Plan Review Details - Permit 02090718
Plan Review Stops For Permit 02090718
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-05-19 Cont ID  
Sent By jwitmer Date 2003-05-19 Time 12:04 Rev Time 1.00
Received By jwitmer Date 2003-05-19 Time 12:04 Sent To  
Notes
2003-05-19 00:00:00BUILDING PROVISO
 1006.2.2 EXTERIOR STAIRWAYS
 EXTERIOR STAIRWAY (2ND STORY LANDING)
 IS REQUIRED TO BE ROOFED OVER.
 MEETS THE REQUIREMENTS OF 1027.1
 SINGLE EXIT FOR STORAGE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-04-14 Cont ID  
Sent By jwitmer Date 2003-04-14 Time 15:51 Rev Time 1.25
Received By jwitmer Date 2003-04-14 Time 15:51 Sent To  
Notes
2003-04-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02090718
 ADD: 1222 OMAR RD
 CONT: ROBERT TURSO
 TEL: (561)439-7326
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION: DENIED
  
 1) EXTERIOR STAIRS SECTION 1006.2.4
 EXTERIOR STAIRS SHALL BE SEPERATED FROM
 THE INTERIOR OF THE BUILDING BY WALLS
 WITH A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HR. WITH FIXED OR SELF CLOS-
 ING OPENING PROTECTIVES AS REQUIRED FOR
 ENTERIOR STAIRS.SEE ATACHMENT.
  
 THE APPROVED PLAN INDICATED 3 WINDOWS
 ON THE FIRST FLOOR, NO REFRENCE TO THESE
 WINDOWS BEING DELETED? 1 HR RATING.
  
 THE DOORS DIRECTLY UNDER THE STAIRS
 WILL ALSO NEED TO BE RATED 1 HR.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-12 Cont ID  
Sent By jwitmer Date 2003-02-12 Time 11:49 Rev Time 1.33
Received By jwitmer Date 2003-02-11 Time 13:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-01-02 Cont ID  
Sent By jwitmer Date 2003-01-02 Time 11:50 Rev Time 1.50
Received By jwitmer Date 2003-01-02 Time 11:50 Sent To  
Notes
2003-01-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02090718
 ADD: 1222 OMAR ROAD
 CONT: ROBERT TURSO
 TEL: (561)439-7326
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE: FIRE ZONE SEE AMENDMENTS FOR BUILD
 INGS LOCATED IN A FIRE ZONE.
  
 1) ORIGINAL COMMENT# (2).
 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 MISSING INFORMATION FOR ROOFED OVER AREA
 SHEET# 1? COMMENTS BACK INDICATE THIS IS
 TO BE A TYPE IV BUILD FULLY SPRINKLERED.
 THE PLANS INDICATE OPEN (NO WALLS) ON
 THE OPEN AREA ROOFED OVER AREA. TABLE
 600 TYPE IV BUILDINGS REQUIRE :
 0'-3' ZERO % OPENINGS, 1 HR RATED
 3'-10' 10% OPENINGS 1HR RATED EXT WALLS
  
 AS NOTED ABOVE & 1ST PLAN REVIEW, THIS
 BUILDING IS IN A "FIRE DISTRICT":
 F 102.2.6 EXTERIOR WALLS OF TYPE IV
 BUILDINGS SHALL HAVE A FIRE RESISTANCE
 OF 2HRS OR MORE WHEN SUCH WALLS ARE LOCA
 TED WITHIN 30 FT OF A COMMON PROPERTY
 LINE OR AN ASSUMED PROPERTY LINE.
  
 THE OPEN AREA HAS TO HAVE 2 HR RATED
 WALLS, DEPENDING ON THE CLOSENESS OF THE
 PROPERTY LINE IT MAY OR MAY NOT HAVE
 OPENINGS IN THE WALL. IF THE WALL IS
 ALLOWEDOPENINGS, 1 1/2 HR PROTECTIVES
 HAVE TO BE INSTALLED ON THE OPENING!!!!
  
 2) ORIGINAL COMMENT 3 WHAT TYPE OF
 CONSTRUCTION ? ANSWER "ALL"
  
 THE BUILDING IS EITHER A TYPE IV OR V?
 SEE TABLE 600, TYPE V 0'-3' REQUIRES A
 3 HR WALL.3'-10' A 2HR WITH 10% OPEN-
 INGS.
  
