Plan Review Details - Permit 02100598
Plan Review Stops For Permit 02100598
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-05 Cont ID  
Sent By btrobaug Date 2003-03-05 Time 18:32 Rev Time 0.50
Received By btrobaug Date 2003-03-05 Time 18:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-24 Cont ID  
Sent By dpalmer Date 2002-10-24 Time 06:42 Rev Time 0.25
Received By dpalmer Date 2002-10-24 Time 06:42 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 18:16 Rev Time 0.00
Received By btrobaug Date 2002-11-20 Time 18:16 Sent To R
Notes
2002-11-20 00:00:00TO ROBBIE M./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By jleech Date 2002-10-21 Time 20:17 Rev Time 0.33
Received By jleech Date 2002-10-21 Time 20:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By jleech Date 2002-10-21 Time 20:17 Rev Time 0.25
Received By jleech Date 2002-10-21 Time 20:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-11-25 Cont ID  
Sent By rmcdouga Date 2002-11-25 Time 11:48 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-25 00:00:00BUILDING PROVISO
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE OUTSWING DOOR WITH ONE SIDELITE
  
 3) SUBMIT REVISED STORM PANEL
 INSTALLATION SCHEDULE.
  
 4) SUBMIT REVISED SHEET A-1 INDICATING
 THE TRANSOM WINDOW ABOVE THE (2) SH26
 WINDOWS IN THE LIVING ROOM AS SHOWN ON
 THE RIGHT SIDE ELEVATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 18:16 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-14 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BEARING TEST REPORT
 FROM A SOIL ENGINEER, INDICATING THE
 MINIMUM SAFE BEARING VALUE OF THE SOIL.
 SEE CITY OF WPB AMENDMENTS TO THE 2001
 FBC SECTION 1804.2.2.
  
 3) PLEASE CLARIFY THE "USP" HUG 26
 TRUSS HANGER SPECIFIED ON SHEET S-2.
 THERE IS NO CONNECTOR LISTED IN THE USP
 CATALOG WITH THIS DESIGNATION.
  
 4) THE ROOF SHEATHING NAILING ZONE FOR
 THE GABLE AT THE FRONT ENTRY IS ZONE 3.
 PLEASE REVISE THE DIAGRAM ON SHEET S-2
 TO INDICATE THIS.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - HORIZONTAL STRUCTURAL MULLIONS
 - SINGLE OUTSWING DOOR WITH ONE SIDELITE
 (THE ONE SUBMITTED IS FOR A DOOR WITH
 TWO (2) SIDELITES ONLY AS SHOWN ON THE
 APPROVED DRAWINGS.
 - SLIDING GLASS DOORS
  
 6) THE STORM PANEL INSTALLATION SCHEDULE
 CONTAINS ERRORS. PLEASE CORRECT.
  
 7) THE ELEVATIONS INDICATE A TRANSOM
 WINDOW ABOVE THE (2) SINGLE HUNG WINDOWS
 IN THE LIVING ROOM. THIS IS NOT
 INDICATED ON THE FLOOR PLAN ON A-1.
 PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-18 Cont ID  
Sent By sgraham Date 2002-10-18 Time 08:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***