Plan Review Details - Permit 02090679
Plan Review Stops For Permit 02090679 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-10-28 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-10-28 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-10-28 |
Time |
09:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-09-20 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-09-20 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-09-20 |
Time |
10:49 |
Sent To |
|
|
Notes |
2002-09-20 00:00:00 | THE SIDE LIGHT SHOWN AS (C) NEAR DOOR | | 201 DOES NOT COMPLY WITH FBC 705.1.3.7. | | PLEASE REVISE AS NECESSARY. | | | | TWO EXIT DOORS ARE REQUIRED FROM THIS | | SPACE IN ACCORDANCE WITH FBC 1004.1.2. | | TRAVEL DISTANCE, (NOT COMMON PATH), | | EXCEEDS 75'.SEE ALSO FBC 1004.1.4. | | | | NOTES TO DOOR 201 SPECIFY AN ELECTRIC | | DEADBOLT.THE LOCKING ARRANGEMENTS ON | | REQUIRED EXIT DOORS MUST COMPLY WITH | | FBC 1012.1.7 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-10-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-10-30 |
Time |
06:30 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-10-30 |
Time |
06:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-09-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-09-17 |
Time |
20:15 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-09-17 |
Time |
20:24 |
Sent To |
|
|
Notes |
2002-09-17 00:00:00 | ************* NOTE ********** | | | | PLEASE SEE FIRE REVIEW COMMENTS FOR | | ANY CHANGES THAT MAY AFFECT ELECTRICAL | | PLANS. | | | | PLEASE NOTE THAT ELECTRICAL PLANS SEEM | | TO OK WITHE THE EXCEPTION OF CHANGES | | THAT MAY BE MADE DUE TO FIRE REVIEW | | COMMENTS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-10-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-10-28 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-10-28 |
Time |
16:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-09-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-09-17 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-09-17 |
Time |
11:56 |
Sent To |
|
|
Notes |
2002-09-17 00:00:00 | 1) IT WAS NOTED THAT DOOR 201 WILL | | BE EQUIPPED WITH AN ELECTRIC STRIKE. | | PLEASE INDICATE ON THE PLANS THAT | | ANY LOCKING DEVICES ON DOORS SHALL | | MEET THE REQUIREMENTS OF DELAYED | | EGRESS OR ACCESS CONTROLLED LOCKS. | | | | 2) FIRE ALARM NOTES # 13 ADVISES THAT | | SECURITY DEVICES WILL BE TIED INTO | | FIRE ALARM SYSTEM. PLEASE REVIEW | | APPLICABLE CODE SECTIONS. OTHER CODE | | REQUIREMENTS NEED TO BE MET IF LOCKING | | DEVICES ARE TO BE INSTALLED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-10-02 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-10-02 |
Time |
12:37 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-10-02 |
Time |
12:22 |
Sent To |
|
|
Notes |
2002-10-02 00:00:00 | MECHANICAL PERMIT 02090742 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-10-05 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-10-05 |
Time |
12:39 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2002-10-05 |
Time |
12:39 |
Sent To |
|
|
Notes |
|
|
|