 3) ORIGINAL COMMENT #4 BEFORE ISSUANCE
 OF THIS PERMIT STRUCTURAL DRAWINGS FOR
 THE METAL BLDG, CALS BY THE ENGINEER
 FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS. CONTRACTORS COMMENT:
 THE METAL BLDG CALCULATIONS BY REGISTER-
 ED ENGINEERTO BE PROVIDED BEFORE ANY
 INSPECTION.
 THE METAL STRUCTURE SHALL REQUIRE A
 SEPERATE PERMIT AND THESE PLANS WOULD BE
 USED FOR REFRENCE ONLY IN REGARDS TO THE
 METAL STRUCTURE!
 THERE ARE (2) ISSUES AT HAND:
 A) SIDE WALL FIRE RATINGS OF METAL
 STRUCTURE.TYPE IV OR V!!!!!
 B) THIS BUILDING IS TO BE ENGINEERED
 FOR A 140 HPH WIND ZONE!!!!!!
  
 4) 1007.3.3 TREADS SHALL HAVE A UNIFORM
 DEPTH AND RISERS OF UNIFORM HEIGHT IN
 ANY STAIRWAY BETWEEN 2 FLOORS. THERE
 SHALL BE NO VARIATION EXCEEDING 3/16
 OF AN INCH IN RISER HEIGHT. SEE PAGE 4.
  
 5) PAGE 4 STAIRWAY, 1007.4.2. STAIRS
 SHALL HAVE FLOORS OR LANDINGS AT DOOR
 OPENINGS. FIRST FLOOR MISSING LANDING
 AND DOOR.
  
 6) 1001.1.3. MEANS OF EGRESS SHALL BE
 CONTINUOUS AND UNOBSTRUCTED PATH OF TRAV
 EL TO THE EXTERIOR OF THE BUILDING. THE
 SECOND STORY EGRESS LEAVES YOU IN THE
 BUILDING?
  
 7) MISSING ROOFING REPORT:
 A) PRODUCT TESTING FOR WIND 1504.1
 B) FIRE DISTRICT CLASS A OR B MANUFAC-
 TURER SPEC. F102.2.4./ 1505.
  
 8) COMMENT # (18)
 FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
 CONTRACTORS COMMENT N/A? IS THE FLOOR
 OF THE NEW AREA CONCRETE OR SOME OTHER
 MATERIAL?
  
 9) RESTROOM/ SHOWER 2ND FLOOR: 11-4.1.3
 IF TOLIET OR BATHING FACILITIES ARE PRO-
 VIDED ON A LEVEL NOT SERVED BY AN ELEVA-
 TOR, THEN A TOLIET OR BATHING FACILITY
 MUST BE PROVIDED ON THE ACCESSIBLE
 GROUND FLOOR.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-29 Cont ID  
Sent By jwitmer Date 2002-10-29 Time 07:39 Rev Time 3.50
Received By jwitmer Date 2002-10-29 Time 07:39 Sent To  
Notes
2002-10-29 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02090718
 ADD: 1222 OMAR ROAD
 CONT: ROBERT TURSO
 TEL: (561)439-7326
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE: FIRE ZONE SEE AMENDMENTS FOR BUILD
 INGS LOCATED IN A FIRE ZONE.
  
 1) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
  
 2) 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, DISCREPANCY, SHEET 1 FLOOR
 PLAN VS ELEVATIONS. MISSING INFORMATION
 FOR ROOFED OVER AREA SHEET 1?
  
 3) WHAT TYPE CONSTRUCTION? V, IV?
 TABLE 600 ISSUES,SEE OPEN AREAS
 TYPE V CONSTRUCTION
 0-3' ZERO % OPENINGS, 3 HR RATED WALL
 SEE 704.5 FOR REQUIRED PARPETS
 OVER 3'-10', 2HR RATED WALL, 10% ALLOWED
 OPENINGS
 TYPE IV CONSTRUCTION
 0'-3', ZERO% OPENINGS,1 HR UNPRO
 0'-3', ZERO % OPENINGS,2 HR 1 HR PRO
 OVER 3'-10' 10 % OPENINGS 1 HR WALL
  
 4) BEFORE ISSUANCE STRUCTURAL DRAWINGS
 FOR METAL BLDG, CALS BY ENGINEER SIGNED
 & SEALED.
  
 5)106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 6)106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 7) TABLE 1604.1 LIVE LOADS INDICATE
 IF 2ND FLOOR LOADS ARE 125/250 SQ FT.
  
 8) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 9)1007.5.1 STAIRS WITH A MINIMUM OF
 4 RISERS SHALL BE EQUIPPED WITH HAND-
 RAILS LOCATED NO LESS THAN 34" NOR MORE
 THAN 38" ABOVE THE LEADING EDGE OF A
 TREAD. ADDITIONAL INFORMATION ON STAIRS
 AND GUARDRAIL/ HANDRAIL.
 10)
 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 11) 1006.1.1 EXIT STAIRS BETWEEN FLOORS
 SHALL BE ENCLOSED IN OR SEPERATED BY
 FIRE RESISTANT CONSTRUCTION IN ACCORD-
 ANCE WITH 705.2 & 705.1.2. THE 2ND FLOOR
 STORAGE AREA IS A TRUE 2ND FLOOR AND NOT
 A MEZZANINE!
 IS THERE A WALL ON THE 2ND STORY
 SEPERATING THE STORAGE AREA FROM THE
 GARAGE WORKSHOP?WHAT TYPE OF WORK WILL
 OCCUR IN THE GARAGE WORKSHOP?
  
 12)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 13)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 14)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A)WINDOWS
 B) DOORS SWING/ OVERHEAD GARAGE DOORS
 C) ROOFING MATERIALS
 D) STORM PANELS/ KEY PLAN/ ANCHOR
 SCHEDULE
  
 15) ARE WINDOWS ELIMINATED IN THE 1ST
 FLOOR OFFICE AND RESTROOMS? THEY ARE NOT
 SHOWN ON 1ST FLOOR PLAN.
  
 16) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 17) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 18) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 19)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-05-22 Cont ID  
Sent By btrobaug Date 2003-05-22 Time 09:00 Rev Time 0.33
Received By btrobaug Date 2003-05-22 Time 09:00 Sent To  
Notes
2003-05-22 00:00:00ENGINEER OF RECORD SIGNED & SEALED 5/15/
 03./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-05-06 Cont ID  
Sent By dpalmer Date 2003-05-06 Time 13:38 Rev Time 0.50
Received By dpalmer Date 2003-05-06 Time 13:38 Sent To  
Notes
2003-05-06 00:00:00*********** UNSAT *****************
  
 ELECTRICAL OK, HOWEVER, PLANS ARE REQ`D
 TO BE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD AS REQ`D UNDER FS/FAC/FBC
 471.025/61G15-23.002/104.4.1.3
  
 PLEASE HAVE ENG ADDRESS ABOVE.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-04-07 Cont ID  
Sent By dpalmer Date 2003-04-07 Time 05:25 Rev Time 0.33
Received By dpalmer Date 2003-04-07 Time 05:21 Sent To  
Notes
2003-04-07 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ SUBMITTED PANEL
 SCHEDULE. CIRCUITING FOR EM/EXT LTS
 700-12E
 2)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS
 ONLY ONE CIRCUIT FOR OFFICE RECEPTS??
 220-13
  
 3)NOTE: PLEASE CLARIFY 100/20 SHOWN
 ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE SEE PANEL SCH. SHOWS A
 200A 2/P, ? FOR?
 CIRCUIT #4
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-17 Cont ID  
Sent By dpalmer Date 2002-12-17 Time 12:40 Rev Time 0.50
Received By dpalmer Date 2002-12-17 Time 12:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-07 Cont ID  
Sent By dpalmer Date 2002-10-07 Time 11:53 Rev Time 0.50
Received By dpalmer Date 2002-10-07 Time 11:53 Sent To  
Notes
2002-10-07 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS
 FOR EXIT AND EMGERGENCY LTS. 700-12
  
 2)NOTE: PLEASE PROVIDE CIRCUTIING ON
 PLANS AND CORRELATE W/ SUBMITTED PANEL
 SCHEDULE.
  
 3)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 -ING METHOD BETWEEN MAIN AND SUB-PANEL.
 SIZE PER 250-122
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS, PANELS, BRKRS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9
  
 5)NOTE: PLEASE CLARIFY SIZE FOR SERVICE
 ENTRANCE CONDUCTORS. SHOWN AS 3-3/10`S
 ? 310-16
  
 6)NOTE: PLEASE SHOW RECEPT FOR A/C UNIT
 210-63.
  
 7)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 215-3,230-42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELETRICAL PLAN REVIEW
 561-659-8096 EX8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2003-05-20 Cont ID  
Sent By nmccray Date 2003-05-20 Time 15:37 Rev Time 0.00
Received By nmccray Date 2003-05-20 Time 15:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2003-04-29 Cont ID  
Sent By nmccray Date 2003-04-29 Time 13:56 Rev Time 0.00
Received By nmccray Date 2003-04-29 Time 13:56 Sent To  
Notes
2003-04-29 00:00:001) PLEASE REF CH. 42 STORAGE OCCUPANCIES
 NFPA 101 LIFE SAFETY CODE 2000 EDITION.
  
