Plan Review Stops For Permit 02091195 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2003-04-17 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2003-04-17 |
Time |
11:00 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-04-17 00:00:00 | ELECTRICAL REVISIONS WILL BE REQUIRED | | FOR TRACK LIGHTING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-01-28 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2003-01-28 |
Time |
13:34 |
Sent To |
|
|
Notes |
2003-01-28 00:00:00 | S SHEETS REV 1 DATED 12/6/02. | | SHOW THE FLOOR DESIGN LOADS FOR THE | | ELEVATED DISPLAY AREAS.SEE FBC 104.2. | | | | A SHEETS REV 3 DATED 11/02. | | | | SHOW HOW THE ELEVATED DISPLAY AREAS WILL | | BE ACCESSED, (EGRESS) SEE FBC 104.2. | | | | THE ADDITIONAL 800 +/- SQUARE FEET OF | | AREA ARE SUBJECT TO IMPACT FEES | | COLLECTED BY THE COUNTY.THE REVISED | | PLANS MUST BE STAMPED BY THAT OFFICE | | AND A COPY OF THE PAID RECEIPT ATTACHED | | TO THE PLAN BEFORE CONSTRUCTION | | APPROVALS CAN BE GRANTED.CALL | | 561-233-5025 FOR MORE INFORMATION. | | | | THE ADDITIONAL PERMIT FEES ARE DUE TO | | THE CITY FOR THE ADDED CONTRACT VALUE | | OF THE WORK. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-12-05 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-12-04 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
drunnels |
Date |
2002-12-04 |
Time |
10:50 |
Sent To |
|
|
Notes |
2002-12-04 00:00:00 | BEFORE THE PERMIT MAY BE ISSUED, THE | | IMPACT FEES MUST BE PAID TO THE COUNTY | | AND THE PLANS STAMPED BY THAT OFFICE. | | | | A COPY OF THE RECORDED NOTICE OF | | COMMENCEMENT MUST BE PROVIDED TO THE | | CITY. | | | | A THIRD SET OF PLANS FOR THE RESIDENT IN | | SPECTOR IS REQUIRED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-10-23 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-10-23 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-10-22 |
Time |
12:07 |
Sent To |
Z |
|
Notes |
2002-10-23 00:00:00 | THE BUILDING DATA INFORMATION ON SHEET | | SP-1 IS NOT CLEAR.THE FLOOR AREAS | | CITED DO NOT AGREE WITH FBC TABLE 500 | | FOR TYPE IV CONSTRUCTION.WILL THE | | BUILDING BE FIRE SPRINKLERED?THE FIRE | | SPRINKLER PLANS NOTED ON THE COVER | | SHEET ARE NOT INCLUDED WITH THESE PLANS. | | | | THIS PLAN REVIEW ASSUMES A TYPE IV FIRE | | SPRINKLERED BUILDING WAS INTENDED. | | | | SHOW THE METHOD OF VENTILATION FOR THE | | REPAIR GARAGE IN ACCORDANCE WITH FBC | | 411.5.5. | | | | THE AREAS SHOWN AS "DELIVERY" AND | | "SERVICE" CANOPIES ARE BUILDING AREA | | AND NOT CANOPIES AS PROVIDED FOR IN FBC | | 3106.2. (>15' PROJECTION)AS SUCH THEY | | ARE SUBJECT TO SPRINKLER REQUIREMENTS | | AND TABLE 600, PARTICULARLY THE WEST | | ELEVATION.PLEASE REVISE AS NECESSARY. | | | | ON CONSTRUCTION OF THIS NATURE, (TILT | | SLAB), THE BUILDING OFFICIAL WILL | | REQUIRE A RESIDENT INSPECTOR.CONTACT | | DON NEELY AT 561-659-8096 X 8333 FOR | | MORE INFORMATION. | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | ISSUED, IMPACT FEES MUST BE PAID TO THE | | COUNTY, THE PERMIT PLANS STAMPED BY | | THAT OFFICE AND A COPY OF THE PAID | | RECEIPT ATTACHED TO THE PERMIT | | APPLICATION.CALL 561-233-5025 FOR | | MORE INFORMATION. | | | | IF PRODUCT TEST REPORTS FOR THE DOORS, | | WINDOWS AND ROOF COVERING ARE NOT | | INCLUDED WITH THIS PERMIT APPLICATION, | | A SEPARATE PERMIT AND FEES WILL BE | | REQUIERED FOR THAT PORTION OF THE WORK. | | | | SHOW HOW THE GLAZED PORTIONS OF THE | | EXTERIOR ENVELOPE WILL RESIST HURRICANE | | MISSILE IMPACT.SEE FBC 1606.1.4. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-01-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-23 |
Time |
07:27 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-01-23 |
Time |
07:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-11-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-11-14 |
Time |
15:59 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2002-11-14 |
Time |
15:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-10-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-10-03 |
