Plan Review Details - Permit 02091705
Plan Review Stops For Permit 02091705
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-05-16 Cont ID  
Sent By dpalmer Date 2003-05-16 Time 06:19 Rev Time 0.25
Received By dpalmer Date 2003-05-16 Time 06:19 Sent To  
Notes
2003-05-16 00:00:00NOTES REDLINED,
 NO EQUIPMENT GROUNDING CONDUCTOR UNTIL
 AFTER FIRST MEANS OF DISC. 250-24
 MOVE SD INTO BEDROOM. OTHER SIDE OF
 HEADER IN DOORWAY. NFPA-72

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-05 Cont ID  
Sent By shernand Date 2003-05-14 Time 15:29 Rev Time 0.50
Received By btrobaug Date 2003-02-05 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 10:34 Rev Time 0.33
Received By dpalmer Date 2003-01-30 Time 10:33 Sent To  
Notes
2003-01-30 00:00:00SEE NOTES REDLINED ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-22 Cont ID  
Sent By dpalmer Date 2002-10-22 Time 06:17 Rev Time 0.50
Received By dpalmer Date 2002-10-22 Time 06:17 Sent To B
Notes
2002-10-22 00:00:00*********** NOTES REDLINED***********
  
 1)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN DISC AND PANEL.
 SIZE PER 250-122
  
 2)NOTE: SD NOT PERMITTEDIN KITCHEN,
 TO BE 3'MIN. NFPA-72 8-1.4.1.6
  
 3)NOTE: PLEASE NOTE CONDUIT BETWEEN MAIN
 AND PANEL TO BE SIZED PER NEC TABLES
 MIN 2".
  
 PLEASE REVISE PLANS BEFORE ROUGH.
 IF THERE ARE NAY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 15:29 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 15:29 Sent To E
Notes
2003-05-14 00:00:00DP DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By kstevens Date 2002-10-16 Time 18:16 Rev Time 0.33
Received By hmoser Date 2002-10-19 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-16 Cont ID  
Sent By kstevens Date 2002-10-16 Time 18:16 Rev Time 0.25
Received By kstevens Date 2002-10-16 Time 18:16 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-10-28 Cont ID  
Sent By lhatten Date 2002-10-28 Time 11:18 Rev Time 2.50
Received By lhatten Date 2002-10-25 Time 11:17 Sent To  
Notes
2002-10-28 00:00:00REVIEW & STAMPED PLANS 10/25/2002
 CALC. FEES & PRINT CARD 10/28/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By sgraham Date 2002-10-07 Time 09:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved