Plan Review Details - Permit 02090323
Plan Review Stops For Permit 02090323
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-27 Cont ID  
Sent By btrobaug Date 2003-02-27 Time 17:49 Rev Time 0.33
Received By btrobaug Date 2003-02-27 Time 17:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-25 Cont ID  
Sent By dpalmer Date 2002-09-25 Time 07:30 Rev Time 0.25
Received By dpalmer Date 2002-09-25 Time 07:30 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-21 Cont ID  
Sent By jleech Date 2002-09-21 Time 09:17 Rev Time 0.33
Received By jleech Date 2002-09-21 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-21 Cont ID  
Sent By jleech Date 2002-09-21 Time 09:17 Rev Time 0.33
Received By jleech Date 2002-09-21 Time 09:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-23 Cont ID  
Sent By rmcdouga Date 2002-10-23 Time 14:38 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-23 00:00:00BUILDING PROVISO
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR EXTERIOR OUTSWING DOOR
 WITH ONE SIDELITE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-10-09 Cont ID  
Sent By rmcdouga Date 2002-10-09 Time 09:16 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-09 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BEARING TEST REPORT
 FROM A SOIL ENGINEER,REGISTERED IN THE
 STATE OF FLORIDA, INDICATING THE MINIMUM
 SAFE BEARING VALUE OF THE SOIL PRIOR TO
 SLAB INSPECTION. SEE CITY OF WEST PALM
 BEACH AMENDMENTS TO THE 2001 FBC SECTION
 1804.2.2.
  
 4) PLEASE CLARIFY THE "USP" HUG 26
 TRUSS HANGER ON SHEET S-2. THERE IS NO
 CONNECTOR LISTED IN THE USP CATALOG WITH
 THIS DESIGNATION.
  
 5) THE ROOF SHEATHING NAILING ZONE FOR
 THE GABLE AT THE FRONT ENTRY IS ZONE 3.
 PLEASE REVISE DIAGRAM ON SHEET S-2 TO
 INDICATE THIS.
  
 6) THE FRONT ENTRY DOOR ON THE PLANS HAS
 ONLY ONE SIDELITE AND THE PRODUCT
 APPROVAL SUBMITTED IS FOR A DOOR WITH
 TWO SIDELITES ONLY. PLEASE SUBMIT A
 CURRENT PRODUCT APPROVAL FOR DOOR AS
 SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-12 Cont ID  
Sent By sgraham Date 2002-09-12 Time 11:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***