 2) PLEASE REF CH. 7 ON OUTSIDE STAIRS
 NFPA 101 LIFE SAFETY CODE 2000 EDITION.
  
 3) PROVIDE THIS OFFICE ON WHAT WILL BE
 STORED IN THIS AREA, IS LOW, ORDINARY OR
 HIGH HAZARD.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-02-11 Cont ID  
Sent By nmccray Date 2003-02-11 Time 11:01 Rev Time 0.00
Received By nmccray Date 2003-02-11 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-02-06 Cont ID  
Sent By nmccray Date 2003-02-06 Time 13:23 Rev Time 0.00
Received By nmccray Date 2003-02-06 Time 13:23 Sent To  
Notes
2003-02-06 00:00:001) SEPARATE PERMIT APPLICATION AND FEES
 ARE REQUIRED FOR FIRE ALARM SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-19 Cont ID  
Sent By mcarsill Date 2002-12-19 Time 15:40 Rev Time 0.00
Received By mcarsill Date 2002-12-19 Time 15:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-04 Cont ID  
Sent By mcarsill Date 2002-10-04 Time 17:14 Rev Time 0.00
Received By mcarsill Date 2002-10-04 Time 17:14 Sent To  
Notes
2002-10-04 00:00:001) PLANS NEED TO CLEARLY IDENTIFY
 EXITING FROM THE BUILDING.
  
 2) PLANS NEED TO CLEARLY IDENTIFY
 ALL ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING.
  
 3) PLEASE INDICATE OCCUPANT LOADS AND
 TRAVEL DISTANCES TO EXITS.
  
 4) PLEASE INDICATE HOW THE TWO
 STRUCTURES WILL ACT AS ONE.
  
 5) PLEASE PROVIDE ADDITIONAL DETAILS
 SO A PROPER PLAN REVIEW CAN BE
 PERFORMED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-05 Cont ID  
Sent By dpalmer Date 2003-05-05 Time 10:55 Rev Time 0.00
Received By dpalmer Date 2003-05-05 Time 10:54 Sent To  
Notes
2003-05-05 00:00:00TO COMM VOARD W/ OTHER REV #8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:56 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 17:56 Sent To  
Notes
2003-05-02 00:00:00COMM BOARD #8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 16:43 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 16:43 Sent To  
Notes
2003-03-31 00:00:00TO COMM BOARD #5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 11:37 Sent To  
Notes
2003-01-27 00:00:00TO COMM BOARD #10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-06 Cont ID  
Sent By btrobaug Date 2002-12-06 Time 16:26 Rev Time 0.00
Received By btrobaug Date 2002-12-06 Time 16:26 Sent To  
Notes
2002-12-06 00:00:00TO COMM BOARD #9./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2003-02-10 Cont ID  
Sent By pkrauss Date 2003-02-10 Time 13:02 Rev Time 0.20
Received By pkrauss Date 2003-02-10 Time 13:00 Sent To  
Notes
2003-02-10 00:00:00NO MECHANICAL CHANGES - PROVISO ON
 PLAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-27 Cont ID  
Sent By pkrauss Date 2002-12-27 Time 14:38 Rev Time 0.35
Received By pkrauss Date 2002-12-27 Time 14:31 Sent To  
Notes
2002-12-27 00:00:00PROVISO:MECHANICAL PERMIT 02090802
  
 RETURN AIR DUCTS OR TRANSFER GRILLES
 REQUIRED FROM ALL "OFFICE" AREAS.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" AWAY FROMT THE BUILDING STRUCTURE
 AS PER 2001 FBC 1503.4.4.
  
 EXHAUST FROM BATHROOMS SHALL NOT
 BE DIRECTED ONTO WALKWAYS AS PER 2001
 FBC(M) 401.5.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-25 Cont ID  
Sent By pkrauss Date 2002-10-25 Time 13:14 Rev Time 0.45
Received By pkrauss Date 2002-10-25 Time 12:19 Sent To  
Notes
2002-10-25 00:00:00DENIED:MECHANICAL PERMIT 02090802
  
 PROVIDE ENERGY CALCULATIONS AS PER THE
 2001 FBC CHAPTER 13.
  
