Plan Review Details - Permit 02101739
Plan Review Stops For Permit 02101739
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-11-12 Time 14:02 Rev Time 0.00
Received By rbrown Date 2003-11-07 Time 10:46 Sent To  
Notes
2003-11-07 00:00:00SHEET R1 REDLINED

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2003-10-29 Cont ID  
Sent By rbrown Date 2003-10-29 Time 16:38 Rev Time 0.00
Received By rbrown Date 2003-10-29 Time 16:38 Sent To  
Notes
2003-10-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 9/29/03:
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 10) FBC TABLE 1606.2ASHEET R1, TRUSS
 CONNECTORS/ANCHORS.
 F) ANCHOR MARK A3 (ALSO APPLIES TO
 ANCHOR MARKS A1 AND A2 BUT THEY ARE NOT
 CRITICAL).ACCCORDING TOTHE USP
 CATALOGUE THE TAPL16 SHALL HAVE
 (6)10D X 1-1/2" NAILS TO THE SEAT PLATE
 AND (13)10D NAILS TO THE TRUSS IN ORDER
 TO GENERATE IT'S MAX. ALLOWABLE
 CAPACITIES OF UPLIFT = 1350 LBS, LATERAL
 F1 = 595 LBS AND F2 = 880 LBS.THE
 SUBMITTED ANCHOR SCHEDULE CLAIMS AN
 UPLIFT CAPACITY OF 1360 LBS AND LATERAL
 LOADS OF 1105 LBS WITH ONLY (14)10D
 NAILS INTO THE TRUSS. AMEND THE SCHEDULE
 (AMEND ALSO FOR ANCHOR MARKS A4, A5 & A6
 SEE COMMENT BELOW).
 G) ANCHOR MARK A4, A5 AND A6.THE USP
 TAPL16 IS ALSO SPECIFIED, FOR THESE
 CONNECTORS, BUT USED IN COMBINATION WITH
 TA16 ANCHORS.AMEND THE SCHEDULE (SEE
 THE ABOVE COMMENT).ALSO THE USP
 CATALOGUE DOES NOT HAVE A CAPACITY TABLE
 FOR THESE ANCHORS COMBINED.JUSTIFY THE
 STATED CAPACITIES OR SPECIFIY
 ALTERNATIVE ANCHORS.
  
 32) THIS COMMMENT HAS NOT BEEN ADDRESSED
 FBC 1606.1.7THE PLANS STILL DO NOT
 STATE THE DESIGN WIND PRESSURE ON THE
 ROOF COVERING (COMPONENTS AND CLADDING)
 FOR SELECTION OF A APPROPRIATE ROOF
 COVERING SYSTEM.ANNOTATE THE PLANS.
  
 34) NOTICE OF COMMENCEMENT.SEE THE
 COMMENT ON PREVIOUS REVIEW.
  
 35) HISTORIC.SEE THE COMMENT ON
 PREVIOUS REVIEW.
  
 36) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 12:39 Rev Time 0.00
Received By rbrown Date 2003-09-29 Time 12:39 Sent To  
Notes
2003-09-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 NO BUILDING PLAN REVIEW CARRIED OUT AT
 REV. #5.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 8/12/03:
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 10) FBC TABLE 1606.2ASHEET R1, TRUSS
 CONNECTORS/ANCHORS:
 A) "MSTA 60 HURRICANE CLIPS".MSTA 60
 AND MSTA TAPL 16 ARE NOT VALID USP
 REFERENCES.ASSUMING THE INTENDED
 ANCHOR IS USP TAPL 16, THE SPECIFIED
 FASTENERS DO NOT CORRELATE WITH THE USP
 CATALOGUE AND HAVE INSUFFICIENT CAPACITY
 FOR THE UPLIFT AT THE LOCATION CALLED UP
 ON THE PLAN (DERIVED FROM
 FBC TABLE 1606.2A, ASSUMING 10 PSF DL
 FOR WIND ANALYSIS). ALSO, AMEND THE ROOF
 PLAN TO STATE THE CALCULATED UPLIFT FOR
 EACH TRUSS.DELETE OR CORRECT THE
 REFERENCE TO DADE COUNTY APPROVAL NO.
 92-0604.03
 B) "USP TRUSS ANCHOR".TAPL 16 & TA 16
 DATA IN THE 2003 USP CATALOGUE DOES NOT
 CORRELATE WITH THE 1735 LB UPLIFT OR THE
 FASTENERS STATED ON THE PLANS.AMEND
 THE PLAN TO STATE ONE TYPE OF ANCHOR AND
 STATE THE CORRECT FASTENERS AND UPLIFT
 CAPACITY.
 C) "USP ANCHOR DETAIL". THE PLAN REFERS
 TO BOTH USP TAPL 16 AND (2) USP TA 16.
 NEITHER ONE, WHEN CHECKED IN THE USP
 CATALOGUE, CORRELATES WITH THE UPLIFT
 (5386 LBS) AND THE FASTENERS STATED ON
 THE PLANS.AMEND THE PLANS TO STATE THE
 CORECT REFERENCES, FASTENERS & UPLIFT
 CAPACITY.ALSO, THE DETAIL STILL REFERS
 TO HUGHES SHA-8 STRAP.AMEND THE DETAIL
 D) "USP ANCHOR DETAIL". THE PLAN REFERS
 TO BOTH USP TAPL 16 AND USP TA 16.THE
 SPECIFIED FASTENERS DO NOT CORRESPOND TO
 THE FASTENERS IN THE USP CATALOGUE.
 AMEND THE PLAN.
 E) "USP USC GIRDER TRUSS ANCHOR".
 AMEND THE PLAN TO SHOW WHICH USC ANCHOR
 IS TO BE USED AND TO SHOW THE
 APPROPRIATE FASTENERS.
  
 12) FBC 11-4.8.2ANNOTATE EACH OF THE
 NEW RAMPS ON THE PLANS TO VERIFY THAT
 THE SLOPE WILL NOT EXCEED 1 IN 12.
  
 26) FBC 13-103.0THE SUBMITTED ENERGY
 CODE COMPLIANCE FORM SHALL HAVE THE
 PROJECT ZIP, OWNER'S NAME AND PERMIT
 NUMBER (02101739) ADDED SHEET 1.ALSO,
 SHEET 2 MUST BE DATED BY THE PREPARER,
 SIGNED AND DATED BY THE BUILDING OWNER/
 OWNER'S AGENT, AND CERTIFIED FOR CODE
 COMPLIANCE BY THE DESIGN PROFESSIONALS
 RESPONSIBLE FOR THE ARCHITECTURAL,
 MECHANICAL, PLUMBING, ELECTRICAL AND
 LIGHTING SYSTEMS.
  
 32) THIS COMMENT HAS NOT BEEN ADDRESSED
 FBC 1606.1.7THE PLANS DO NOT STATE THE
 DESIGN WIND PRESSURE ON THE ROOF FOR
 SELECTION OF AN APPROPRIATE ROOF SYSTEM.
 ANNOTATE THE PLANS.
  
