Plan Review Details - Permit 02102000
Plan Review Stops For Permit 02102000
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By jleech Date 2003-02-05 Time 19:33 Rev Time 0.25
Received By dpalmer Date 2003-02-10 Time 06:45 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 13:21 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 13:21 Sent To M
Notes
2003-05-08 00:00:00MECH REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-22 Cont ID  
Sent By btrobaug Date 2003-01-22 Time 17:58 Rev Time 0.00
Received By btrobaug Date 2003-01-21 Time 17:58 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 17:02 Rev Time 0.00
Received By btrobaug Date 2002-10-30 Time 17:02 Sent To Z
Notes
2002-10-30 00:00:00TO Z IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-21 Cont ID  
Sent By pkrauss Date 2003-05-21 Time 08:25 Rev Time 0.20
Received By pkrauss Date 2003-05-21 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-05 Cont ID  
Sent By shernand Date 2003-05-08 Time 13:21 Rev Time 0.33
Received By jleech Date 2003-02-05 Time 19:32 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-01 Cont ID  
Sent By sgraham Date 2003-01-24 Time 15:56 Rev Time 0.25
Received By jleech Date 2003-02-01 Time 11:33 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-02-11 Cont ID  
Sent By jgomez Date 2003-02-11 Time 17:28 Rev Time 2.00
Received By jgomez Date 2003-02-11 Time 17:28 Sent To  
Notes
2003-02-11 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 3-REVISE HANDRAIL HEIGHT ON BUILDING
 SECTION 1/A-5. SEE SECTION 1007.5.1
 FBC 2001 FOR HANDRAIL HEIGHT.
 4-DETAIL 2/S-2 DOESN'T SPECIFY THE
 CONNECTORS. SPECIFY THEM AS REQUIRED.
 SEE FRAMING PLANS FOR LOCATION AND
 CALCULATED LOADS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.

Review Stop Z ZONING
Rev No 2 Status P Date 2003-01-24 Cont ID  
Sent By sgraham Date 2003-01-24 Time 15:56 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2003-01-22 Time 17:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-11-04 00:00:00DENIED NEED SITE SURVEY