Plan Review Details - Permit 02102183
Plan Review Stops For Permit 02102183
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-30 Cont ID  
Sent By dpalmer Date 2002-12-30 Time 07:13 Rev Time 1.00
Received By dpalmer Date 2002-12-30 Time 07:13 Sent To  
Notes
2002-12-30 00:00:00PLANS OK.
 CONTRACTOR NEEDS TO COME IN AND TAKE
 ALL OLD/VOIDED SHEETS OUT AND MAKE TWO
 COMPLETE SETS AND PLACE ALL VOIDED SHEET
 S IN THIRD SET.
  
 IF THERE ARE ANY QUESTIONS , PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By dpalmer Date 2002-11-14 Time 09:42 Rev Time 1.00
Received By dpalmer Date 2002-11-14 Time 09:42 Sent To  
Notes
2002-11-14 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE PLANS MUST BE SIGNED
 DTAED AND SEALED BY THE ENGINEER OF
 RECORD. REQ`D PER FS/FAC 471.025,
 471.003 H 1/ FBC 104.4.1.3
 FOR 277/480V
  
 2)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. 215-3,230-42
 ETC.
  
 3)NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220-12B.
  
 4)NOTE: PLEASE CLARIFY HOW 700-12 IS MET
  
 5)NOTE: PLEASE SHOW ALL CIRCUIT ON PLANS
 AND CORRELATE WITH PANEL SCHEDULE.
  
 6)NOTE: PLEASE CLARIFY LOCATIONS OF MAIN
 -S. GROUPING OF MAINS PER 230-72
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-01-02 Cont ID  
Sent By mcarsill Date 2003-01-02 Time 19:01 Rev Time 0.00
Received By mcarsill Date 2003-01-02 Time 19:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By mcarsill Date 2002-11-14 Time 12:49 Rev Time 0.00
Received By mcarsill Date 2002-11-14 Time 12:49 Sent To  
Notes
2002-11-14 00:00:001) PLANS INDICATE THE INSTALLATION OF
 AN ADDITIONAL FIRE ALARM CONTROL PANEL.
 NO NEW ADDITIONAL FIRE ALARM PANELS
 WILL BE ALLOWED TO BE INSTALLED WITHIN
 TENANT SPACES. FIRE ALARM EQUIPMENT MUST
 BE CONNECTED WITHIN THE TENANT SPACE
 TO THE BASE BUILDING FIRE ALARM PANEL.
 EXISTING SUB FIRE ALARM CONTROL PANELS
 HAVE CAUSED SIGNIFICANT PROBLEMS.
 PLEASE DELETE THIS ITEM FROM THE
 PLANS AND REVISE AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-09 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 18:12 Rev Time 1.00
Received By dpalmer Date 2003-01-09 Time 18:12 Sent To  
Notes
2003-01-09 00:00:00PROCESSED PLANS, TOOK OUT OLD SHEETS
 MADE TWO NEW SETS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 17:34 Rev Time 0.00
Received By btrobaug Date 2002-12-10 Time 17:34 Sent To  
Notes
2002-12-10 00:00:00COMM BOARD #47./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-04 Cont ID  
Sent By dpalmer Date 2002-11-04 Time 10:16 Rev Time 0.00
Received By dpalmer Date 2002-10-31 Time 10:16 Sent To  
Notes
2002-11-04 00:00:00TO COMM BOARD .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-27 Cont ID  
Sent By pkrauss Date 2002-12-27 Time 15:45 Rev Time 1.45
Received By pkrauss Date 2002-12-27 Time 15:15 Sent To  
Notes
2002-12-27 00:00:00PROVISO:
  
 1.AHU UNIT ACCESS PRIOR TO COMMENCING
 WORK CLARIFY SAFETY FOR SERVICING. WILL
 THERE BE SUFFICIENT CLEARANCE FOR
 REPLACMENT OF THE COILS & FAN MOTORS?
 2001 FBC(M) 306.1.
  
 RESPONSE TO COMMENTS 3, 4, & 5 OKAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By pkrauss Date 2002-11-14 Time 13:28 Rev Time 0.50
Received By pkrauss Date 2002-11-14 Time 12:12 Sent To  
Notes
2002-11-14 00:00:00DENIED:
  
 CLARIFY ACCESS FOR MAINTENANCE, SERVICE
 OR REPLACEMENT OF THE AHU'S AND ITS
 COMPONENTS.2001FBC(M) 306.1
  
 INDICATE ELEVATION OF AHU'S.
  
 PROVIDE MANUFACTURER SUBMITTAL DATA ON
 THE STANDS FOR THE CONDENSER UNITS.
 SHOW COMPLIANCE WITH 2001 FBC TABLE
 1511.7 - MINIMUM HEIGHT REQUIREMENT FROM
 ROOF SURFACE.SHOW ACCESS TO CONDENSER
 UNITS LOCATED ON THE ROOF.
  
 ADDITIONAL PERMIT REQUIRED FOR WALK IN
 COOLERS OR FREEZERS. PROVIDE SUBMITTAL
 DATA FROM MANUFACTURER. SHOULD CONDENSER
 UNIT BE REMOTE, SHOW LOCATION OF C.U.
  
 INDENTIFY CONDENSATE TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-30 Cont ID  
Sent By kstevens Date 2002-12-30 Time 09:22 Rev Time 1.00
Received By kstevens Date 2002-12-30 Time 09:22 Sent To  
Notes
2002-12-30 00:00:00PASSED/PROVISO
  
 RPZ BACKFLOW REQUIRED - MANUF. INFO. FOR
 NSF COMPLIANCE FOR FILTER SHALL BE ON
 JOB FOR FINAL - FLOOR SINK REQUIRED AT
 WATER HEATER

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-18 Cont ID  
Sent By kstevens Date 2002-11-18 Time 15:16 Rev Time 3.00
Received By kstevens Date 2002-11-18 Time 15:15 Sent To  
Notes
2002-11-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1.3 SECTION 11-4.22.4 IF TOILET
 STALLS ARE PROVIDED, THAN AT LEAST ONE
 SHALL BE A STANDARD TOILET STALL COMPLY-
 ING WITH 11-4.17. EACH TOILET ROOM SHALL
 COMPLY.
 2) SHT A10.3 TYPICAL WATERPROOF MENBRANE
 DETAIL. AN ENGINEERED - SIGNED, SEALED,
 AND DATED SUBMITTAL OF WATERPROOFING DE-
 TAIL IS REQUIRED.
 3) SHTS. P.1 & P.2, ALL INDIRECT WASTE
 SHALL DRAIN INTO A FLOOR SINK. SEC 802.3
 FLOOR DRAINS ARE NOT AN APPROVED IN-
 DIRECT WASTE RECEPTOR. FLOOR SINKS SHALL
 BE LOCATED AS NOT TO PRESENT A TRIPPING
 HAZARD.
 4) SHT P.3 RISER NOTE #6, ALL WATER
 FILTERS SHALL BE "NSF" APPROVED. PLEASE
 SUBMIT MANUF. INFO.
 5) SHT P.5 FLOOR DRAIN SPECIFICATIONS,
 FD-3, FLOOR DRAINS NOT APPROVED FOR IN-
 DIRECT WASTE. ALL INDIRECT WASTE SHALL
 BE DRAINED TO A FLOOR SINK. (SEE REVIEW
 COMMENT #3).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377