Plan Review Details - Permit 02101998
Plan Review Stops For Permit 02101998
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-27 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 14:32 Rev Time 0.25
Received By dpalmer Date 2002-11-27 Time 14:31 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-04-10 Time 12:06 Rev Time 0.00
Received By shernand Date 2003-04-10 Time 12:06 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2002-10-31 Time 13:22 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-04-12 Cont ID  
Sent By rregueir Date 2003-04-12 Time 09:47 Rev Time 0.33
Received By rregueir Date 2003-04-12 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-10 Cont ID  
Sent By shernand Date 2003-04-10 Time 12:06 Rev Time 0.33
Received By rregueir Date 2003-03-10 Time 18:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-30 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 14:32 Rev Time 0.33
Received By jleech Date 2002-11-30 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-13 Cont ID  
Sent By sgraham Date 2002-11-04 Time 15:39 Rev Time 0.25
Received By jleech Date 2002-11-13 Time 19:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-04-22 Cont ID  
Sent By jgomez Date 2003-04-22 Time 16:58 Rev Time 0.50
Received By jgomez Date 2003-04-22 Time 16:58 Sent To  
Notes
2003-04-22 00:00:00REVISION FOR TOP OF BEAM ELEVATION AT
 ZERO LOT LINE WALL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-04 Cont ID  
Sent By jgomez Date 2002-12-04 Time 18:36 Rev Time 2.00
Received By jgomez Date 2002-12-04 Time 18:36 Sent To  
Notes
2002-12-04 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO REVISE DETAIL FOR ONE HR
 FIRE RATED WALL ASSEMBLY AT ZERO LOT
 LINE WALL. TABLE REFERENCED ON DETAIL
 11/S3 IS FOR CONCRETE WALL ASSEMBLIES,
 NOT WOOD. SEE SECTION 709.6 FBC 2001
 FOR WOOD ASSEMBLIES AND NEED COMPLETE
 ASSEMBLY TAKING INTO CONSIDERATION
 INTERIOR AND EXTERIOR EXPOSURE TO FIRE
 AS REQUIRED BY TABLE 600 FBC 2001.
 2-ARCHITECT TO REVISE THE DIAPHRAGM
 SCHEDULE TO MATCH ENGINEERING ANALYSIS
 AND SPECIFICATIONS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED ANCHOR SIZE AND WASHER.
 COLUMN SCHEDULE DOESN'T HAVE ANY
 INFORMATION EITHER.SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 13:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***