 34)713.13(2) FL. STATUTES.THE
 DESCRIBED WORKS DID NOT COMMENCE WITHIN
 90 DAYS OF RECORDING THE NOTICE OF
 COMMENCEMENT SO THE NOTICE IS VOID AND
 OF NO FURTHER EFFECT.IT SHALL BE RE-
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.
  
 35) THE PLANS SHALL BE RE-ROUTED TO
 HISTORIC PRESERVATION DIVISION BEFORE A
 PERMIT CAN BE ISSUED.
  
 36) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-08-12 Cont ID  
Sent By rbrown Date 2003-08-12 Time 17:58 Rev Time 0.00
Received By rbrown Date 2003-08-12 Time 17:58 Sent To  
Notes
2003-08-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/2/03:
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) 61G15-23.002(2)FL. ADMIN. CODE
 THE ENGINEERS LICENSE NUMBER SHALL BE
 PRINTED ON EACH SHEET.
  
 7) FBC 3401.7.1ADDITIONS TO EXISTING
 BUILDINGS.AS THE AREA OF THE ADDITION
 EXCEEDS 25% OF THE AREA OF THE EXISTING
 BUILDING, THE EXISTING BUILDING AND THE
 ADDITION SHALL BE MADE TO COMPLY WITH
 ALL, EXCEPT STRUCTURAL, REQUIREMENTS OF
 THE CODE FOR A BUILDING OF AREA EQUAL TO
 THE COMBINED AREA.THIS REQUIREMENT
 GIVES RISE TO COMMENTS 26 TO 31 BELOW.
  
 10) SHEET R1, TRUSS CONNECTORS/ANCHORS.
 THE STATED ANCHORS 'HCLH/HCRH', SHA-6'
 AND 'HD 2X' ARE ALL HUGHES REFERENCES.
 HUGHES ARE NO LONGER SUPPLIERS OF
 ANCHORS.SPECIFY ALTERNATIVE ANCHORS.
 ALSO, THE SPECIFIED UPLIFT AND FASTENERS
 FOR THE 'HETA20' TRUSS ANCHOR DO NOT
 CORRELATE TO THE UPLIFT AND FASTENERS IN
 THE 2003 SIMPSON CATALOGUE.AMEND SHEET
 R1.FINALLY, THE ROOF PLAN SHALL BE
 AMENDED TO SHOW WHAT TYPE OF ANCHOR IS
 TO BE USED IN EACH LOCATION.
  
 12) FBC 11-4.1.2(1)EXTERIOR RAMPS TO
 THE NEW HALL AND THE NEW PATIO HALL.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 AMEND THE PLANS TO SHOW THE SURFACE
 MATERIAL (PAVERS, CONCRETE, ASPHALT,
 GRASS, GRAVEL?) LEADING TO THE BASE OF
 THE RAMPS AND TO SHOW CLEAR, LEVEL
 ACCESS TO THE RAMPS FROM THE ACCESSIBLE
 PARKING AND SIDEWALK.
  
 14) PRODUCT APPROVAL DOCUMENTS:
 -DRAWING SHEET #2 OF THE STEEL STORM
 PANEL SHUTTER PRODUCT APPROVAL IS
 MISSING.ALSO, DRAWING SHEET #1 IS A
 POOR COPY AND IS NOT LEGIBLE.SUBMIT
 LEGIBLE COPPIES OF DRAWING SHEETS 1 & 2
 SEE NOTE** BELOW.
 -THE ALUMINUM SINGLE HUNG WINDOW
 PRODUCT APPROVAL NOA# 02-0612.04 IS FOR
 A SINGLE UNIT APPLICATION ONLY.SUBMIT
 A PRODUCT APPROVAL FOR AN APPROPRIATE
 STRUCTURAL MULLION FOR WINDOW TYPE B
 (KITCHEN WINDOW).SEE NOTE** BELOW.
 -THE 'GLADIATOR' O/S GLAZED STEEL
 DOOR PRODUCT APPROVAL NOA# 99-1007.01 IS
 MISSING SHEET 6 OF 7.SEE NOTE** BELOW.
 -THE MODIFIED BITUMEN ROOF SYSTEM
 PRODUCT APPROVAL NOA# 00-0331.08 SHALL
 BE MARKED TO SHOW WHICH SYSTEM TYPE IS
 TO BE USED.
 **COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP
  
 26) FBC 13-103.1.1.1SUBMIT AN ENERGY
 CODE COMPLIANCE FORM FOR THE WHOLE
 BUILDING (SEE COMMENT 7 ABOVE).THE
 FORM MUST BE SIGNED BY THE PREPARER,
 BUILDING OWNER AND THE DESIGN
 PROFESSIONALS RESPONSIBLE FOR THE
 ARCHITECTURAL, MECHANICAL, PLUMBING,
 ELECTRICAL AND LIGHTING SYSTEMS.
  
 27) FBC 1007.3ANNOTATE THE PLANS TO
 SHOW THAT THE EXISTING STAIR TREADS ARE
 MIN. 11" AND RISERS ARE MAX. 7".
  
 28) FBC 1007.4THE STAIR SHALL HAVE A
 FULL LANDING BETWEEN THE TOP RISER AND
 THE DOOR.THE DOOR AND ASSOCIATED WALL
 SHALL BE REPOSITIONED.AMEND THE PLANS
 TO SHOW THE PROPOSAL FOR COMPLIANCE.
  
 29) 1007.5THE EXISTING STAIR HANDRAIL
 SHALL BE MADE TO COMPLY WITH ALL OF THE
 REQUIREMENTS OF FBC 1007.5, INCLUDING:
 -HANDRAIL HEIGHT SHALL BE BETWEEN
 34" (36" TO ALSO COMPLY WITH FBC 1026.5)
 AND 38" ABOVE THE LEADING EDGE OF THE
 TREAD.
 -HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF THE STAIR.
 -HANDRAIL CROSS-SECTIONAL SHAPE AND
 SIZE SHALL COMPLY.
 -THE HANDRAILS SHALL EXTEND AT LEAST
 12" HORIZONTALLY BEYOND THE TOP RISER OF
 THE FLIGHT AND SHALL CONTINUE TO SLOPE
 PAST THE BOTTOM RISER FOR A DISTANCE
 EQUAL TO ONE TREAD.
 -THE HANDRAIL/GUARDING AND
 ATTACHMENTS SHALL MEET THE STRENGTH
 REQUIREMENTS OF FBC 1608.2.1.1 TO
 FBC 1608.2.2.4
  
 30) FBC 1015.3THE EXISTING STAIR
 GUARDING SHALL REJECT THE PASSAGE OF A
 4" SPHERE.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 31) FBC 2405.2 THE GLAZING IN THE SHOWER
 ENCLOSURES AND WINDOWS IN BATH# 4 & 6
 (IF THE BOTTOM EDGE OF THE GLASS IS NOT
 GREATER THAN 60" ABOVE THE STANDING
 SURFACE) IS IN A HAZARDOUS LOCATION AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 32) FBC 1606.1.7THE PLANS DO NOT STATE
 THE DESIGN WIND PRESSURE ON THE ROOF FOR
 SELECTION OF AN APPROPRIATE ROOF SYSTEM.
 ANNOTATE THE PLANS.
  
