Plan Review Details - Permit 02091647
Plan Review Stops For Permit 02091647
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-21 Cont ID  
Sent By dpalmer Date 2002-10-21 Time 16:21 Rev Time 0.50
Received By dpalmer Date 2002-10-21 Time 16:21 Sent To B
Notes
2002-10-21 00:00:00REDLINED LOCATION FOR BATH RECEPTS PER
 210-52D
  
  
 DEWEY PALMER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-08 Cont ID  
Sent By dpalmer Date 2003-01-08 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2003-01-08 Time 15:11 Sent To B
Notes
2003-01-08 00:00:00TO ROBERT MCDOUDAL'S DESK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-19 Cont ID  
Sent By kstevens Date 2002-10-16 Time 18:05 Rev Time 0.50
Received By hmoser Date 2002-10-19 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-03 Cont ID  
Sent By pschmitz Date 2002-12-03 Time 10:37 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-12-03 00:00:00REVISION, APPR. PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-16 Cont ID  
Sent By kstevens Date 2002-10-16 Time 18:05 Rev Time 0.33
Received By kstevens Date 2002-10-16 Time 18:05 Sent To M
Notes
2002-10-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM, LAUNDRY SINK
 SHALL NOT DRAIN THRU WET VENTED BATHROOM
 SEC 909.1/909.2.SECOND FLOOR RISER
 DOES NOT REFLECT FLOOR PLAN. TUB TO BE
 ON LEFT SIDE OF WATER CLOSET. (SEE SHT
 1 OF 6 FOR RED LINE CORRECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-01-09 Cont ID  
Sent By rmcdouga Date 2003-01-09 Time 14:50 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-01-09 00:00:00PROVISO ITEMS #3 AND #4 OK 1-9-02

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-10-28 Cont ID  
Sent By rmcdouga Date 2002-10-28 Time 13:02 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-28 00:00:00***********BUILDING PROVISO*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3) SUBMIT A DETAILED DRAWING OF THE
 REINFORCING STEEL PLACEMENT FOR THE
 CANTILEVERED FOR THE CANTILEVERED BEAMS
 AT THE COVERED REAR PORCH. INDICATE THE
 DISTANCE THE STEEL AND HOOPS ARE TO
 EXTEND BACK INTO THE 8 X 12 TIEBEAM ON
 THE EXTERIOR WALLS.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE
 RECTANGULAR FIXED GLASS WINDOWS AND THE
 TOMBSTONE SHAPED FIXED GLASS WINDOWS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-01 Cont ID  
Sent By sgraham Date 2002-10-01 Time 11:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***