Plan Review Details - Permit 02090679
Plan Review Stops For Permit 02090679
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By hpiskura Date 2002-10-28 Time 10:29 Rev Time 0.00
Received By hpiskura Date 2002-10-28 Time 09:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-20 Cont ID  
Sent By hpiskura Date 2002-09-20 Time 12:19 Rev Time 0.00
Received By hpiskura Date 2002-09-20 Time 10:49 Sent To  
Notes
2002-09-20 00:00:00THE SIDE LIGHT SHOWN AS (C) NEAR DOOR
 201 DOES NOT COMPLY WITH FBC 705.1.3.7.
 PLEASE REVISE AS NECESSARY.
  
 TWO EXIT DOORS ARE REQUIRED FROM THIS
 SPACE IN ACCORDANCE WITH FBC 1004.1.2.
 TRAVEL DISTANCE, (NOT COMMON PATH),
 EXCEEDS 75'.SEE ALSO FBC 1004.1.4.
  
 NOTES TO DOOR 201 SPECIFY AN ELECTRIC
 DEADBOLT.THE LOCKING ARRANGEMENTS ON
 REQUIRED EXIT DOORS MUST COMPLY WITH
 FBC 1012.1.7

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-30 Cont ID  
Sent By dpalmer Date 2002-10-30 Time 06:30 Rev Time 0.50
Received By dpalmer Date 2002-10-30 Time 06:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-17 Cont ID  
Sent By dpalmer Date 2002-09-17 Time 20:15 Rev Time 0.50
Received By dpalmer Date 2002-09-17 Time 20:24 Sent To  
Notes
2002-09-17 00:00:00************* NOTE **********
  
 PLEASE SEE FIRE REVIEW COMMENTS FOR
 ANY CHANGES THAT MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE NOTE THAT ELECTRICAL PLANS SEEM
 TO OK WITHE THE EXCEPTION OF CHANGES
 THAT MAY BE MADE DUE TO FIRE REVIEW
 COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By mcarsill Date 2002-10-28 Time 16:01 Rev Time 0.00
Received By mcarsill Date 2002-10-28 Time 16:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-17 Cont ID  
Sent By mcarsill Date 2002-09-17 Time 11:56 Rev Time 0.00
Received By mcarsill Date 2002-09-17 Time 11:56 Sent To  
Notes
2002-09-17 00:00:001) IT WAS NOTED THAT DOOR 201 WILL
 BE EQUIPPED WITH AN ELECTRIC STRIKE.
 PLEASE INDICATE ON THE PLANS THAT
 ANY LOCKING DEVICES ON DOORS SHALL
 MEET THE REQUIREMENTS OF DELAYED
 EGRESS OR ACCESS CONTROLLED LOCKS.
  
 2) FIRE ALARM NOTES # 13 ADVISES THAT
 SECURITY DEVICES WILL BE TIED INTO
 FIRE ALARM SYSTEM. PLEASE REVIEW
 APPLICABLE CODE SECTIONS. OTHER CODE
 REQUIREMENTS NEED TO BE MET IF LOCKING
 DEVICES ARE TO BE INSTALLED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-02 Cont ID  
Sent By pkrauss Date 2002-10-02 Time 12:37 Rev Time 0.35
Received By pkrauss Date 2002-10-02 Time 12:22 Sent To  
Notes
2002-10-02 00:00:00MECHANICAL PERMIT 02090742

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-10-05 Cont ID  
Sent By jleech Date 2002-10-05 Time 12:39 Rev Time 0.50
Received By jleech Date 2002-10-05 Time 12:39 Sent To  
Notes
***NONE***