Plan Review Details - Permit 02101948
Plan Review Stops For Permit 02101948
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-09 Cont ID  
Sent By rmcdouga Date 2002-12-09 Time 11:26 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-13 Cont ID  
Sent By kstevens Date 2002-12-07 Time 08:56 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-13 00:00:00DENIED BY BUILDING
  
 1) SPECIFY ON THE PLANS COMPLIANCE WITH
 THE RESIDENTIAL SWIMMING POOL BARRIER
 REQUIREMENT. SEE 2001 FBC 424.2.17.
  
 2) INDICATE ON THE PLANS WHICH ONE OF
 THE RESIDENTIAL SWIMMING POOL SAFETY
 OPTIONS WILL BE USED. SEE FLORIDA
 STATUES 515.
  
 3) REVISE GENERAL NOTES TO REFERENCE THE
 2001 FLORIDA BUILDING CODE.
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-12 Cont ID  
Sent By kstevens Date 2002-11-09 Time 07:56 Rev Time 0.25
Received By btrobaug Date 2002-11-12 Time 06:59 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 18:54 Rev Time 0.00
Received By btrobaug Date 2002-11-26 Time 18:54 Sent To P
Notes
2002-11-26 00:00:00IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 16:37 Rev Time 0.00
Received By btrobaug Date 2002-10-30 Time 16:37 Sent To Z
Notes
2002-10-30 00:00:00TO ZONING IN BOX./WRT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-07 Cont ID  
Sent By kstevens Date 2002-12-07 Time 08:56 Rev Time 0.50
Received By kstevens Date 2002-12-07 Time 08:56 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-09 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 18:54 Rev Time 0.50
Received By kstevens Date 2002-11-09 Time 07:39 Sent To E
Notes
2002-11-09 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) GENERAL NOTES, #1 & #5, CODE IS FBC-
 2001 NOT SBCCI OR COUNTY SWIMMING POOL
 CODE. PLEASE CHANGE REFERENCES.
 2) CLEANING LINE NOT SHOWN ON PIPING
 SCHEMATIC.
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. AND NSPI-5 (ADD TO NOTES
 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 5) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 6) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 7) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 9) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 10) FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING. THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND RE-
 MOVAL. SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER FUN-
 CTION OF THE FILTRATION AND PIPING SYS-
 TEM. SEC 424.2.8.3 WHERE CHECK VALVES
 ARE INSTALLED THEY SHALL BE OF THE SWING
 OR VERTICAL CHECK PATTERNS. SEC 424.2.8.
 4 COMBINATION VALVES SHALL REQUIRE APP-
 ROVAL OF THE ADMINISTRATIVE AUTHORITY
 PRIOR TO THEIR INSTALLATION.
 11) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 12) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 13) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-13 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 16:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***