Time |
10:26 |
Rev Time |
2.00 |
Received By |
dpalmer |
Date |
2002-10-03 |
Time |
10:23 |
Sent To |
|
|
Notes |
2002-10-03 00:00:00 | *************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE PLANS NEED TO BE | | COMPLETED FOR SUFFICIENT REVIEW. | | PLEASE NOTE THERE ARE MANY ITEMS THAT | | MISSINGAND/OR DO NOT CORRELATE. | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
N |
Date |
2002-11-07 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-11-07 |
Time |
15:34 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-11-07 |
Time |
15:34 |
Sent To |
|
|
Notes |
2002-11-07 00:00:00 | N/A | | 1. SEE # 02110492 FOR UNDERGROUND | | UTILITIES PERMIT. | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI` |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2002-10-09 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-10-09 |
Time |
14:01 |
Rev Time |
5.00 |
Received By |
mamini |
Date |
2002-10-09 |
Time |
14:01 |
Sent To |
|
|
Notes |
2002-10-09 00:00:00 | FAILED: | | 1. PLEASE PROVIDE STORM WATER | | CALCULATIONS FOR THE PROPOSED SITE. | | 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT | | 3. PERMIT FORM F.D.O.T, FOR DISCHARGING | | INTO THE 70' DRAINAGE EASEMENT MUST BE | | OBTAINED. | | 4. ANY WORK WITHIN PUBLIC R.O.W WOULD | | REQUIRE PERMIT FOM PALM BEACH COUNTY & | | CWP PUBLIC UTILITIES 659-8040. | | 5. ALL PARKING STALLS MUST BE PAINTED | | WITH DOUBLE 4" STRIPE, SEE ARCHITECTURAL | | DWG. SP-2. | | 6. ALL CONNECTION TO CITY SERVICES MUST | | APPROVED BY CWP PUBLIC UTILITIES, | | 659-8040 | | 7. FOR THE INSTALLATION/INSPECTION AND | | SIZE OF THE PROPOSED OIL/WATER SEPARATOR | | CONTACT RODNEY COMPO, 837-4051 EXT. 4074 | | 8. * PLEASE NOTE THAT A SEPARATE PERMIT* | | * APPLICATION AND FEES FOR THE* | | * UNDERGROUND UTILITIES/ SITE WORKS * | | * IS REQUIRED. * | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2003-01-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-01-24 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-01-24 |
Time |
11:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-11-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-11-14 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-11-14 |
Time |
14:12 |
Sent To |
|
|
Notes |
2002-11-14 00:00:00 | 1) IT APPEARS THAT A FIRE HYDRANT IS | | MISSING FROM THE PARKING AREA. PLEASE | | REVIEW PREVIOUS PLANS FOR THE LOCATION | | OF THE SECOND FIRE HYDRANT. | | | | 2) THE SIX INCH GATE VALVE LOCATED NEAR | | THE 8X6 TEE SHALL BE AN INDICATING TYPE | | VALVE. | | | | 3) A KNOX-BOX WILL BE REQUIRED. | | | | 4) PROVIDE SEPARATE PLANS AND PERMITS | | FOR FIRE SPRINKLER AND FIRE ALARM | | SYSTEM. | | | | 5) ENSURE EMERGENCY LIGHTING THROUGHOUT. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-10-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-10-04 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-10-04 |
Time |
16:10 |
Sent To |
|
|
Notes |
2002-10-04 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO, DURING AND AFTER CONSTRUCTION. | | | | 2) PLEASE INDICATE ON PLANS HOW THE | | MOTORCYCLES WILL BE DISPLAYED IN | | SHOWROOM. PLEASE INDICATE PROPOSED | | FUEL AND BATTERY ARRANGEMENTS. | | | | 3) NO CHANGES OF ELEVATIONS PERMITTED | | AT EXIT DOORS. ELEVATIONS ARE TO BE THE | | SAME FOR AT LEAST THE WIDTH OF THE | | DOOR. | | | | 4) BUILDING ADDRESS REQUIRED. | | | | 5) WILL THERE BE ANY PAINTING OR WELDING | | CONDUCTED ON SITE. | | | | 6) NO FIRE SPRINKLER SYSTEM PLANS OR | | HYDRAULIC CALCULATIONS PROVIDED. | | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM SYSTEM INSTALLATION. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2002-12-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-27 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-12-27 |
Time |
12:45 |
Sent To |
|
|
Notes |
2002-12-27 00:00:00 | TO COMM BOARD #55 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-11-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-05 |
Time |