 PROVIDE OUTSIDE AIR CALCS AS PER 2001
 FBC(M) TABLE 403.7.
  
 INDICATE WHAT IS BEING "STORED" IN THE
 STORAGE AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-05-23 Cont ID  
Sent By kstevens Date 2003-05-23 Time 08:51 Rev Time 0.33
Received By kstevens Date 2003-05-23 Time 08:51 Sent To  
Notes
2003-05-23 00:00:00PASSED/PROVISO
  
 BREAK ROOM SINK SHALL COMPLY WITH SEC
 11-4.24

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-04-12 Time 11:29 Rev Time 0.33
Received By kstevens Date 2003-04-12 Time 11:29 Sent To  
Notes
2003-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 NEW SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. NEW RISER SHOWS 3
 LAVS AND NEW STACK FOR SECOND FLOOR. NEW
 REVISION REQUIRED FOR FLOOR PLAN TO RE-
 FLECT CHANGES ON SANT. RISER DIAG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-02-01 Cont ID  
Sent By kstevens Date 2003-02-01 Time 05:10 Rev Time 0.50
Received By kstevens Date 2003-02-01 Time 05:09 Sent To  
Notes
2003-02-01 00:00:00PASSED/PROVISO - WATER COOLER TO BE
 ARI-1010 COMPLIANT - MANUF. INFO AT
 FINAL

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-12-30 Cont ID  
Sent By kstevens Date 2002-12-30 Time 08:00 Rev Time 0.75
Received By kstevens Date 2002-12-27 Time 16:46 Sent To  
Notes
2002-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, PLEASE PROVIDE
 A WATER RISER DIAGRAM.
 2) FROM PREVIOUS REVIEW, PLEASE PROVIDE
 A DETAIL FOR THE DRINKING FOUNTAIN. SHOW
 COMPLIANCE WITH 11-4.15 AND ALL SUBSECT-
 IONS. ALSO SHOW PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING PER
 11-4.1.3(10)(A).
 3) FROM PREVIOUS REVIEW, PLEASE SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS AND SHOW LOCATIONS FOR EACH.
 SEE SECTIONS 1106 & 1107.ALSO ADD 1/2
 AREA FOR ALL VERTICAL WALLS.
 4) FROM PREVIOUS REVIEW, PLEASE INDICATE
 TYPE OF MATERIAL TO BE STORED ON SECOND
 FLOOR. OTHER REVIEW COMMENTS MAY RESULT
 ACCORDING TO INFORMATION GIVEN.
 5) COMMENTS BY BLDG AND FIRE REVIEWS
 WERE ANSWERED IN WRITTEN FORM, BUT NOT
 FOR PLUMBING. PLEASE INDICATE WHERE AND
 HOW COMMENTS ARE ADDRESSED FOR TIMELY
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-28 Cont ID  
Sent By kstevens Date 2002-10-28 Time 11:46 Rev Time 1.25
Received By kstevens Date 2002-10-28 Time 11:46 Sent To  
Notes
2002-10-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE PROVIDE A SANITARY AND A WATER
 RISER DIAGRAM.
 2) PLEASE PROVIDE DETAIL FOR ACCESSIBLE
 TOILET ROOM AND FOR DRINKING FOUNTAIN.
 SHOW COMPLIANCE WITH 11-4.22 AND ALL
 SUBSECTIONS. ALSO SHOW COMPLIANCE WITH
 11-4.15 AND ALL SUBSECTIONS INCLUDING
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 3) ALL SHEETS OF A SIGNED AND SEALED SET
 OF PLANS SHALL BE SIGNED AND SEALED BY
 ENGINEER/ARCHITECT OF RECORD. (SEE SHEET
 SHOWING DRINKING FOUNTAIN LOCATION)
 4) NO INFORMATION GIVEN FOR ROOF PRIMARY
 AND SECONDARY DRAINS. PLEASE SUBMIT
 CALCULATIONS FOR EACH PER 1106 AND 1107
 5) PLEASE INDICATE TYPE OF MATERIAL TO
 BE STORED ON SECOND FLOOR. OTHER REVIEW
 COMMENTS MAY RESULT ACCORDING TO INFOR-
 ATION GIVEN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-10-01 Cont ID  
Sent By sgraham Date 2002-10-01 Time 11:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-09-23 Cont ID  
Sent By sgraham Date 2002-09-23 Time 14:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-09-23 00:00:00DENIED, NEED LEVEL I PLAN REVIEW


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved