2002-12-09 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT:02101887 |
| ADD: 3177 SANTA MARGARITA RD |
| CONT: DOUBLE R BLDG CORP |
| TEL: (954)796-0777 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| A PRELIMINARY GEOTECHNICAL EVALUATION |
| SECTION 7. THE REPORT INDICATES THAT IN |
| SEC 4.3 BUILDING FOUNDATIONS: ALL FINAL |
| DESIGNS SHOULD BE BASED ON A MORE COM- |
| PREHENSIVE STUDY ONCE THE BUILDING |
| LOCATIONS AND STRUCTURAL LOADS ARE |
| FINALIZED. |
| |
| THE REPORT GIVEN TO THE CITY ALSO ISN'T |
| SIGNED NOR SEALED! |
| |
| |
| 3)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A) HORIZONTAL MULLIONS, REPORT SUBMITT- |
| ED IS FOR VERTICAL USAGE ONLY, SEE |
| LIMITATIONS. |
| B) FRONT ENTRY DOOR |
| C) FRENCH DOORS W/ GLAZING |
| D) STORM SHUTTERS MISSING KEY PLAN & |
| INSTALATION SCHEDULE |
| |
| 4)SITE SPECIFIC ENGINEERING (PRODUCT |
| APPROVAL) REQUIRES THE WET SIGNATURE, |
| DATE AND EMBOSSED SEAL OF THE ENGINEER |
| CERTIFYING THE PRODUCT AND SIGNATURE |
| AND SEAL OF THE DESIGN PROFESSIONAL |
| OF RECORD.BROWARD REPORTS REQUIRE SITE |
| SPECIFIC ENGINEERING, USING THE CRITERIA |
| SET FORTH IN W.P.B. LARGE MISSLE |
| STANDARD. BOTH THE CERTIFICATE OF |
| COMPLIANCE AND THE INSTALATION AFFIDAVAT |
| IS TO BE ON THE APPROVED FORMS PROVIDED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| 4) STORM SHUTTER SCHEDULE: |
| FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 5) TABLE 600 ZERO-LOT LINE REQUIRES THE |
| WALL TO BE 1 HR RATED, THIS INCLUDDES |
| THE GLASS BLOCK, NO INFORMATION PROVIDED |
| |
| 6) ON C1 PLAN NOTES #11 INDICATES HVHZ |
| ZONE! W.P.B. IS NOT LOCATED IN SUCH A |
| ZONE ONLY DADE/ BROWARD COUNTIES. STORM |
| SHUTTERS ARE STILL REQUIRED, 140 MPH |
| WIND ZONE. |
| |
| 7) ON C1 FRAMING NOTE # 15 SPECIFIES |
| FASTENERS FOR HIGH RIB LATH @ 6" O.C., |
| ASTM C-1063 RIB LATH SHALL BE ATTACHED @ |
| 4" O.C. (AT EACH RIB). |
| |
| 8) 2111.1.9 COUNTY AMENDMENTS/ FBC |
| REQUIRE A 1.5" RECESS (WATER STOP) |
| WHERE EXTERIOR WALL (CMU) BEAR ON A CON- |
| CRETE FLOOR SURFACE.SEE TYPICAL WALL |
| SECTIONS A-1 & A-6. |
| |
| 9) PLANS INDICATETHE USE OF A "F12" |
| FOOTING,MISSING IN SCHEDULE. |
| |
| 10) FOUNDATION SCHEDULE MISSING THE |
| FOOT & INCH DESIGNATIONS. |
| |
| 11) ROOF NAILING ZONE # 3, WHEN THE MEAN |
| ROOF HEIGHT IS GREATER THAN 25', ZONE 3 |
| REQUIRES RING SHANK NAILS. |
| |
| 12) DISCREPENCIES, PLEASE CORRECT: |
| A) DETAIL# 8 ON SHEET 7 IS INDICATED AS |
| 2ND STORY FRAMING WHILE IT IS BLOCK! |
| B) DETAIL# 9 SHEET 7 SAME AS ABOVE, |
| FRAME VS. BLOCK! |
| C) DETAIL 13 ON A-7 IS NOT INDICATED ON |
| THE FRAMING PLAN, PROBABLY SHOULD BE |
| DETAIL# 8 SHEET 7. |
| D) SHEET# 8 DETAIL 12 AS INDICATED ON |
| THE 2ND FLOOR FRAMING PLAN MISSING |
| DETAIL, DETAILS START WITH # 15. |
| |
| 13)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |