Time 20:14 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-12-16 Cont ID  
Sent By rmcdouga Date 2002-12-16 Time 15:55 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-16 00:00:00BUILDING PROVISO
  
 1) SUBMIT SIGNED AND SEALED ENGINEERED
 DRAWINGS FOR THE HANGER CONNECTOR SHOWN
 IN DETAIL D ON S2.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE OVAL AND ARCHED TOP
 FIXED GLASS WINDOWS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 18:21 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-05 00:00:00BUILDING DENIED
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE A SIGNED AND SEALED SOIL TEST
 REPORT FROM A SOIL ENGINEER INDICATING
 THE SOIL BEARING CAPACITY.
  
 2) THE F4 FOOTINGS FOR THE COLUMNS AT
 THE COVERED PORCH ARE NOT GIVEN IN THE
 FOOTING SCHEDULE ON S1.
  
 3) SPECIFY THE WASHER SIZE FOR THE 1/2"
 J-BOLT SHOWN IN SECTION 3 ON S1.
  
 4) THE NAIL SPACING INDICATED FOR THE
 ROOF SHEATHING ON THE DETAILS ON S2 AND
 ON GN1 ARE NOT CORRECT. PLEASE CORRECT.
 SEE CITY OF WPB AMENDMENTS TO FBC TABLE
 23O6.1.
  
 5) CLARIFY THE SIZE OF THE DOOR TO THE
 CABANA BATH ON A1. THERE APPEARS TO BE A
 TYPO (210868 IS GIVEN).
  
 6) THE BUILT-UP WOOD POST COLUMN IS
 SPECIFIED AS (2) 2X4 ON S1 AND ON S3 IT
 IS GIVEN AS (3) 2X4. PLEASE CLARIFY.
  
 7) SUBMIT SIGNED AND SEALED ENGINEERED
 DRAWINGS FOR THE BUCKET CONNECTION SHOWN
 IN DETAIL D ON S2.
  
 8)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE OVAL AND ARCHED TOP
 FIXED GLASS WINDOWS.
  
 9) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By dpalmer Date 2002-11-04 Time 09:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***