 33) FBC 3502 THE NOTES ADDED TO SHEET A3
 SHALL BE AMENDED AS FOLLOWS:
 -MASONRY WALL NOTE D REFERS TO
 ASTM C 90-75 FOR CONCRETE BLOCKS.THE
 STANDARD REFERENCED IN THE CODE IS
 ASTM C 90-90
 -DESIGN DATA NOTE A REFERS TO
 ACI 318-77 FOR STRUCTURAL CONCRETE.THE
 STANDARD REFERENCED IN THE CODE IS
 ACI 318-99
 -DESIGN DATA NOTE F REFERS TO
 ASTM A 185-73 FOR WELDED WIRE FABRIC.
 THE STANDARD REFERENCED IN THE CODE IS
 ASTM A 185-92
 -PRE-ENGINEERED WOOD TRUSSES NOTE B
 REFERS TO PALM BEACH COUNTY. THIS SHOULD
 BE CITY OF WEST PALM BEACH.
 -WOOD FRAMING NOTE D REFERS TO
 STANDARD BUILDING CODE.THIS SHOULD BE
 FLORIDA BUILDING CODE
  
 34) 713.13(2) FL. STATUTES.THE
 DESCRIBED WORKS DID NOT COMMENCE WITHIN
 90 DAYS OF RECORDING THE NOTICE OF
 COMMENCEMENT SO THE NOTICE IS VOID AND
 OF NO FURTHER EFFECT.IT SHALL BE RE-
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.
  
 35)HISTORIC PRESERVATION DIVISION
 STAMPED THE PLANS AS 'APPROVED' ON
 10/28/02.THE PLANS HAVE BEEN THROUGH
 A NUMBER OF REVISIONS SINCE THEN.WHEN
 THE REVISED PLANS HAVE BEEN PASSED BY
 THE CONSTRUCTION SERVICES DEPARTMENT
 THEY SHOULD BE TAKEN, TOGETHER WITH THE
 STAMPED 'OLD' PLANS, FOR REVIEW AND
 RE-STAMPING BY HISTORIC PRESERVATION
 DIVISION.
  
 36) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-05-05 Cont ID  
Sent By rbrown Date 2003-05-02 Time 15:02 Rev Time 0.00
Received By rbrown Date 2003-05-02 Time 15:02 Sent To  
Notes
2003-05-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/19/03:
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) 61G15-23.002(2)FL. ADMIN. CODE.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE ENGINEER'S NAME AND
 ADDRESS HAVE BEEN 'TAPED' ON THE PLAN
 SHEETS.THIS IS NOT APPROPRIATE FOR
 PERMITTING AND RECORD RETENTION PURPOSES
 (FBC* 104.2.1.3).PRINT THE DETAILS ON
 THE PLANS.PLANS SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER SHALL INCLUDE THE
 NAME AND ADDRESS OF THE ENGINEER AS WELL
 AS THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING
 BUSINESS, IF APPROPRIATE.
  
 4) FBC 434.2ASSISTED LIVING FACILITY.
 THE PLANS NOW CONFIRM THE APPROPRIATE
 OCCUPANCY AND THE BUILDING COMES UNDER
 THE ABOVE SPECIAL OCCUPANCY DEFINITION.
 SEE COMMENTS 22, 23 AND 24, BELOW FOR
 ADDITIONAL REQUIREMENTS FOR THIS USAGE.
  
 7) FBC 3401.7.1ADDITIONS TO EXISTING
 BUILDINGS.THIS COMMENT HAS NOT BEEN
 ADDRESSED.FROM THE EXISTING AND NEW
 FLOOR AREAS GIVEN ON SHEET A2, THE AREA
 OF THE ADDITION EXCEEDS 25% OF THE AREA
 OF THE EXISTING BUILDING.IF THE
 EXISTING BUILDING AND THE ADDITION ARE
 NOT SEPARATED BY A 4-HOUR FIRE WALL,
 BOTH THE EXISTING BUILDING AND THE
 ADDITION SHALL BE MADE TO COMPLY WITH
 ALL THE REQUIREMENTS OF THE CODE FOR A
 BUILDING OF AREA EQUAL TO THE COMBINED
 AREA OF THE ADDITION AND THE EXISTING
 BUILDING.SUBMIT FURTHER PLANS,
 INCLUDING THE EXISTING BUILDING, TO
 DEMONSTRATE COMPLIANCE.
  
 9) SHEET A3, GENERAL STRUCTURAL NOTES.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.CORRECT NOTE 1 TO READ
 "....AS AMENDED BY THE CITY OF WEST PALM
 BEACH"
  
 10) SHEET A3, TRUSS CONNECTOR/ANCHOR
 SCHEDULE AND NOTES.ANCHOR A-3 IS
 SPECIFIED WITH 7-16D NAILS AND A MAXIMUM
 UPLIFT OF 1060 LBS.THIS DOES NOT
 REFLECT THE USP CATALOGUE REQUIREMEMENT
 FOR 13-10D NAILS TO THE TRUSS PLUS
 6-10D X 1-1/2 NAILS TO THE SEAT PLATE.
 ALSO, ANCHOR B-5 IS SPECIFIED AS RTF OR
 RTP (NOT LEGIBLE). THIS IS AN INCOMPLETE
 OR INCORRECT USP REFERENCE.RE-SPECIFY
 AS NECESSARY AND PROVIDE A LEGIBLE
 SCHEDULE.
  
 12) FBC 11-4.1.2(1)EXTERIOR RAMPS TO
 THE NEW HALL AND THE NEW PATIO HALL.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 AMEND THE PLANS TO SHOW THE SURFACE
 MATERIAL (PAVERS, CONCRETE, ASPHALT,
 GRASS, GRAVEL?) LEADING TO THE BASE OF
 THE RAMPS AND TO SHOW CLEAR, LEVEL
 ACCESS TO THE RAMPS FROM THE ACCESSIBLE
 PARKING AND SIDEWALK.
  
 14) PRODUCT APPROVAL DOCUMENTS.THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED.
 PRODUCT APPROVALS HAVE BEEN SUBMITTED AS
 LOOSE SHEETS IN NON-NUMERICAL ORDER.
 ALSO, THE DOOR PRODUCT APPROVAL IS
 EXPIRED.PROVIDE TWO COPIES OF VALID
 (NON-EXPIRED) PRODUCT APPROVALS.THE
 SHEETS IN EACH PRODUCT APPROVAL SHALL
 BE COLLATED AND STAPLED, AND THE
 RELEVANT PRODUCTS/COMPONENTS SHALL BE
 CIRCLED OR OTHERWISE HIGHLIGHTED.
  
 THE FOLLOWING ARE NEW COMMENTS ARISING
 FROM REVIEW OF THE REVISED PLANS:
  
 22) FBC 434.4.3.1A MINIMUM OF 35 SQFT
 OF LIVING AND DINING SPACE SHALL BE
 PROVIDED FOR EACH RESIDENT, LIVE-IN
 STAFF MEMBER AND LIVE-IN FAMILY MEMBER.
 AMEND THE PLANS TO CLEARLY SHOW HOW THIS
 REQUIREMENT IS TO BE MET.
  
