Plan Review Details - Permit 02091414
Plan Review Stops For Permit 02091414
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-04 Cont ID  
Sent By btrobaug Date 2002-10-01 Time 10:12 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By btrobaug Date 2002-10-17 Time 15:58 Rev Time 0.50
Received By btrobaug Date 2002-10-17 Time 15:40 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-01 Cont ID  
Sent By btrobaug Date 2002-10-01 Time 09:34 Rev Time 1.00
Received By btrobaug Date 2002-10-01 Time 06:44 Sent To B
Notes
2002-10-01 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND MAKE NECESSARY
 CORRECTIONS ON PLANS.
  
 1} PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66.THE NOTE ON
 THE GROUNDING ELECTRODE SYSTEM IN
 UNACCEPTABLE FOR REVIEW. PLEASE PROVIDE
 DETAILS OF THE GES.
  
 2} THE LOADCENTER PANEL SCHEDULE FOR
 PANEL "L" INDICATES 12 SPACES,YET PANEL
 "L" LOAD CALCULATION INDICATES MORE
 LOADS NOT LISTED IN THE SCHEDULE.PLEASE
 CORRELATE.
  
 3} IT IS UNCLEAR WHAT THE PURPOSE OF THE
 EXISTING METER FEEDING THE EXISTING 100
 AMP DISCONNECT IS.IF THE NEW METER IS
 FEEDING THE NEW PANEL "L" WHAT IS THE
 EXISTING DISCONNECT FEEDING? PLEASE
 CLARIFY AND CORRELATE THE RISER
 DIAGRAM, LOAD CALCS,NUMBER & LOCATION
 OF PANELS,ETC.
  
 4} ON THE RISER DIAGRAM IT APPEARS THAT
 THE NEW METER IS BEING FED FROM THE OLD
 METER,PLEASE CLARIFY.IF THERE IS ANOTHER
 BUILDING BEING FED FROM THIS SERVICE,
 SHOW GROUNDING AND DISCONNECTING MEANS
 AT THAT LOCATION.
  
 5} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By pkrauss Date 2002-10-17 Time 16:43 Rev Time 0.35
Received By pkrauss Date 2002-10-17 Time 16:42 Sent To  
Notes
2002-10-17 00:00:00MECH PERMIT 02091419

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-28 Cont ID  
Sent By btrobaug Date 2002-10-17 Time 15:58 Rev Time 0.50
Received By hmoser Date 2002-09-28 Time 07:26 Sent To  
Notes
2002-09-28 00:00:00PLAN/DENIED
 1) NO ENERGY CACULATIONS
 2) REFER TO SECTION 601.4 BALANCED
 RETURN AIR FBC(M) 2001
 3) NEED MODEL NUMBER OF EVAP.COIAL
 4) REFER TO SECTION 610.1.ABC.3.5.2
 AIRHANDLING UNIOTS CHAPTOR 13 FL.
 ENERGY CODE 2001
 PLAN REVIEW BY HAROLD MOSER
 (651)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-10-04 Cont ID  
Sent By lsmith Date 2002-10-04 Time 11:56 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2002-10-04 Cont ID  
Sent By lsmith Date 2002-10-04 Time 11:57 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***