Plan Review Details - Permit 02090768
Plan Review Stops For Permit 02090768
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-22 Cont ID  
Sent By hpiskura Date 2002-11-22 Time 15:37 Rev Time 0.00
Received By hpiskura Date 2002-11-22 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-20 Cont ID  
Sent By hpiskura Date 2002-09-20 Time 14:25 Rev Time 0.00
Received By hpiskura Date 2002-09-20 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 07:04 Rev Time 0.50
Received By dpalmer Date 2002-11-15 Time 06:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-18 Cont ID  
Sent By btrobaug Date 2002-11-05 Time 15:07 Rev Time 0.50
Received By dpalmer Date 2002-09-18 Time 06:13 Sent To  
Notes
2002-09-18 00:00:00************* UNSAT ***************
  
  
 1)NOTE: PLEASE CLARIFY PANELS "A1" AND
 "B" ARE SHOWN AS MLO AND MAIN BRKR?
  
 2)NOTE: PLEASE NOTE, IT IS NOTED THAT
 ALL LOADS SHOWN ARE AT CONNECTED LOAD.
 PLEASE SHOW CALCS. SQ.FT/ RECEPTS/
 AND CONTINOUS LOADS AT 125%.
 220-3,220-10,-220-11,220-13,230-42,215-3
  
 3)NOTE: PLEASE CLARIFY EM LTS SHOWN AS
 NEW/RELOCATED AS CONNECTED TO LIGHTING/
 BRANCH CIRCUIT. PER 700-12E
  
 PLEASE SEE FIRE REVIEW COMMENTS AND
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-13 Cont ID  
Sent By mcarsill Date 2002-11-13 Time 10:25 Rev Time 0.00
Received By mcarsill Date 2002-11-13 Time 10:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-17 Cont ID  
Sent By mcarsill Date 2002-09-17 Time 13:02 Rev Time 0.00
Received By mcarsill Date 2002-09-17 Time 13:02 Sent To  
Notes
2002-09-17 00:00:001) SINCE THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED, DEAD-END CORRIDORS
 ARE NOT PERMITTED OVER TWENTY (20) FEET
 IN LENGTH.
  
 2) SINCE THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED, ALL ELECTRICAL,
 MECHANICAL, AND STORAGE ROOMS ARE TO BE
 FIRE SEPARATED BY AT LEAST ONE HOUR
 WITH OPENING PROTECTIVES.
  
 3) FIRE ALARM NOTES # 11 INDICATES
 SECURITY DEVICES TIED INTO FIRE
 ALARM SYSTEM. PLEASE BE ADVISED THAT
 OTHER REQUIREMENTS ARE TO BE MET PRIOR
 TO PLACING SECURITY DEVICES ON EXIT
 DOORS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-05 Cont ID  
Sent By btrobaug Date 2002-11-05 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2002-11-05 Time 15:07 Sent To  
Notes
2002-11-05 00:00:00TO COMM BOARD # 15./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-01 Cont ID  
Sent By pkrauss Date 2002-10-01 Time 12:57 Rev Time 0.35
Received By pkrauss Date 2002-10-01 Time 12:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-08 Cont ID  
Sent By kstevens Date 2003-01-08 Time 09:51 Rev Time 0.10
Received By kstevens Date 2003-01-08 Time 09:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-10-01 Cont ID  
Sent By pkrauss Date 2002-10-01 Time 12:57 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2002-10-01 00:00:00NO PLUMBING PLANS SUBMITTED/EXISTING