Plan Review Details - Permit 02101904
Plan Review Stops For Permit 02101904
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-05-05 Time 14:02 Rev Time 0.00
Received By hpiskura Date 2003-04-21 Time 09:15 Sent To  
Notes
2003-04-21 00:00:00AS NOTED PREVIOUSLY, SEPARATE PERMITS
 ARE REQUIRED FOR DOORS, WINDOWS ANDS
 ROOFCOVERINGS NOT INCLUDED WITH THE
 ORIGINAL PERMIT APPLICATION.
  
 THE METRO-DADE NOA # 01-430.01 HAS
 ILLEGIBLE PAGES.ALSO, IT IS REQUIRED
 TO BE REVIEWED BY THE DESIGNER OF
 RECORD FOR CONFORMANCE WITH THE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-04-01 Cont ID  
Sent By shernand Date 2003-04-17 Time 09:59 Rev Time 0.00
Received By hpiskura Date 2003-04-01 Time 09:10 Sent To  
Notes
2003-04-01 00:00:00PLEASE PROVIDE AN EVALUATION REPORT FOR
 THE JAMES HARDIE SIDING PRODUCTS, NOTE
 THE SPECIFIC PRODUCT(S) TO BE USED, THE
 INSTALLATION METHOD FOR THE WPB WIND
 ZONE (140 MPH)

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-25 Cont ID  
Sent By sthyng Date 2003-03-26 Time 15:30 Rev Time 1.50
Received By lsmith Date 2003-02-25 Time 08:13 Sent To  
Notes
2003-02-25 00:00:00****************PROVISO NOTES********
  
  
 1. THE CONTRACTOR WILL BE REQUIRED TO
 APPLY FOR SEPARATE PERMITS FOR THE
 FOLLOWING ITEMS:
 1. STOREFRONT & WINDOWS
 2. DOORS
 3. ROOFING MATERIALS
 4. FIBER-CEMENT SIDING
  
 SEE JOB SPEC BOOK FOR FURTHER
 SUBMITTALS REQUIRED THROUGHTOUT THE JOB.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANSEXAMINER
 659-8096 EXT 8394 OR
 HAROLD PISKURA @ 659-8096 EXT. 8219

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By lsmith Date 2003-02-25 Time 07:06 Rev Time 0.00
Received By hpiskura Date 2003-02-07 Time 07:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By btrobaug Date 2002-11-05 Time 16:24 Rev Time 0.00
Received By hpiskura Date 2002-12-03 Time 09:17 Sent To  
Notes
2002-12-03 00:00:00SHEET SP1 RE: THE HANDICAP PARKING
 SPACES.PLEASE PROVIDE SPECIFIC DESIGN
 INFORMATION, DO NOT QUOTE THE CODE
 SECTION.ALSO, THE SITE PLAN DOES NOT
 HAVE ANY DIMENSIONS LOCATING THE
 PROPOSED CONSTRUCTION ON THE PROPERTY.
  
 THE PLANS DO NOT INDICATE THE ROOF SLOPE
 OR THE WIND PRESSURE ZONES.
  
 PLEASE DEMONSTRATE HOW THE GABLE ENDS OF
 THE ROOF WILL MEET THE "STRUCTURALLY
 CONTINUOUS" REQUIREMENT OF FBC 2313.4.1.
  
 PLEASE PROVIDE A SPECIFIC METHOD OF
 INSTALLATION FOR THE "FIBER CEMENT
 PANELS" AS DEFINED BY THEIR NER 405
 LISTING.
  
 INDICATE THE ATTIC ACCESS REQUIRED BY
 FBC 2309.6.
  
 SHOW A STRUCTURAL DETAIL FOR THE
 TRANSITION/TERMINATION OF THE 8X16 TIE
 BEAM AT ELEVATION 109'-4" INTO THE CMU
 PRACTICE WALL.
  
 THE SPECIFICATIONS DECLARE AN F'M OF
 2000 PSI FOR THE MASONRY AND THE
 STRUCTURAL SHEET CALLS OUT 1500 PSI.
 PLEASE CLARIFY THE INTENT.THE
 SPECIFICATIONS ARE NOT SEALED BY THE
 ENGINEER.
  
 IF THE TEST REPORTS AND OR THE NOTICE OF
 ACCEPTANCE INFORMATION FOR THE DOORS
 WINDOWS AND ROOF COVERING ARE NOT
 INCLUDED WITH THE PERMIT APPLICATION, A
 SEPARATE PERMIT, FEES AND PLANS WILL BE
 REQUIRED.
  
 SHOW HOW THE GLAZED AREAS OF THE
 BUILDING EXTERIOR WILL RESIST HURRICANE
 MISSILE IMPACT.SEE FBC 1606.1.4.
2002-11-05 00:00:00TO ZONING BOX./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-04-29 Cont ID  
Sent By btrobaug Date 2003-04-29 Time 09:23 Rev Time 1.00
Received By btrobaug Date 2003-04-29 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-21 Cont ID  
Sent By shernand Date 2003-04-03 Time 14:59 Rev Time 1.00
Received By dpalmer Date 2003-02-21 Time 14:56 Sent To Z
Notes
2003-02-21 00:00:00TO ZONING/SG FOR SIGN OFF.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 11:32 Rev Time 0.75
Received By dpalmer Date 2003-02-07 Time 05:14 Sent To  
Notes
2003-02-07 00:00:00************** UNSAT ************
  
 PLANS ARE BEING SUBMITTED COMPLETED AND
 HAVE THE FOLLOWING COMMENTS.
  
 1)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULE. ONE SHOWS 100A PANEL AND OTHER
 SHOWS 200A?
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW DISC AND PANEL. 110-9/215-5
  
 3)NOTE: PLEASE INCLUDE CWP AS PART OF
 THE GROUNDING SYSTEM AT BLDG. 250-50
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 SOME CONN LOADS SHOWN ON PANEL SCHEDULE
 EXCEED 100A RATING OF PANEL, SOME ARE
 SHOWN UNDER?? PLEASE SUBMIT A LOAD
 CALC PER 220-3,10,11,13 ETC, ANY CONTIN-
 UOUS LOADS AT 125%. 215-3,230-42 ETC
 PLEASE ADJUST SERVICE AS NEEDED BY LOAD.
  
 5)NOTE: PLEASE SEE MECH PLAN, AHU HEAT
 IS SHOWN AT 5KW, ELECTRICAL PANEL/LOADS
 DO NOT CORRELATE, ELEC SHOWS AHU AT 13A
 AND #12 AWG ON 2P-20??? PLEASE ALSO SEE
 COMP UNIT SHOWN AS 2-P35A ON #12??
 PLEASE SEE 424-3 FOR OCP OF HEAT. MIN
 125% OF LOAD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-09 Cont ID  
Sent By dpalmer Date 2002-12-09 Time 13:47 Rev Time 1.00
Received By dpalmer Date 2002-12-09 Time 13:47 Sent To  
Notes
2002-12-09 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SHOW ALL CIRCTUIING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL.215-5
  
 2)NOTE: PLEASE NOTE, NO LOAD CALCULATION
 -S/ PANEL SCHEDULE WERE SUBMITTED.
 215-5
  
 3)NOTE: PLEASE SHOW TRACK LIGHTING CALCS
 PER 220-12B
  
 4)NOTE: PLEASE NOTE THERE IS NO EQUIP-
 -MENT GROUND BETWEEN METER AND MAIN.
 250-24, PLEASE ALSO NOTE GROUNDING
 CONDUCTOR SHOWN, IS SHOWN AS #5. PLEASE
 NOTE #5 IS NOT A STANDARD SIZE PER AWG.
  
 5)NOTE: PLEASE PROVIDE GROUNDING SYSTEM
 AT BLDG. 250-50/ 250-32
  
 PLEASE NOTE PLANS NEED TO BE COMPLETED
 FOR COMPLETE REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-06 Cont ID  
Sent By mcarsill Date 2003-02-06 Time 12:03 Rev Time 0.00
Received By mcarsill Date 2003-02-06 Time 12:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-12 Cont ID  
Sent By mcarsill Date 2002-12-12 Time 13:49 Rev Time 0.00
Received By mcarsill Date 2002-12-12 Time 13:49 Sent To  
Notes
2002-12-12 00:00:001) PLEASE INDICATE IN WRITING HOW
 LONG THE TRAILERS WILL BE AT THIS
 SITE.
  
 2) BUILDING ADDRESS REQUIRED ON
 BUILDING.
  
 3) THE INTERIOR STORAGE ROOM SHALL
 BE SEPARATED BY AT LEAST ONE HOUR
 WITH 45 MINUTE OPENING PROTECTIVES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 14:02 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 14:02 Sent To B
Notes
2003-05-05 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 09:59 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 09:58 Sent To B
Notes
2003-04-17 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 14:59 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 14:59 Sent To E
Notes
2003-04-03 00:00:00LIGHTING FIXTURES SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 14:56 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 14:56 Sent To P
Notes
2003-04-03 00:00:00SUBMITTING FOR PLUMBING FIXTURES &
 ACCESSORIES

