Plan Review Details - Permit 02091576
Plan Review Stops For Permit 02091576
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-10 Cont ID  
Sent By btrobaug Date 2002-10-10 Time 10:43 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-10 Cont ID  
Sent By kstevens Date 2002-10-09 Time 11:53 Rev Time 0.25
Received By btrobaug Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-31 Cont ID  
Sent By kstevens Date 2002-10-31 Time 18:46 Rev Time 0.25
Received By kstevens Date 2002-10-31 Time 18:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-09 Cont ID  
Sent By kstevens Date 2002-10-09 Time 11:53 Rev Time 0.00
Received By kstevens Date 2002-10-09 Time 11:53 Sent To E
Notes
2002-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. AND NSPI-5
 2) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-03 Cont ID  
Sent By sgraham Date 2002-10-03 Time 11:10 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***