 23) FBC 434.4.3.2A ROOM, SEPARATE FROM
 RESIDENT'S BEDROOMS, SHALL BE PROVIDED
 FOR LEISURE TIME ACTIVITIES.AMEND THE
 PLANS TO CLEARLY SHOW HOW THIS
 REQUIREMENT IS TO BE MET.
  
 24) FBC 434.4.3.3THE DINING AREA SHALL
 BE FURNISHED TO ACCOMMODATE COMMUNAL
 DINING.AMEND THE PLANS TO CLEARLY
 SHOW HOW THIS REQUIREMENT IS TO BE MET.
  
 25) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-02-19 Cont ID  
Sent By nmccray Date 2003-04-29 Time 14:55 Rev Time 0.00
Received By rbrown Date 2003-02-19 Time 10:03 Sent To  
Notes
2003-02-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 ***NOTE:***
 A NUMBER OF THE COMMENTS FROM THE
 PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED.
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/4/02:
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) 61G15-23.002(2)FL. ADMIN. CODE.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 PLANS SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER SHALL INCLUDE THE
 NAME AND ADDRESS OF THE ENGINEER AS WELL
 AS THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING
 BUSINESS, IF APPROPRIATE.
  
 4) FBC 311.2THE STATED R2 OCCUPANCY
 IS INCORRECT.PLANNING AND ZONING HAVE
 ADVISED THAT THEIR APPROVAL WAS BASED
 ON GROUP HOME OCCUPANCY WHICH WOULD BE
 R4 RESIDENTIAL.ALSO, THE CURRENT
 OCCUPATIONAL LICENSE (SUMMARY SHEET
 ATTACHED) IS FOR ADULT CONGREGATE LIVING
 FACILITY (ACLF) WHICH IS A GROUP HOME
 AND SO R4 RESIDENTIAL OCCUPANCY.AMEND
 THE PLANS ACCORDINGLY.
  
 6) FBC 11-4.1.5ACCESSIBLE TOILETS AND
 BEDROOMS.THE EXTENT OF REQUIRED
 PROVISIONS WILL BE DEPENDENT UPON THE
 RESPONSE TO COMMENT 4 ABOVE.
  
 7) FBC 3401.7.1ADDITIONS TO EXISTING
 BUILDINGS.FROM THE EXISTING AND NEW
 FLOOR AREAS NOW GIVEN ON SHEET A2, THE
 AREA OF THE ADDITION EXCEEDS 25% OF THE
 AREA OF THE EXISTING BUILDING.IF THE
 EXISTING BUILDING AND THE ADDITION ARE
 NOT SEPARATED BY A 4-HOUR FIRE WALL BOTH
 THE EXISTING BUILDING AND THE ADDITION
 SHALL BE MADE TO COMPLY WITH ALL
 REQUIREMENTS OF THE CODE FOR A BUILDING
 OF AREA EQUAL TO THE COMBINED AREA OF
 THE ADDITION AND THE EXISTING BUILDING.
 SUBMIT FURTHER PLANS, INCLUDING THE
 EXISTING BUILDING, TO DEMONSTRATE
 COMPLIANCE.
  
 8) SHEET A3, GENERAL NOTES. THIS COMMENT
 HAS NOT BEEN PROPERLY ADDRESSED.ON THE
 PREVIOUSLY SUBMITTED PLAN SET, THE FIRST
 LINE OF THE FIRST NOTE HAD BEEN
 CORRECTED, BY HAND, TO READ FLORIDA
 BUILDING CODE INSTEAD OF STANDARD
 BUILDING CODE.THIS CORRECTION HAS NOT
 BEEN CARRIED OUT ON THE REVISED PLANS.
 THE SIXTH NOTE STILL REFERS TO STANDARD
 BUILDING CODE. AMEND ALL SUCH REFERENCES
 TO FLORIDA BUILDING CODE 2001.
  
 9) SHEET A3, GENERAL STRUCTURAL NOTES.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 AMEND NOTE 1 TO REFERENCE FLORIDA
 BUILDING CODE AND THE CITY OF WEST PALM
 BEACH INSTEAD OF STANDARD BUILDING CODE
 AND PALM BEACH COUNTY.
  
 10) SHEET A3, TRUSS CONNECTOR/ANCHOR
 SCHEDULE AND NOTES. THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED. THE SCHEDULE IS
 NOW LEGIBLE BUT REFERS TO 'SEMCO' WHO NO
 LONGER SUPPLY TRUSS CONNECTORS/ANCHORS.
 SPECIFY CURRENT ANCHORS.THE SCHEDULE
 NOTES STILL REFER TO ASCE 7-88 AND A
 BASIC WIND SPEED OF 110 MPH.AMEND THIS
 TO ASCE 7-98 AND 140 MPH.REVIEW THE
 SUBMITTED PLAN SETS AND AMEND ALL OTHER
 REFERENCES THAT INCORRECTLY CALL UP
 SOUTHERN BUILDING CODE, STANDARD
 BUILDING CODE, 110 MPH WIND SPEED AND
 ASCE 7-88, INCLUDING THE OCCURANCE IN
 THE LOAD SCHEDULE ON SHEET A3 WHICH
 STILL HAS NOT BEEN CORRECTED.THE ONLY
 CORRECTION THAT HAS BEEN MADE IS THE
 BASIC WIND SPEED ON THE LOAD SCHEDULE.
  
 12) FBC 11-4.1.2(1)EXTERIOR RAMPS TO
 THE NEW HALL AND THE NEW PATIO HALL.
 THE PLANS HAVE BEEN REVISED TO EXTEND
 THESE RAMPS TO ACHIEVE COMPLIANT
 GRADIENTS.AS A RESULT OF THE EXTENSION
 THE SIDEWALKS LEADING TO THE BASE OF THE
 RAMPS WILL REQUIRE ADJUSTMENT TO ALLOW
 UNRESTRICTED WHEELCHAIR ACCESS TO EACH
 RAMP.
  
 14) SHUTTER PRODUCT APPROVAL DOCUMENTS.
 THE DRAWING SUBMITTED WITH EASTERN METAL
 SUPPLY INC. SBCCI TESTING & EVALUATION
 REPORT NO. 2211 ARE NOT THE SAME SHEETS
 REFERENCED IN 6.1 SUBSTANTIATING DATA ON
 PAGE 7 OF 8. SUBMIT DRAWING SHEETS WHICH
 CORRESPOND TO THE TEST REPORT.
  
 THE FOLLOWING ARE NEW COMMENTS ARISING
 FROM REVIEW OF THE REVISED PLANS:
  
 17) FBC* 104.2.1.3TWO VERSIONS OF
 SHEET A1 WERE SUBMITTED WITH DIFFERENT
 INFORMATION ON EACH.RE-NUMBER THE
 MOST RECENT (WITH THE LANDSCAPING) TO
 DIFFERENTIATE IT FROM THE VERSION
 PREVIOUSLY SUBMITTED.
  
 18) FBC* 104.2.1.3 SHEET A2 AND SHEET A7
 (DOOR SCHEDULE) HAVE PENCIL NOTES ADDED.
 THE USE OF PENCIL IS NOT APPROPRIATE ON
 PLANS FOR PERMITTING PURPOSES.AMEND
 THE PLANS IN INK.
  
 19) SHEET D1, CONCRETE BEAM SCHEDULE.
 THE PREVIOUSLY SUBMITTED PLAN SET
 INCLUDED HANDWRITTEN NOTES FOR BEAM TYPE
 RB-3. THESE NOTES HAVE BEEN OMITTED FROM
 THE REVISED PLAN SET.
  
 20) SHEET S1, FOUNDATION PLAN.THE
 PREVIOUSLY SUBMITTED PLAN SET INCLUDED
 HANDWRITTEN NOTES SPECIFYING VERTICAL
 REBAR DOWELS ON EACH SIDE OF THE DOOR
 AND WINDOW OPENINGS.THESE NOTES HAVE
 BEEN OMITTED FROM THE REVISED PLAN SET.
  
 21) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-05 Cont ID  
Sent By rbrown Date 2002-12-04 Time 16:08 Rev Time 0.00
Received By rbrown Date 2002-12-04 Time 16:08 Sent To  
Notes
2002-12-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) 61G15-23.002(2) FL. ADMIN. CODE.
 PLANS SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER SHALL INCLUDE THE
 NAME AND ADDRESS OF THE ENGINEER AS WELL
 AS THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING
 BUSINESS, IF APPROPRIATE.
  
 4) FBC 309, 420, 434.IS THE OCCUPANCY
 GROUP I (UNRESTRAINED) INSTITUTIONAL,
 R4 ASSISTED LIVING FACILITY OR NURSING
 HOME?THE PLANS AND/OR APPLICATION FORM
 SHALL STATE WHICH OCCUPANCY CATEGORY THE
 FACILITY WILL BE USED FOR.UNTIL THIS
 INFORMATION IS PROVIDED, A FULL PLAN
 REVIEW CANNOT BE COMPLETED.
  
 5) FBC* 104.2.1.3SHEETS A1, A2, A3 AND
 A6 HAVE TEXT WHICH CANNOT BE READ DUE TO
 POOR CONTRAST/COPY QUALITY.SUBMIT
 LEGIBLE COPIES.A FULL PLAN REVIEW HAS
 NOT BEEN COMPLETED.
  
 6) FBC 11-4.1.5ACCESSIBLE TOILETS AND
 BEDROOMS.THE EXTENT OF REQUIRED
 PROVISIONS WILL BE DEPENDENT UPON THE
 RESPONSE TO COMMENT 4 ABOVE.
  
 7) FBC 104.2.1.2THE PLANS SHALL STATE
 THE FLOOR AREA AND, IF DIFFERENT, THE
 'AREA UNDER ROOF' FOR THE EXISTING AND
 THE NEW CONSTRUCTION.
  
 8) SHEET A3, GENERAL NOTES.THE FIRST
 NOTE REFERS TO THE CODE "..AS AMENDED BY
 PALM BEACH COUNTY".THIS SHOULD READ
 "..AS AMENDED BY THE CITY OF WEST PALM
 BEACH".THE FIFTH NOTE REFERS TO THE
 STANDARD BUILDING CODE AND PALM BEACH
 COUNTY AGAIN.ALL SUCH REFERENCES SHALL
 BE AMENDED.
  
 9) SHEET A3, GENERAL STRUCTURAL NOTES.
 NOTE 1 SHALL BE AMENDED TO REFERENCE
 FLORIDA BUILDING CODE AND THE CITY OF
 WEST PALM BEACH INSTEAD OF STANDARD
 BUILDING CODE AND PALM BEACH COUNTY.
  
 10) SHEET A3, TRUSS CONNECTOR/ANCHOR
 SCHEDULE NOTES.THE NOTES ARE NOT FULLY
 LEGIBLE BUT APPEAR TO MAKE REFERENCE TO
 ASCE 7-88 AND A WIND SPEED OF 110 MPH.
 THIS SHALL BE AMENDED TO ASCE 7-98 AND
 140 MPH.AMEND ALL OTHER REFERENCES TO
 SOUTHERN BUILDING CODE, STANDARD
 BUILDING CODE, 110 MPH WIND SPEED AND
 ASCE 7-88, INCLUDING THE TWO OCCURANCES
 IN THE LOAD SCHEDULE ON SHEET A3.
  
 11) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 - SHOWER WINDOWS (SCHEDULE MARK C)
 - ANY GLAZING IN THE SHOWER DOORS
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
  
 12) FBC 1013.3 & FBC 11-4.8.2EXTERIOR
 RAMPS TO THE NEW HALL AND THE NEW PATIO
 HALL.SHEETS A2 AND S1 SHOW FIVE RISERS
 WHICH IMPLIES A LEVEL CHANGE OF 34.75".
 THE PROPOSED RAMP WOULD HAVE A SLOPE
 GREATER THAN 1 IN 12.AMEND THE RAMP TO
 COMPLY.
  
 13) FBC 104.2.1.2EXTERIOR STAIR AT
 NORTH ELEVATION.IS THIS STAIR NEW
 CONSTRUCTION?SHEET A6 SHOWS IT AS PART
 OF THE EXISTING BUILDING, AND IT IS NOT
 SHOWN ON SHEET A1 AS PART OF THE NEW
 CONSTRUCTION.IS THERE A RAMP
 ASSOCIATED WITH THIS STAIR, NO DETAILS
 HAVE BEEN PROVIDED?AMEND THE PLANS TO
 CLARIFY THE PROPOSALS FOR THIS AREA.
  
 14) THE SUBMITTED SHUTTER PRODUCT
 APPROVAL NOA# 99-0318.03 EXPIRED PRIOR
 TO THE DATE OF PERMIT APPLICATION.
 SUBMIT AN NEW PRODUCT APPROVAL.
  
 15) NORTH ELEVATION WINDOW (SCHEDULE
 MARK B).THE SUBMITTED SINGLE HUNG
 WINDOW PRODUCT APPROVAL NOA# 01-0226.04
 IS APPLICABLE TO SINGLE UNIT
 APPLICATIONS ONLY (SEE LIMITATIONS ON
 SPECIFIC CONDITIONS SHEET).SUBMIT A
 NEW WINDOW PRODUCT APPROVAL OR AN
 APPROPRIATE MULLION PRODUCT APPROVAL.
  
 16) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-09-26 Cont ID  
Sent By btrobaug Date 2005-09-26 Time 15:41 Rev Time 0.50
Received By btrobaug Date 2005-09-26 Time 15:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-10-20 Cont ID  
Sent By dpalmer Date 2003-10-20 Time 10:37 Rev Time 0.50
Received By dpalmer Date 2003-10-20 Time 10:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-09-24 Cont ID  
Sent By dpalmer Date 2003-09-22 Time 19:38 Rev Time 1.00
Received By dpalmer Date 2003-09-22 Time 19:38 Sent To  
Notes
2003-09-24 00:00:00A 4X FEE THAT WAS ADDED HAS BEEN DELETE
 -ED BY KIM MCVEY PER MIKE SIZEMORE.
 UNDER CITY CODE AND FS THIS SHALL NOT
 BE DONE. FEES ARE DUE AND MUST BE PAID.
 ELECTRICAL SHALL REMAIN INJ -F- STATUS
 UNITL THAT TIME. 553.80(2)(B),
 CITY ADMINISTRATIVE CODE 104.6.2
2003-09-22 00:00:00** REDLINED OCP FOR DRYER TO BE 30A FOR
 5KW.**

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-08-19 Cont ID  
Sent By dpalmer Date 2003-08-19 Time 15:32 Rev Time 1.50
Received By dpalmer Date 2003-08-19 Time 15:32 Sent To  
Notes
2003-08-19 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES FROM LAST
 REVIEW PERTAINING TO PANEL SCHEDULE AND
 CORRELATION OF LOADS/AWG'S AND OCP.
 PLEASE SEE GEN LT ETC 20OCP ON #14,
 DRYER SHOWN AS 120V
 PLEASE SEE OVEN MICR AT 12KW W/ 40A OCP
  
 2)NOTE: PLEASE SEE PREVIOUS NOTES
 THAT LIST BATHS TO BE DEDICATED AS
 20A AND #12 AWG. 210-11C-3/ 210-52D
  
 3)NOTE: PLEASE SEE MISSING INFORMATION
 REQ'D ON TITLE BLOCK FOR ENGINEER OF
 RECORD UNDER FAC/FS 61G15-23.002/ 471
  
 PLEASE SEE LETTER ATTACHED ONCE AGAIN
 FOR FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONAL. PLEASE NOTE, A
 4X FEE FOR PLAN WILL BE ACCESSED FOR THE
 PLAN REVIEW PORTION IF COMMENTS ARE NOT
 ADDRESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE GROUNDING ELECTRODE CONDUCTOR
 IT WAS GIVEN IN NOTES AT LAST MEETING
 THIS NEEDS TO BE SIZED PER 250-66
 THIS HAS NOT BEEN CHANGED TO DATE, STILL
 SHOWS #4

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-04-11 Cont ID  
Sent By dpalmer Date 2003-04-11 Time 02:25 Rev Time 0.50
Received By dpalmer Date 2003-04-11 Time 02:25 Sent To  
Notes
2003-04-11 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM,
 SHOWS #1`S AND #3 FOR 200A DISC AND
 PANEL? PLEASE SIZE PER 310-16
  
 2)NOTE: PLEASE SEE CIRCUITS ON PANEL
 SCHEDULE/LOAD CALCS. SMALL APPL AND
 GEN LT SHOWN AT 240V? PLEASE ALSO SEE
 CIRCUITS #`S SHOWN FOR SM APPL ,, SHOWS
 TWO CIRCUITS AND SHOWS LOAD FOR THREE
 CIRCUITS?PLEASE CLARIFY
  
 3)NOTE: PLEASE SEE PLANS,ALMOST ALL
 RECEPTS AND LTS ARE SHOWN ON TWO CIRCUIT
 -S 21&28. PLEASE SEE 210-52D/210-11C3
 BATHS MAY NOT BE ON WITH OTHER CIRCUITS,
 PLEASE ALSO CLARIFY, SOME CIRCUITS ARE
 SHOWN GOING OVER TO EXISTING BLDG CROSS-
 ING OVER TO AREA WITH SEPARATE SERVICE?
 210-25 PLEASE ADJUST CIRCUITS.
  
 4)NOTE: PLEASE SEE 250-122 FOR SIZING
 OF EQUIPMENT GROUNDING CONDUCTOR FROM
 NEW MAIN TO PANEL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-24 Cont ID  
Sent By dpalmer Date 2003-02-24 Time 05:52 Rev Time 0.25
Received By dpalmer Date 2003-02-24 Time 05:52 Sent To  
Notes
2003-02-24 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. NONE WERE ADDRESSED.
  
 2)NOTE: PLEASE SEE ATTACHED LETTER PER
 FS 553.80(2)(B) FOR NEXT PLAN REVIEW.
  
 PLEASE SUBMIT COMPLETED PLANS FOR REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By dpalmer Date 2002-11-05 Time 07:33 Rev Time 0.50
Received By dpalmer Date 2002-11-05 Time 07:33 Sent To  
Notes
2002-11-05 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE PLANS SIGNED AND
 SEALED BY AN ENGINEER MUST CONTAIN
 A TITLE BLOCK W/ INFORMATION SET FORTH
 IN FAC. 61G15-23.002
  
 2)NOTE: PLEASE SHOE ALL CIRCITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE-
 (S).
  
 3)NOTE: PLEASE NOTE, SD`S REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND A
 MIN OF 3' AWAY FORM BATHROOMS.
 NFPA-72 8-1.4.1.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2003-11-06 Cont ID  
Sent By mcarsill Date 2003-11-06 Time 15:21 Rev Time 0.00
Received By mcarsill Date 2003-11-06 Time 15:21 Sent To  
Notes
2003-11-06 00:00:00APPROVED PROVISO:
  
 1) KITCHEN DOOR SHALL NOT SWING INTO
 HALLWAY. DOOR SWING IS TO BE REVERSED
 AND SHALL OPEN INWARD NOT OUTWARD AS
 DISPLAYED IN SOME SHEETS.
  
 2) STILL HAVE NOT RECEIVED PROPOSED
 EVACUATION CAPABILITY FOR THE NEW
 RESIDENTS.
  
 3) SMOKE DETECTORS ARE REQUIRED IN
 LIVING ROOMS, DENS, DAY ROOMS, ETC.
  
 4) EVERY BATHROOM DOOR SHALL BE ABLE
 TO BE UNLOCKED FROM THE OUTSIDE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2003-10-09 Cont ID  
Sent By mcarsill Date 2003-10-09 Time 17:50 Rev Time 0.00
Received By mcarsill Date 2003-10-09 Time 17:50 Sent To  
Notes
2003-10-14 00:00:001) DOOR FROM KITCHEN BLOCKS EXIT
 HALLWAY BY MORE THAN 50 PERCENT. THIS
 PROBLEM HAS BEEN PREVOUSLY DISCUSSED
 WITH THE CONTRACTOR AND SHOULD HAVE
 BEEN REVISED ON THE PLANS.
  
 2) NO EVACUATION CAPABILITY OF THE
 NEW PROPOSED RESIDENTS HAS BEEN
 PROVIDED. THIS INFORMATION HAD BEEN
 REQUESTED ON THE 4TH PLAN REVIEW.
  
 3) COULD NOT LOCATE INFORMATION WITH
 REGARDS TO SELF-CLOSING DEVICES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2003-08-27 Cont ID  
Sent By mcarsill Date 2003-08-27 Time 07:47 Rev Time 0.00
Received By mcarsill Date 2003-08-27 Time 07:47 Sent To  
Notes
2003-08-27 00:00:001) SEPARATE PLANS AND PERMITS
 REQUIRED FIRE ALARM SYSTEM REMODEL.
  
