Plan Review Details - Permit 02101251
Plan Review Stops For Permit 02101251
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-05-07 Cont ID  
Sent By jwitmer Date 2003-05-07 Time 11:21 Rev Time 0.55
Received By jwitmer Date 2003-05-07 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2003-05-06 Time 11:31 Rev Time 0.75
Received By jwitmer Date 2002-11-07 Time 11:08 Sent To  
Notes
2002-11-07 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02101251
 ADDRESS: 4431 EMBARCADERO DR
 CONT: MIKE MOORE
 TELL # (561)775-3447
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-11-05 Cont ID  
Sent By jwitmer Date 2002-11-05 Time 14:52 Rev Time 1.00
Received By jwitmer Date 2002-11-05 Time 14:52 Sent To  
Notes
2002-11-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02101251
 ADD: 4431 EMBARCADERO DR
 CONT: MIKE MOORE
 TEL: (561)723-9147 STEVE BRANDON
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS SUBMITTED BY THE ARCHITECT ARE
 COPIES, NOT SIGNED NOR SEALED, FL ADDMIN
 ISTRATIVE CODE 61G1-16.001 ALL PLANS,
 REPORTS SPECIFICATIONS ISSUED BY THE
 ARCHITECT AND FILED FOR PUBLIC RECORD
 SHALL ACQUIRE A SEAL.
 2) 61G1-16.003 DOCUMENTS SHALL BE SO
 SIGNED PERSONALLY AND SEALED BY THE
 RESPONSIBLE ARCHITECT.
 3) 61G1-16.004(6)
 A SPACE FOR THE PRINTED NAME OF THE PER-
 SON SEALING THE DOCUMENT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-22 Cont ID  
Sent By jwitmer Date 2002-10-22 Time 09:17 Rev Time 1.25
Received By jwitmer Date 2002-10-22 Time 09:17 Sent To  
Notes
2002-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02101251
 ADD: 4431 EMBARCADERO
 CONT: MIKE MOORE
 TEL: (561)775-3447
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) THE LETTER FROM OLIVER & GLIDEN
 INDICATES THAT THE EXISTING 1-HR RATED
 CEILING GRID & TILE ARE TO BE REPLACED.
 NO INFORMATION ON THE RATING OF THE GRID
 NOR TILE HAS BEEN SUBMITTED. NEITHER IS
 INFORMATION SUBMITTED ON THE LIGHT FIX-
 TURES IF THE CANS ARE 1 HR RATED OR IF
 RATED ENCLOSERES ARE TO BE USED. SEE
 705.1.1 FIRE RATED ASSEMBLIES, 705.6 FOR
 PENETRATION OF HORIZONTAL ASSEMBLIES,
 AND 705.6.2 MEMBRANE PENETRATIONS.
  
 4)705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED. INDICATE HOW CEILING TILE IS
 TO BE HELD IN PLACE, ACCESS TO AREA
 ABOVE THE CEILING, ETC?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-05-06 Cont ID  
Sent By btrobaug Date 2003-05-06 Time 11:16 Rev Time 1.08
Received By btrobaug Date 2003-05-06 Time 10:51 Sent To B
Notes
2003-05-06 00:00:00 
 NOT ENOUGH INFORMATION FOR REVIEW
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT THERE IS AN ELECTRICAL
 PERMIT REQUIRED FOR THE SCOPE OF WORK
 INDICATED ON THE DRAWING.
  
 AT THE TIME OF APPLICATION THE
 ELECTRICAL CONTRACTOR SHALL SUBMIT
 PANEL SCHEDULES AND ADDED LOADS FOR THE
 PANELS OF ORIGIN,AND INDICATE THE
 AMPERAGE RATINGS OF SAME,INDICATE THAT
 ALL CONTINUOUS LOADS ARE CALCULATED AT
 125%.ALSO INDICATE THE BRANCH CIRCUIT
 NUMBERS ON THE FLOOR AND CEILING PLAN.
  
 NO ELECTRICAL WORK IS TO BE PERFORMED
 PRIOR TO OBTAINING A PERMIT PER 101.4.3
 CWPB AMMENDMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 11:09 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 11:09 Sent To B
Notes
2003-04-28 00:00:00JW DESK