Plan Review Details - Permit 02090615
Plan Review Stops For Permit 02090615
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-23 Cont ID  
Sent By hpiskura Date 2002-09-23 Time 13:59 Rev Time 0.00
Received By hpiskura Date 2002-09-23 Time 13:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-15 Cont ID  
Sent By btrobaug Date 2002-10-15 Time 11:29 Rev Time 1.00
Received By btrobaug Date 2002-10-15 Time 10:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-25 Cont ID  
Sent By dpalmer Date 2002-09-25 Time 06:15 Rev Time 0.50
Received By btrobaug Date 2002-09-25 Time 06:15 Sent To  
Notes
2002-09-25 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE NOTE ALL CIRCUITING NEEDS
 TO BE ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.215-5
  
 2)NOTE: PLEASE NOTE SIZING OF OCP FOR
 AHU. PER 424-3. PLEASE NOTE MIN OF 125%
 SHOWN AS 2P50 FOR 10KW?
  
 3)NOTE : PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600-5
  
 4)NOTE: PLEASE NOTE LOADS ON BRKRS ON
 PANEL SCHEDULE NEED TO CORRELATE WITH
 MAX OCP. PLEASE NOTE #12 W/ 25 BRKR?
 #6 W/ 24KW LOAD ON 2P-50 FOR X-RAY DISC.
 PLEASE NOTE X-RAY DISC IS SHOWN AS 100A
 ON PLANS??
  
 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%. PER
 215-3,230-42.
  
 6)NOTE: PLEASE CLARIFY SHOW WINDOW J-BOX
 ? WINDOW RECEPT? 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-09-25 Cont ID  
Sent By mcarsill Date 2002-09-25 Time 11:41 Rev Time 0.00
Received By mcarsill Date 2002-09-25 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-10-18 Cont ID  
Sent By kstevens Date 2002-10-18 Time 17:19 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-18 Cont ID  
Sent By kstevens Date 2002-10-18 Time 17:12 Rev Time 1.25
Received By kstevens Date 2002-10-18 Time 17:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-09-27 Cont ID  
Sent By btrobaug Date 2002-10-15 Time 11:30 Rev Time 0.00
Received By kstevens Date 2002-09-27 Time 18:28 Sent To  
Notes
2002-09-27 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE SHOW EXISTING FLOOR PLAN TO
 SHOW ALL FIXTURES THAT WILL BE DEMO'ED
 IS THERE AN EXISTING GREASE LINE?
 2) PLEASE SUBMIT A SANITARY AND WATER
 RISER DIAGRAM. SHOW ALL PIPE SIZES, VENT
 LINES, WATER HAMMER ARRESTORS ECT.
 3) A RPZ BACKFLOW SHALL BE REQUIRED FOR
 WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-19 Cont ID  
Sent By sgraham Date 2002-09-19 Time 11:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***