13:51 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-05 |
Time |
13:51 |
Sent To |
|
|
Notes |
2002-11-05 00:00:00 | TO COMM BOARD #19./WRT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2003-01-10 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-01-10 |
Time |
14:59 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2003-01-10 |
Time |
14:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-11-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-11-22 |
Time |
13:57 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2002-11-22 |
Time |
13:57 |
Sent To |
|
|
Notes |
2002-11-22 00:00:00 | PROVISO:MECHANICAL PERMIT 02100418 | | | | PROVIDE MANUFACTURER SUBMITTAL DATA ON | | THE ENERGY RECOVERY VENTILATOR PRIOR TO | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-10-02 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-10-02 |
Time |
16:23 |
Rev Time |
2.00 |
Received By |
hmoser |
Date |
2002-10-02 |
Time |
16:23 |
Sent To |
|
|
Notes |
2002-10-02 00:00:00 | PASS/PRIVISO | | 1) ALL DUCT,DUCT REINFORCEMENT,DUCT SAG | | SUPPORTS.TO BE INSTALLED TO SMACA | | STANDARDS | | 2) A/C DUCT IN ROOM 121 MUST HAVE | | FIRE DAMPER.REFER TO SECTION 607.1.3 | | FOR EXECPTIONS | | 3) NEED MANUFACTURER INSTRUCTIONS | | ENERGY RECOVERY VENTILATOR | | PLAN REVIEW BY HAROLD MOSER | | (561)659-8096 EXT 8390 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-11-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-11-20 |
Time |
21:45 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-11-20 |
Time |
21:44 |
Sent To |
|
|
Notes |
2002-11-20 00:00:00 | PASSED/PROVISO | | | | THERMAL EXPANSION CONTROL REQUIRED |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-10-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-10-12 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-10-12 |
Time |
09:30 |
Sent To |
|
|
Notes |
2002-10-12 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | FBC-2001 | | | | 1) SHT CIVIL 6 0F 9 OIL/WATER SEPARATOR | | DETAIL, 2 WAY CLEAN OUTS ARE REQUIRED. | | 2) FOR OIL/WATER SEPARATOR SIZE CONTACT | | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE | | MANAGER, (561) 837-4074. WASTE ORD. # | | 2938-96 | | 3) SHT LP-1 SEPARATE IRRIGATION PERMIT | | IS REQUIRED. | | 4) SHT A-1 MINIMUM FACILITIES CALLS FOR | | 3 DRINKING FOUNTAINS. 2 HI/LOW DRINKING | | FOUNTAINS ARE SHOWN WHICH COUNT AS 2. | | SEE SECTION 410.1 A WATER COOLER CAN BE | | USED AS A THIRD DRINKING FOUNTAIN. IF | | USED IT SHALL COMPLY WITH ARI-1010. | | PLEASE PROVIDE MANUFACTURE CUT SHEETS. | | 5) SHT A-1.3 DETAIL #7 LIFT PLATFORM PIT | | SHOWS A DRAIN, BUT NO PIPING IS INDICAT- | | ED OR SHOWN. PLEASE CLAIRFY. | | 6) SHT A-2 PLEASE PROVIDE CALCULATIONS | | FOR PRIMARY AND SECONDARY ROOF DRAINS. | | SHOW TOTAL SQUARE FOOTAGE OF ROOF AREA | | INCLUDING 1/2 AREA OF ALL VERTICAL WALLS | | SHOW SQUARE FOOTAGE FOR EACH ROOF DRAIN. | | SHOW LOCATION AND SIZE FOR SECONDARY | | ROOF DRAINS. | | 7) SHT A-8 FINISH SCHEDULE. THE WALLS OF | | ALL PUBLIC RESTROOMS SHALL BE LINED WITH | | A NON ABSORBENT MATERIAL TO A HEIGHT OF | | 4 FEET. SEC 1204.2 - PLEASE INDICATE THE | | PAINT TYPE FOR WALLS. | | 8) SHT A-9 DETAIL #7 WATER CLOSET SHALL | | BE SET 1'6" OFF WALL TO CENTER, NOT 1'4" | | AS SHOWN. LAV SHALL BE SET 34" TO FLOOD | | RIM LEVEL. | | 9) SHT A-9 DETAIL #14 W/C TO BE SET 1'6" | | TO CENTER OFF WALL NOT 1'4" AS SHOWN. | | 10) SHT A-10 DETAIL #16 SHOW DETAIL FOR | | BENCH PER 11-4.35.4 | | 11) SHT M-4 PLUMBING NOTES: NUMBERING | | SECQUENCE NOT CONSISTANT. #'S 10-11-12 | | REPETE. SECOND #10 REFERS TO AIR CHAMB- | | ERS WHICH ARE NOT APPROVED. PLEASE DE- | | LETE REFERENCE AND RE-NUMBER NOTES. | | 12) SHT M-4 RELIEF (T/P) VALVE DISCHARGE | | SHALL NOT BE TRAPPED. SEC 504.7.1 | | WATER HEATER REQUIRES THERMAL EXPANSION | | CONTROL. SEC 607.3.2. PLEASE SHOW ON DE- | | TAIL. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-05-06 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-10-23 |
Time |
14:14 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|