Plan Review Details - Permit 02090768
Plan Review Stops For Permit 02090768 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-11-22 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-11-22 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-11-22 |
Time |
15:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-09-20 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-09-20 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-09-20 |
Time |
12:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-11-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-11-15 |
Time |
07:04 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-11-15 |
Time |
06:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-09-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-05 |
Time |
15:07 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-09-18 |
Time |
06:13 |
Sent To |
|
|
Notes |
2002-09-18 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY PANELS "A1" AND | | "B" ARE SHOWN AS MLO AND MAIN BRKR? | | | | 2)NOTE: PLEASE NOTE, IT IS NOTED THAT | | ALL LOADS SHOWN ARE AT CONNECTED LOAD. | | PLEASE SHOW CALCS. SQ.FT/ RECEPTS/ | | AND CONTINOUS LOADS AT 125%. | | 220-3,220-10,-220-11,220-13,230-42,215-3 | | | | 3)NOTE: PLEASE CLARIFY EM LTS SHOWN AS | | NEW/RELOCATED AS CONNECTED TO LIGHTING/ | | BRANCH CIRCUIT. PER 700-12E | | | | PLEASE SEE FIRE REVIEW COMMENTS AND | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-11-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-11-13 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-11-13 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-09-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-09-17 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-09-17 |
Time |
13:02 |
Sent To |
|
|
Notes |
2002-09-17 00:00:00 | 1) SINCE THE BUILDING IS NOT FIRE | | SPRINKLER PROTECTED, DEAD-END CORRIDORS | | ARE NOT PERMITTED OVER TWENTY (20) FEET | | IN LENGTH. | | | | 2) SINCE THE BUILDING IS NOT FIRE | | SPRINKLER PROTECTED, ALL ELECTRICAL, | | MECHANICAL, AND STORAGE ROOMS ARE TO BE | | FIRE SEPARATED BY AT LEAST ONE HOUR | | WITH OPENING PROTECTIVES. | | | | 3) FIRE ALARM NOTES # 11 INDICATES | | SECURITY DEVICES TIED INTO FIRE | | ALARM SYSTEM. PLEASE BE ADVISED THAT | | OTHER REQUIREMENTS ARE TO BE MET PRIOR | | TO PLACING SECURITY DEVICES ON EXIT | | DOORS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-11-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-05 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-05 |
Time |
15:07 |
Sent To |
|
|
Notes |
2002-11-05 00:00:00 | TO COMM BOARD # 15./WRT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-10-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-10-01 |
Time |
12:57 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-10-01 |
Time |
12:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-01-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-01-08 |
Time |
09:51 |
Rev Time |
0.10 |
Received By |
kstevens |
Date |
2003-01-08 |
Time |
09:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2002-10-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-10-01 |
Time |
12:57 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-10-01 00:00:00 | NO PLUMBING PLANS SUBMITTED/EXISTING |
|
|
|