Plan Review Details - Permit 02100015
Plan Review Stops For Permit 02100015
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 16:11 Rev Time 1.00
Received By btrobaug Date 2002-11-20 Time 15:39 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-24 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 15:38 Rev Time 0.50
Received By btrobaug Date 2002-10-24 Time 07:05 Sent To R
Notes
2002-10-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS,AND RESUBMIT FOR REVIEW:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE RISER DIAGRAM DOES NOT SHOW THE
 MAIN DISCONNECT REQUIRED BY 230-70 NEC
 & 230-70(A) CWPB AMMENDMENTS.
  
 A) ALSO NOTE THAT IF THE MAIN IS TO BE
 LOCATED IN THE PANEL,THE #6 EQ. GND.
 MUST BE REMOVED PER 250-24(A)(1).
  
 3} THE NOTE REGARDING LOAD CALCS SHOULD
 REFER TO 220-30 INSTEAD OF 230-30.
  
 4} PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250-50(A),(B) &
 (C),REFERENCE FOOTER STEEL.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 6} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 7} PLEASE NOTE KITCHEN COUNTERTOP
 RECEPTACLES MUST COMPLY WITH
 210-8(A)(6)GFI'S.
  
 8} NOTE GARAGE RECEPTACLES AS GFI PER
 210-8(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R.(BILL) TROBAUGH
 ELECTRICAL PLANS REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 15:38 Rev Time 0.00
Received By btrobaug Date 2002-11-19 Time 15:38 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By jleech Date 2002-10-19 Time 06:52 Rev Time 0.33
Received By jleech Date 2002-10-19 Time 06:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-05 Cont ID  
Sent By kstevens Date 2002-12-05 Time 18:10 Rev Time 0.50
Received By kstevens Date 2002-12-05 Time 18:09 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-10-19 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 16:22 Rev Time 0.25
Received By jleech Date 2002-10-19 Time 06:52 Sent To  
Notes
2002-10-19 00:00:00NO RISER DIAGRAM. NO PLUMBING REVIEW
 DONE.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-12-09 Cont ID  
Sent By rmcdouga Date 2002-12-09 Time 18:48 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-09 00:00:00BUILDING PROVISO
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
 - SINGLE HUNG WINDOWS (COMPLETE &
 LEGIBLE COPIES TO BE SUBMITTED)
 - SHEET 3 OF SINGLE OUTSWING STEEL DOOR
 TO BE SUBMITTED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-10-24 Time 12:02 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-06 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 4) SPECICFY THE MAXIMUM SPACING OF THE
 VERTICAL WALL REINFORCEMENT.
  
 5) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE A SOIL BEARING TEST, SIGNED AND
 SEALED BY A FL SOIL ENGINEER.
  
 6) THE TYPICAL WALL SECTION ON SHEET 1
 INDICATES R-19 INSULATION AND THE ENERGY
 CALCULATIONS LIST R-30. PLEASE CORRECT.
  
 7) SPECIFY ON THE PLANS THAT THE BOTTOM
 OF THE FOOTER SHALL BE A MINIMUM OF 12
 INCHES BELOW FINISH GRADE AND THE LOWEST
 BUILDING FLOOR ELEVATION AT PERIMETER OF
 MONOLITHIC FOUNDATION AT HABITABLE AREAS
 SHALL BE A MINIMUM OF 4 INCHES ABOVE
 FINISH GRADE. FBC 1804.1.3 AND CITY OF
 W.P.B. AMENDMENTS 1804.1.7.
  
 8) INDICATE THE INTERNAL PRESSURE
 COEFFICENT ON THE PLANS.SEE FBC 1606.1.7
  
 9) THE FRONT (EGRESS) DOOR IS REQUIRED
 TO PROVIDE A CLEAR OPENING OF NOT LESS
 THAN 32 INCHES WIDE. SEE FBC 1012.1.
  
 10) PROVIDE ATTIC ACCESS OPENING. SEE
 FBC 2309.7.
  
 11) SPECIFY THE CEILING FINISH MATERIAL
 FOR THE COVERED PORCH AND FRONT ENTRY.
  
 12) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM. FBC CHAPTER 13
  
 13)PROVIDE (2) COPIES OF AN INSTALLATION
 SCHEDULE AND CORRESPONDING KEY PLAN FOR
 THE STORM PANELS.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS
 - SINGLE HUNG WINDOWS (THE ONE SUBMITTED
 IS MISSING SEVERAL PAGES OF DRAWINGS AND
 OTHERS ARE ILLEGIBLE)
 - SINGLE OUTSWING STEEL DOOR (MISSING
 SHEET 3 OF THE DRAWINGS)
 - ROOFING MATERIALS (ONES SUBMITTED ARE
 NOT ACCEPTABLE)
 - DOUBLE OUTSWING DOORS
 - HORIZONTAL SLIDING WINDOWS
 - SLIDING GLASS DOORS
 - GLASS BLOCK
 - ARCHED FIXED GLASS WINDOWS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-03 Cont ID  
Sent By sgraham Date 2002-10-03 Time 14:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***