Plan Review Details - Permit 02081828
Plan Review Stops For Permit 02081828
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-01-29 Cont ID  
Sent By hpiskura Date 2003-01-29 Time 10:17 Rev Time 0.00
Received By hpiskura Date 2003-01-29 Time 09:40 Sent To  
Notes
2003-01-29 00:00:00REV #2 DATED 12/11/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-16 Cont ID  
Sent By hpiskura Date 2002-10-16 Time 14:17 Rev Time 0.00
Received By hpiskura Date 2002-10-11 Time 14:26 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-09 Cont ID  
Sent By hpiskura Date 2002-09-09 Time 14:40 Rev Time 0.00
Received By hpiskura Date 2002-09-09 Time 11:14 Sent To  
Notes
2002-09-09 00:00:00SHOW THE FIRE RATED MIXED OCCUPACCY
 SEPARATION IN ACCORDANCE WITH FBC
 704.1.1 BETWEEN THE OFFICE AREA ON THE
 EAST SIDE AND THE WAREHOUSE ON THE
 WEST.GROUP B AND GROUP S, INCLUDING
 THE DOORS.
  
 WHAT IS THE STRUCTURE "EXISTING SHED TO
 REMAIN" SHOWN ON SHEET A 2.1 AND
 ELSEWHERE?
  
 ARE THE OPENINGS TO BE CUT IN THE
 EXISTING SEPARATION WALLS TO RECEIVE
 ANY KIND OF HEADER OR LINTEL?WILL THE
 OPENING GO TO THE DECK ABOVE?PLEASE
 CLARIFY.
  
 THE ENERGY CODE CALCULATIONS ARE NOT
 SIGNED AND SEALED AND THE PLANS DO NOT
 REFLECT THE INSULATION VALUES.SEE FBC
 13-103.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 06:23 Rev Time 0.25
Received By dpalmer Date 2003-01-30 Time 06:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 07:53 Rev Time 0.50
Received By dpalmer Date 2003-01-23 Time 07:53 Sent To  
Notes
2003-01-23 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE NOTE, E-3.0 DOES NOT
 SHOW ANY REVISIONS? PLEASE CLARIFY.
 PLEASE SHOW AS CLOUDS/TRIANGLES.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-08 Cont ID  
Sent By dpalmer Date 2002-10-08 Time 19:45 Rev Time 0.50
Received By dpalmer Date 2002-10-08 Time 19:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-06 Cont ID  
Sent By dpalmer Date 2002-09-06 Time 11:21 Rev Time 2.00
Received By dpalmer Date 2002-09-06 Time 11:10 Sent To  
Notes
2002-09-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS ARE NOT
 COMPLETED FOR REVIEW. PANEL SCHEDULES
 ETC.
  
 2)NOTE: PLEASE NOTE THAT ELECTRICAL
 POWER PLANS AND RISER DIAGRAM DO NOT
 CORRELATE.
  
 3)NOTE: PLEASE NOTE SOME EQUIPMENT
 GROUNDING CONDUCTORS SHOWN BETWEEN
 GUTTER(S)/METER AND MAIN DISC`S. THIS
 IS PARALLELING THE NEUTRAL WHICH IS NOT
 PERMITTED. PLEASE SEE 250-24.
  
 4)NOTE: PLEASE CLARIFY CONDUCTORS ON
 RISER DIAGRAM. SOME SHOWN AS ALUM AND
 OTHERS AT COPPER? PLEASE NOTE AMPERAGE
 RATINGS OF ALUM CONDUCTORS PER 310-16
 SOME AREAS ON RISER MISSING CONDUCTORS/
 SIZES SHOWN.
  
  
 5)NOTE: PLEASE NOTE POWER PLAN SHOWS
 A NEW SERVICE AT ONE LOCATION AND ALSO
 SHOWS SERVICE EQUIPMENT COMING FROM
 EXISTING PANELS THAT ARE NOT SHOWN AS
 NEW?? PLEASE SEE PLASN AND CORRELATE.
  
 6)NOTE: PLEASE CLARIFY METHOD(S) FOR
 GROUNDING ELECTRODES?? 250-50
  
 7)NOTE: PLEASE CLARIFY LOAD CALCS
 SHOWING "TWO PHASE"??
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 PLEASE NOTE MAINS/PANELS/BRKRS ALL
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9
  
 PLEASE NOTE THAT WHEN PLANS ARE
 COMPLETED, A FULL REVIEW CAN ONLY THEN
 TAKE PLACE. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 PLEASE NOTE PER FS/FAC 471.025/ 61G15-
 23.002

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-02-03 Cont ID  
Sent By nmccray Date 2003-02-03 Time 13:56 Rev Time 0.00
Received By nmccray Date 2003-02-03 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-02 Cont ID  
Sent By mcarsill Date 2002-10-02 Time 10:04 Rev Time 0.00
Received By mcarsill Date 2002-10-02 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-28 Cont ID  
Sent By mcarsill Date 2002-08-28 Time 11:46 Rev Time 0.00
Received By mcarsill Date 2002-08-28 Time 11:46 Sent To  
Notes
2002-08-28 00:00:001) IS THE EXISTING BUILDING FIRE
 SPRINKLER PROTECTED.
  
 2) PLEASE INDICATE ANY FIRE SEPARATIONS
 BETWEEN MIXED OCCUPANCIES AND BETWEEN
 TENANTS.
  
 3) SINGLE TENANT OR MULTIPLE TENANTS.
  
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 5) PLEASE INDICATE WHAT THE STORAGE
 AREAS WILL BE USED FOR.
  
 6) PLEASE PROVIDE OCCUPANT LOADS.
  
 7) FIRE ALARM EQUIPMENT NEW OR EXISTING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:24 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 09:24 Sent To P
Notes
2003-04-25 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 11:26 Sent To M
Notes
2003-02-20 00:00:00TO MECH INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-02 Cont ID  
Sent By dpalmer Date 2003-01-02 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2003-01-02 Time 15:11 Sent To  
Notes
2003-01-02 00:00:00TO COMM BOARD #15

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-02-24 Cont ID  
Sent By pkrauss Date 2003-02-24 Time 13:00 Rev Time 0.50
Received By pkrauss Date 2003-02-24 Time 09:18 Sent To  
Notes
2003-02-24 00:00:00MECHANICAL PERMIT 02081834

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-01-17 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 11:26 Rev Time 0.50
Received By pkrauss Date 2003-01-17 Time 09:47 Sent To  
Notes
2003-01-17 00:00:00PROVISO:
  
 PLEASE PROVIDE SUBMITTAL OF CURBS FOR
 THE "RELOCATED" RTU'S (MINIMUM OF 8"
 FROM THE ROOF SURFACE 2001 FBC 1511.7).
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-07 Cont ID  
Sent By hmoser Date 2002-10-07 Time 18:36 Rev Time 1.00
Received By hmoser Date 2002-10-07 Time 18:36 Sent To  
Notes
2002-10-07 00:00:00PASS/PROVISO
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR FBC.(M)2001
 2) REFER TO SECTION 606 SMOKE DETECTION
 SYSTEMS CONTROL FBC(M)2001.
 WITH HORN & STROBE
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-16 Cont ID  
Sent By hmoser Date 2002-09-16 Time 12:58 Rev Time 1.00
Received By hmoser Date 2002-09-16 Time 12:58 Sent To  
Notes
2002-09-16 00:00:00PLAN DENIED
 1) NO FAN SCHEDULE FOR BATH EXHAUST
 2) NO EQUIPMENT SCHEDULE
 3) MECHANICAL PLANS PAGE 1.0 AND 1.1
 DO NOT MATCH
 4) NEED MORE INFORMATION ON PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-04-26 Cont ID  
Sent By kstevens Date 2003-04-26 Time 08:38 Rev Time 0.50
Received By kstevens Date 2003-04-26 Time 08:36 Sent To  
Notes
2003-04-26 00:00:00REVISION OK - SHOWING ORIGINAL GRAB BARS
 IN TOILET ROOMS - NEW CABINET IN LOUNGE
 SINK TO COMPLY WITH 11-4.24

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-01-29 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:24 Rev Time 0.33
Received By kstevens Date 2003-01-29 Time 10:28 Sent To  
Notes
2003-01-29 00:00:00REVISION OK - TOILET ROOM IS EXISTING -
 THEY WERE GOING TO REMOVE IT BUT NOW
 THEY WILL NOT.

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-01-18 Cont ID  
Sent By kstevens Date 2003-01-18 Time 17:01 Rev Time 0.50
Received By kstevens Date 2003-01-18 Time 17:00 Sent To  
Notes
2003-01-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A2.1 NEW TOILET ROOM DOES NOT
 MEET CODE REQUIREMENTS OF 11-4.22,
 11-4-22.3 - AN UNOBSTRUCTED TURNING
 SPACE COMPLYING WITH 11-4.2.3 SHALL BE
 PROVIDED. TOILET SHALL NOT OBSTRUCT
 TURNING CIRCLE.
 2) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM FOR NEW
 TOILET ROOM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By kstevens Date 2002-10-17 Time 14:56 Rev Time 0.25
Received By kstevens Date 2002-10-17 Time 14:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-09-16 Cont ID  
Sent By hpiskura Date 2002-10-16 Time 14:18 Rev Time 0.00
Received By kstevens Date 2002-09-16 Time 17:06 Sent To  
Notes
2002-09-16 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) 20 PERCENT OVER CONTRACT AMOUNT SHALL
 BE SPENT ON ACCESSIBLE ALTERATIONS FOR
 PRIMARY FUNCTIONS. 11-4.1.6(2) PLEASE
 PROVIDE INFORMATION SHOWING HOW THE
 $40,522.40 WILL BE SPENT FOR ACCESSIBLE
 ALTERATIONS.
 2) SHT SP-1 SHOWS OFFICE SPACE FOR JFD'S
 WAREHOUSE AND WAREHOUSE #2 BUT IT'S NOT
 SHOWN ON FLOOR PLAN. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377