Plan Review Details - Permit 02100663
Plan Review Stops For Permit 02100663
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-01-07 Cont ID  
Sent By hpiskura Date 2003-01-07 Time 17:51 Rev Time 0.00
Received By hpiskura Date 2003-01-07 Time 17:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-12 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 12:43 Rev Time 0.00
Received By hpiskura Date 2002-12-12 Time 10:23 Sent To  
Notes
2002-12-12 00:00:00REVISION DATED 11/18/02 A2

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-13 Cont ID  
Sent By jwitmer Date 2002-11-13 Time 12:50 Rev Time 0.13
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-28 Cont ID  
Sent By jwitmer Date 2002-10-28 Time 12:45 Rev Time 1.00
Received By jwitmer Date 2002-10-28 Time 12:45 Sent To  
Notes
2002-10-28 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02100663
 ADD: 1817 S DIXIE HWY
 CONT: TROPICAL CONCRETE RESTORATION
 TEL: (561)848-4767
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 2)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. INDICATE HANDICAPPED RESTROOMS
  
 3)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-12-24 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 12:43 Rev Time 0.25
Received By dpalmer Date 2002-12-24 Time 12:43 Sent To B
Notes
2002-12-24 00:00:00TO JIM WITMER

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-20 Cont ID  
Sent By kstevens Date 2002-12-17 Time 17:13 Rev Time 0.25
Received By dpalmer Date 2002-11-20 Time 05:52 Sent To  
Notes
2002-11-20 00:00:00NOTES REDLINED ON PLANS.
 CIRCUITING FOR EM LTS AND EXT LTS 700-12
 -E.
 MAX OCP FOR AHU/HEAT 5KW SHOWN AT 2P60A
 NOTED PER NAMEPLATE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-13 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 16:52 Rev Time 1.00
Received By dpalmer Date 2002-11-13 Time 11:16 Sent To  
Notes
2002-11-13 00:00:00************* PROVISO/NOTES ***********
  
 1)NOTE: PLEASE NOTE, LOAD CALCUALTIONS
 AND PANEL SCHEDULES NEED TO CORRELATE
 FOR A/C LOADS. ONE SHOWN AT 5KW AND THE
 OTHER AT 10KW.
  
 2)NOTE: PLEASE NOTE PLANS ALSO NEED TO
 BE RE-PRINTED, SIGNED , DATED AND SEALED
 BY ENGINEER OF RECORD. 471.025
  
  
 PLEASE CORRELATE AND REVISE ALL PLANS
 AND SUBMIT FOR REVIEW BEFORE ANY ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-17 Cont ID  
Sent By dpalmer Date 2002-10-17 Time 07:00 Rev Time 0.50
Received By dpalmer Date 2002-10-17 Time 07:00 Sent To  
Notes
2002-10-17 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE MISSING RECEPT FOR
 A/C COND UNIT. 210-63
  
 2)NOTE: PLEASE CLARIFY METER LOCATION,
 NO MORETHAN 8' OF UNPROTECTED CONDUCTORS
 INSIDE BLDG. 230-70 LOCAL AMENDMENTS.
  
 3)NOTE: PLEASE NOTE THAT GROUNDING ELEC-
 -TRODE SYSTEM SHOWS GOING TO CONCRETE
 ENCASED ELECTRODE, PLEASE NOTE IF
 SHOWN THEN ONE WOULD HAVE TO BE INSTALL-
 ED? PLEASE NOTE IF EXISTING BLDG, THEN
 CUTTING/CHIPPING OUT STEEL IS NOT REQ`D
 ONLY WHERE AVAILABLE PER 250-50.
  
 4)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE.
 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-06 Cont ID  
Sent By mcarsill Date 2002-12-06 Time 15:07 Rev Time 0.00
Received By mcarsill Date 2002-12-06 Time 15:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-10-23 Cont ID  
Sent By mcarsill Date 2002-10-23 Time 15:52 Rev Time 0.00
Received By mcarsill Date 2002-10-23 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 17:00 Rev Time 0.00
Received By btrobaug Date 2002-12-05 Time 17:00 Sent To P
Notes
2002-12-05 00:00:00IN BOX"P"./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-19 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 16:52 Rev Time 0.00
Received By btrobaug Date 2002-11-19 Time 16:52 Sent To E
Notes
2002-11-19 00:00:00TO DVP./WRT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-05 Cont ID  
Sent By pkrauss Date 2002-12-05 Time 13:15 Rev Time 0.25
Received By pkrauss Date 2002-12-05 Time 12:57 Sent To  
Notes
2002-12-05 00:00:00O.A. CALCS ON PLAN APPROVED 11-6-02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-06 Cont ID  
Sent By pkrauss Date 2002-11-06 Time 15:11 Rev Time 0.30
Received By pkrauss Date 2002-11-06 Time 15:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-29 Cont ID  
Sent By pkrauss Date 2002-10-29 Time 14:48 Rev Time 0.40
Received By pkrauss Date 2002-10-29 Time 14:48 Sent To  
Notes
2002-10-29 00:00:00DENIED:MECHANICAL PERMIT 02100699
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
  
 INDICATE LOCATION SIZE & MATERIAL OF
 OUTSIDE AIR DUCT.
  
 PROVIDE ENERGY CALCS AS PER 2001 FBC
 CHAPTER 13
  
 INDICATE TERMINATION OF CONDENSATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-17 Cont ID  
Sent By kstevens Date 2002-12-17 Time 17:13 Rev Time 0.25
Received By kstevens Date 2002-12-17 Time 17:13 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-02 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 17:00 Rev Time 0.50
Received By kstevens Date 2002-12-02 Time 16:46 Sent To  
Notes
2002-12-02 00:00:00BATHROOM EXISTING - TOILET AND LAV
 BEING MOVED FOR ADA COMPLIANCE