 2) SEPARATE PLANS AND PEMRITS REQUIRE
 FOR FIRE SPRINKLER REMODEL.
  
 3) ALL NEW SMOKE DETECTORS THAT ARE
 INSTALLED SHALL BE POWERED BY THE
 HOUSE ELECTRICAL SERVICE. THESE SMOKE
 DETECTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S
 REQUIREMENTS.
  
 4) ALL NEW STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES. ALL NEW
 STAIRS SHALL BE AT LEAST 44" WIDE.
  
 5) DOORS # 5 AND # 6 ARE NOT NOTED
 ON THE DOOR SCHEDULE. ALSO NO
 INFORMATION PROVIDED WITH REGARDS
 TO SELF-COSING DEVICES INSTALLED
 ON THE SLEEPING ROOM DOORS.
  
 6) ARE ANY FIRE SPRINKLERS PLANNED TO
 PROTECT THE WOOD TRUSSES.
  
 7) NO INFORMATION PROVIDED FOR INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 8) IN SOME AREAS OF THE PLANS 5/8"
 DRYWALL IS NOTED. 5/8" TYPE X DRYWALL
 IS REQUIRED.
  
 9) DOESN'T THE KITCHEN DOOR BLOCK THE
 EGRESS HALLWAY BY MORE THEN 50 %.
  
 10) PLEASE INDICATE THE EVACUATION
 CAPABILITY OF THE NEW PROPOSED
 RESIDENTS. WILL THEY BE SLOW, PROMPT
 OR IMPRACTICAL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-04-29 Cont ID  
Sent By nmccray Date 2003-04-29 Time 14:54 Rev Time 0.00
Received By nmccray Date 2003-04-29 Time 14:54 Sent To B
Notes
2003-04-29 00:00:00DENIED:
  
 NOTES AND COMMENTS FROM 1ST & 2ND PLAN
 REVIEW HAVE NOT BEEN ADDRESSED.
 (SEE ATTACHED)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT MIKE CARSILLO OR NATE
 MCCRAY AT 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-03-05 Cont ID  
Sent By mcarsill Date 2003-03-05 Time 15:03 Rev Time 0.00
Received By mcarsill Date 2003-03-05 Time 15:02 Sent To  
Notes
2003-03-05 00:00:001) DRAWINGS DO NOT PROVIDE THE REQUIRED
 INFORMATION TO PERFORM A PROPER PLAN
 REVIEW.
  
 2) PLANS DO NOT INDICATE ALL EXISTING
 FIRE AND LIFE SAFETY EQUIPMENT.
  
 3) PLANS ARE DIFFICULT TO READ IN
 SOME LOCALES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 13:35 Sent To  
Notes
2002-11-22 00:00:001) PLANS ARE DIFFICULT TO READ.
  
 2) PLEASE CLEARLY IDENTIFY ALL LIFE
 SAFETY DEVICES AND OR SYSTEMS. THE
 ELECTRICAL LEGEND INDICATES A LEGEND
 FOR SMOKE DETECTORS BUT NONE COULD
 BE LOCATED. PLEASE SHOWN THESE ON
 THE PLANS.
  
 3) PLANS NEED TO CLEARLY IDENTIFY
 THE NEW WORK THAT IS PLANNED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-10-17 Cont ID  
Sent By csiegber Date 2003-10-16 Time 16:14 Rev Time 0.00
Received By csiegber Date 2003-10-17 Time 16:02 Sent To  
Notes
2003-10-16 00:00:00TO COMM BD#23

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-10-14 Cont ID  
Sent By csiegber Date 2003-10-14 Time 12:39 Rev Time 0.00
Received By csiegber Date 2003-10-14 Time 12:39 Sent To B
Notes
2003-10-14 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 16:09 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 16:09 Sent To  
Notes
2003-09-17 00:00:00ON COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 14:47 Rev Time 0.00
Received By alange Date 2003-08-04 Time 14:47 Sent To  
Notes
2003-08-04 00:00:00TO COMM BD #43

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-01 Cont ID  
Sent By sthyng Date 2003-04-01 Time 08:07 Rev Time 0.00
Received By sthyng Date 2003-04-01 Time 08:07 Sent To  
Notes
2003-04-01 00:00:00COMM BOARD #60

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-06 Cont ID  
Sent By btrobaug Date 2003-02-06 Time 17:08 Rev Time 0.00
Received By btrobaug Date 2003-02-04 Time 17:08 Sent To  
Notes
2003-02-06 00:00:00COM BOARD #54./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 10:42 Rev Time 0.00
Received By btrobaug Date 2002-11-04 Time 10:41 Sent To  
Notes
2002-11-04 00:00:00TO COMM BOARD #22./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By sgraham Date 2002-10-31 Time 08:26 Rev Time 0.00
Received By btrobaug Date   Time   Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2005-01-27 Cont ID  
Sent By prafter Date 2005-01-27 Time 10:37 Rev Time 1.50
Received By prafter Date 2005-01-27 Time 10:37 Sent To  
Notes
2005-01-27 00:00:00ORGINAL PLANS ARE KENNETH KRUGER PE.
 SIGNED SEALED PLANS.561/434/4061.
 AS BULT PLANS TO BE SAME ENG.
 PAT RAFTER 561/805/6725 OR 805/6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-09-30 Cont ID  
Sent By pkrauss Date 2003-09-30 Time 12:49 Rev Time 0.45
Received By pkrauss Date 2003-09-30 Time 12:46 Sent To  
Notes
2003-09-30 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 AS PER NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2003-08-20 Cont ID  
Sent By pkrauss Date 2003-08-20 Time 11:27 Rev Time 0.40
Received By pkrauss Date 2003-08-20 Time 11:27 Sent To  
Notes
2003-08-20 00:00:00PLEASE PROVIDE INFORMATION ON THE
 SEPARATION BETWEEN THE BEDROOM AREAS.
 PLANS INDICATE THE WALLS HAVING A 1 HR
 FIRE RESISTANCE RATING.PLEASE PROVIDE
 FIRE DAMPERS AS PER 2001 FBC(M) 607.1.2
 OR SHOW COMPLIANCE WITH 607.1.3 #3 ITEMS
 1 THROUGH 4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-04-14 Cont ID  
Sent By pkrauss Date 2003-04-14 Time 14:29 Rev Time 0.35
Received By pkrauss Date 2003-04-14 Time 14:14 Sent To  
Notes
2003-04-14 00:00:00DENIED:
  
 COMMENTS NOT ADDRESSED FROM 1ST & 2ND
 PLAN REVIEW (SEE ATTACHED).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-02-18 Cont ID  
Sent By pkrauss Date 2003-02-18 Time 14:27 Rev Time 1.00
Received By pkrauss Date 2003-02-18 Time 14:26 Sent To  
Notes
2003-02-18 00:00:00DENIED:
  
 1.PLAN SHEET A(B)3 DETAIL 9, INDICATES
 TENANT SEPARATION.CLARIFY FIRE
 RESISTANCE RATING FOR THIS PARTITION.
 SHOULD RATING BE 1 HR OR GREATER, FIRE
 DAMPERS ARE REQUIRED AT EACH PENETRATION
 AS PER 2001 FBC(M) 607.2.1.
  
 2.AS PER 2001 FBC CHAPTER 13 SECTION
 407.1.ABCD.2.2.2 ZONES, HEATING AND
 COOLING TO EACH ZONE SHALL BE CONTROLLED
 BY INDIVIDUAL THERMOSTATIC CONTROLS
 RESPONDING TO TEMPERATURE WITHIN THE
 ZONE.A DWELLING UNIT IS CONSIDERED A
 ZONE.
  
 3.PROVIDE INFORMATION ON THE KITCHEN.
 INDICATE ANY NEW EQUIPMENT.SEPARATE
 PLANS & PERMIT REQUIRED FOR HOOD & FIRE
 SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By kstevens Date 2002-11-19 Time 17:55 Rev Time 0.45
Received By pkrauss Date 2002-11-26 Time 16:12 Sent To  
Notes
2002-11-26 00:00:00DENIED:
  
 PLANS ARE NOT CLEAR & HARD TO READ.
  
 AS PER 2001 FBC(M) 601.4, BALANCED AIR
 RETURN REQUIRED.PROVIDE RETURN AIR
 FROM ALL BEDROOM AREAS.
  
 INDICATE OCCUPANCY TYPE.
  
 PLAN SHEET A-2 INDICATES 2001 FBC &
 1997 ELEC, ENERGY, & ACCESSSIBILITY
 CODES.PLEASE REFERENCE APPLICABLE
 CODES.
  
 INDICATE ANY OF THEEXISTING WALLS
 ARE FIRE RATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-10-08 Cont ID  
Sent By kstevens Date 2003-10-08 Time 13:05 Rev Time 1.00
Received By kstevens Date 2003-10-08 Time 13:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-08-19 Cont ID  
Sent By kstevens Date 2003-08-19 Time 13:02 Rev Time 1.50
Received By kstevens Date 2003-08-19 Time 13:01 Sent To  
Notes
2003-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) 61G15023.002(2) SEE ATTACHED SHEET.
 ENGINEERS SHALL HAVE THEIR LICENSE NUM-
 BER ON EACH SHEET. (IN TITLE BLOCK)
 2) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUPS SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SEC 909.1
 SEE ATTACHED SHEET FOR RISER DIAGRAM
 THAT MEETS CODE REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-04-18 Cont ID  
Sent By kstevens Date 2003-04-18 Time 10:55 Rev Time 1.75
Received By kstevens Date 2003-04-18 Time 10:54 Sent To  
Notes
2003-04-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 AMEND. DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEWS. SHT A5 PLEASE
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR BOTH THE OLD
 AND NEW ROOFS. (NEW PARAPET HEIGHT
 EFFECTS BOTH ROOFS.) SHOW SQUARE FOOTAGE
 FOR ALL ROOFS, INCLUDING 1/2 AREA OF ALL
 VERTICAL WALLS AND ANY AREA OF ROOFS
 THAT DRAIN ONTO THE ROOFS FROM ABOVE.
 SEE SECTIONS 1106 & 1107.
 2) NOW THAT USAGE AND OCCUPANCY IS CLEAR
 THE FAIR HOUSING ACT SHALL BE ENFORCED.
 PLEASE SHOW COMPLIANCE WITH REQUIREMENTS
 1 THRU 7. SPECIFY "A" OR "B" TYPE BATH-
 ROOMS. SHOW ALL BACKING PER REQUIREMENT
 #6. SHOW ALL CLEAR FLOOR SPACE ON FLOOR
 PLAN. SHOW ALL PROPER DIMENSIONS FOR
 FIXTURES INCLUDING HEIGHT, CENTER OF
 FIXTURE TO WALL ECT.
 4) WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-02-07 Cont ID  
Sent By kstevens Date 2003-02-07 Time 17:26 Rev Time 1.75
Received By kstevens Date 2003-02-07 Time 17:25 Sent To  
Notes
2003-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: SHT A5 PLEASE
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR BOTH THE OLD
 AND THE NEW ROOFS. (NEW PARPET HEIGHT
 EFFECTS BOTH ROOFS). SHOW SQUARE FOOTAGE
 FOR ALL ROOFS INCLUDING 1/2 AREA OF ALL
 VERITCAL WALLS AND ANY AREA OF ROOFS
 THAT DRAIN ONTO THE FOOFS FROM ABOVE.
 SEE SECTIONS 1106 & 1107.
 2) WILL THIS BE AN ASSISTED LIVING
 RESIDENCE?
 3) ALL BATHROOMS SHALL COMPLY WITH
 CHAPTER 11 OF THE FBC-2001.
 4) WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-19 Cont ID  
Sent By kstevens Date 2002-11-19 Time 17:37 Rev Time 3.00
Received By kstevens Date 2002-11-19 Time 17:37 Sent To M
Notes
2002-11-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 34
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) PLANS DO NOT HAVE SUFFICENT CLAIRITY
 AND DETAIL TO INDICATE THE NATURE AND
 CHARACTER OF THE WORK BEING DONE. PLANS
 ARE SMUGED AND HARD TO READ. PLEASE SUB-
 MIT PLANS THAT ARE CLEAR AND READABLE.
 SEC 104.2.1
 2) SHT A2 APPLICABLE CODES ARE FBC-2001
 NOT AS STATED ON PLANS.
 3) SHT A5 PLEASE SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINS FOR BOTH
 THE OLD AND NEW ROOFS. (NEW PARAPET
 HEIGHT EFFECTS BOTH ROOFS). SHOW SQUARE
 FOOTAGE FOR ALL ROOFS INCLUDING 1/2 AREA
 OF ALL VERTICAL ROOFS AND ANY AREA OF
 ROOFS THAT DRAIN ONTO ROOFS FROM ABOVE.
 SECTION 1106 & 1107
 4) PLEASE INDICATE THE NUMBER OF OCCU-
 PANTS TO BE HOUSED AT THE FACILITY AND
 SUBMIT CALCULATIONS FOR PLUMBING FACIL-
 ITIES REQUIRED. SECTION 434.4.5.1.
 5) PLEASE SUBMIT AN EXISTING FLOOR PLAN
 TO DETERMINE EXISTING FACILITIES.
 6) SHT EP1 PLUMBING NOTES #7, AIR CHAMB-
 ERS ARE NOT APPROVED. DELETE REFERENCE.
 7) PLEASE SUBMIT DETAILS FOR BATHROOMS
 PER SECTION 434.4.5.3. SHOW ALL GRAB
 BARS REQUIRED FOR SHOWERS OR TUBS AND
 FOR WATER CLOSETS.
 8) SECTION 434.4.3.1 REQUIRES A MINIMUM
 LIVING & DINING SPACE OF 35 SQ FT PER
 RESIDENT, LIVE IN STAFF, & LIVE IN FAM-
 ILY MENBERS. PLEASE INDICATE ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-31 Cont ID  
Sent By sgraham Date 2002-10-31 Time 08:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To I
Notes
***NONE***