Plan Review Details - Permit 02101822
Plan Review Stops For Permit 02101822
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-01-17 Cont ID  
Sent By lsmith Date 2003-01-17 Time 10:53 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-11 Cont ID  
Sent By kstevens Date 2003-01-08 Time 18:55 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-12-11 00:00:001. ENGINEER SHOWS 13 PILINGS REQUIRED.
 NEED CONTRACT FOR PILING PLACEMENT.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-26 Cont ID  
Sent By dpalmer Date 2002-12-26 Time 05:46 Rev Time 0.25
Received By dpalmer Date 2002-12-26 Time 05:46 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-11 Cont ID  
Sent By kstevens Date 2002-12-07 Time 08:33 Rev Time 0.25
Received By dpalmer Date 2002-12-11 Time 06:29 Sent To B
Notes
2002-12-11 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR VERIFICATION OF VALUE OF WORK.
 104.6.5.
  
 2)NOTE: PLEASE NOTE, ELECTRICAL RISER
 DIAGRAM DOES NOT INCLUDE HEATER AS BEING
 INSTALLED. PLEASE PROVIDE SPECS FOR
 LISTING OF EQUIPMENT. PLEASE ALSO NOTE,
 IF HEATER HAS ELECTRICAL IGNITION,
 PLEASE SHOW WIRING ON DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2002-11-07 Time 18:24 Rev Time 0.00
Received By btrobaug Date 2002-11-07 Time 18:24 Sent To P
Notes
2002-11-07 00:00:00TO P IN BOX./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:35 Rev Time 0.00
Received By btrobaug Date   Time   Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-08 Cont ID  
Sent By kstevens Date 2003-01-08 Time 18:17 Rev Time 0.50
Received By kstevens Date 2003-01-08 Time 18:17 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2003-01-08 Cont ID  
Sent By dpalmer Date 2002-12-26 Time 05:46 Rev Time 1.50
Received By kstevens Date 2002-12-13 Time 16:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-07 Cont ID  
Sent By sgraham Date 2002-12-03 Time 11:22 Rev Time 0.50
Received By kstevens Date 2002-12-07 Time 08:19 Sent To E
Notes
2002-12-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (NOTES)
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2002-12-03 Cont ID  
Sent By sgraham Date 2002-12-03 Time 11:22 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2002-11-25 Cont ID  
Sent By sgraham Date 2002-11-25 Time 10:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-11-25 00:00:00DENIED, 2ND CK LIST, POOL NOT MEETING
 SETBACK

Review Stop Z ZONING
Rev No 1 Status F Date 2002-10-29 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-10-29 00:00:00DENIED,SETBACK SHOULD BE 10' INSTEAD
 8'