Plan Review Details - Permit 02100206
Plan Review Stops For Permit 02100206
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 08:34 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 08:34 Rev Time 0.50
Received By btrobaug Date 2002-11-04 Time 08:07 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-11 Cont ID  
Sent By kstevens Date 2002-10-09 Time 18:47 Rev Time 0.25
Received By btrobaug Date 2002-10-11 Time 10:50 Sent To B
Notes
2002-10-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE LOAD CALC'S SHOWING
 EXISTING AND ALL NEW LOADS BEING ADDED
 TO THE SERVICE.
 ALSO PLEASE INDICATE THE AMPEREAGE
 RATING OF THE EXISTING SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 15:55 Rev Time 0.00
Received By btrobaug Date 2002-10-30 Time 15:38 Sent To P
Notes
2002-10-30 00:00:00TO PLUMB. IN BOX./WRT

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-01 Cont ID  
Sent By kstevens Date 2002-11-01 Time 18:18 Rev Time 1.00
Received By kstevens Date 2002-11-01 Time 18:18 Sent To  
Notes
2002-11-01 00:00:00FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
  
  
 FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-09 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 15:56 Rev Time 0.00
Received By kstevens Date 2002-10-09 Time 18:43 Sent To E
Notes
2002-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 2) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-08 Cont ID  
Sent By sgraham Date 2002-10-08 Time 08:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***