Plan Review Details - Permit 02090938
Plan Review Stops For Permit 02090938
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-01 Cont ID  
Sent By hpiskura Date 2002-10-01 Time 11:05 Rev Time 0.00
Received By hpiskura Date 2002-10-01 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-18 Cont ID  
Sent By btrobaug Date 2002-11-18 Time 15:06 Rev Time 0.50
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-19 Cont ID  
Sent By dpalmer Date 2002-09-19 Time 05:51 Rev Time 0.25
Received By dpalmer Date 2002-09-19 Time 05:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-09-25 Cont ID  
Sent By mcarsill Date 2002-09-25 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2002-09-25 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By pkrauss Date 2002-10-07 Time 14:01 Rev Time 0.40
Received By pkrauss Date 2002-10-07 Time 14:01 Sent To  
Notes
2002-10-07 00:00:00PROVISO:
  
 PLAN SHEET A-1 ROOM 133 INDICATES A NEW
 1 HR PARTITION - PLEASE NOTE DUCTWORK
 PENETRATING THIS PARTITION SHALL COMPLY
 WITH 2001 FBC(M) 607.1.2.
  
 RELOCATION OF THE AHU'S - REFERENCE
 MANUFACUTRER INSTALLATION INSTRUCTIONS
 FOR LINE SIZE SHOULD DEVELOPED LENGTH
 INCREASE BETWEEN THE AHU AND THE C.U.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By kstevens Date 2002-10-07 Time 17:12 Rev Time 0.00
Received By kstevens Date 2002-10-07 Time 17:12 Sent To  
Notes
2002-10-07 00:00:00PASSED/PROVISO - WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE NOT ON
 TOP OF DROP.