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 14:49 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 14:49 Sent To B
Notes
2003-04-03 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-03-26 Time 15:30 Rev Time 0.00
Received By sthyng Date 2003-03-26 Time 15:30 Sent To B
Notes
2003-03-26 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-20 Cont ID  
Sent By sgraham Date 2003-02-24 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 11:32 Sent To E
Notes
2003-02-20 00:00:00TO DVP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-31 Cont ID  
Sent By btrobaug Date 2003-01-31 Time 18:11 Rev Time 0.00
Received By btrobaug Date 2003-01-28 Time 18:14 Sent To  
Notes
2003-01-31 00:00:00COM BOARD #3./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-03 Cont ID  
Sent By btrobaug Date 2002-12-03 Time 08:33 Rev Time 0.00
Received By btrobaug Date 2002-12-03 Time 08:33 Sent To  
Notes
2002-12-03 00:00:00COMM BOARD # 15./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-05 Cont ID  
Sent By btrobaug Date 2002-11-05 Time 16:18 Rev Time 0.00
Received By btrobaug Date 2002-11-05 Time 16:18 Sent To Z
Notes
2002-11-05 00:00:00TO ZONING BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-12 Cont ID  
Sent By pkrauss Date 2003-02-12 Time 16:28 Rev Time 0.45
Received By pkrauss Date 2003-02-12 Time 16:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-24 Cont ID  
Sent By pkrauss Date 2002-12-24 Time 09:43 Rev Time 0.45
Received By pkrauss Date 2002-12-24 Time 09:29 Sent To  
Notes
2002-12-24 00:00:00DENIED:
  
 1.PLEASE PROVIDE ENERGY & COOLING LOAD
 CALCULATION AS PER 2001 FBC CHAPTER
 13 SECTION 400.0 & 407.1.ABCD.1.
  
 2.PLAN SHEET M1 GENERAL HVAC NOTES #2,
 INDICATES CONDENSING UNIT SHALL BE
 A 1.5 TON UNIT.EQUIPMENT SCHEDULE
 INDICATES A 3 TON. PLEASE CORRELATE.
  
 3.PLEASE CLARIFY R/A LOUVERD DOOR INTO
 THE STORAGE ROOM. AS PER 2001 FBC(M)
 602.1 RETURN AIR PLENUMS SHALL BE
 LIMITED TO UNINHABITED SPACES, THE
 STORAGE ROOM IS NOT CONSIDERED AN
 UNINHABITED SPACE.
  
 4.CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" AWAY FROM THE BUILDING
 STRUCTURE, 2001 FBC 1503.4.4.
  
 5.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 6.EXHAUST FAN SCHEDULE INDICATES FANS
 ARE IN THE CLASS RMS? PLAN INDICATES
 EXHAUST FANS ARE IN THE RESTROOMS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-04 Cont ID  
Sent By kstevens Date 2003-04-04 Time 13:41 Rev Time 0.75
Received By kstevens Date 2003-04-04 Time 13:39 Sent To  
Notes
2003-04-04 00:00:00SUBMITTALS OK - PLUMBING FIXTURES &
 EQUIPMENT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-05 Cont ID  
Sent By shernand Date 2003-04-03 Time 14:56 Rev Time 0.75
Received By kstevens Date 2003-02-05 Time 09:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-26 Cont ID  
Sent By kstevens Date 2002-12-26 Time 11:03 Rev Time 1.50
Received By kstevens Date 2002-12-26 Time 11:02 Sent To  
Notes
2002-12-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT P-1 WASTE AND VENT RISER DOES NOT
 REFLECT FLOOR PLAN. DRINKING FOUNTAIN
 NOT SHOWN ON RISER.
 2) SHT P-1 WASTE & VENT RISER, VENT REQ-
 UIRED FOR SHOWER & FLOOR SINK, AND VENT
 REQUIRED FOR SINK IN PRO SHOP.
 3) SHT P-1 INDIRECT WASTE SHALL DRAIN
 TO A FLOOR SINK. 802.3 - FLOOR DRAIN IS
 NOT AN APPROVED WASTE RECEPTOR.
 4) SHT P-1 WATER RISER DOES NOT REFLECT
 FLOOR PLAN. DRINKING FOUNTAIN NOT SHOWN
 ON WATER RISER DIAGRAM.
 5) RPZ BACKFLOW REQUIRED ON WATER SERV.
 6) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED PER 607.3.2.
 PLEASE SHOW ON DETAIL
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 4 Status P Date 2003-02-24 Cont ID  
Sent By sthyng Date 2003-03-26 Time 15:30 Rev Time 1.00
Received By lsmith Date   Time   Sent To B
Notes
2003-02-25 00:00:00PER AG 2/24/03 (SEE PLANS)

Review Stop Z ZONING
Rev No 3 Status P Date 2003-02-24 Cont ID  
Sent By sgraham Date 2003-02-24 Time 16:37 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-02-24 Cont ID  
Sent By lmartine Date 2003-02-24 Time 16:13 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-02-24 00:00:00APPROVED BY SHIRLEY2/24/03 LM

Review Stop Z ZONING
Rev No 1 Status F Date 2002-11-25 Cont ID  
Sent By dpalmer Date 2003-02-21 Time 15:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-11-25 00:00:00DENIED, NEED TO GO TO THE DAC BOARD