Plan Review Details - Permit 02081739
Plan Review Stops For Permit 02081739
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-09 Cont ID  
Sent By btrobaug Date 2002-10-09 Time 10:43 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-10-09 00:00:00*******PROVISO************
  
 COPY OF CONTRACT TO VERIFY VALUE.IF
 DIFFERENT VALUE SHOWN FEES ARE TO BE
 ADJUSTED AND CONTRACTOR TO PAY
 DIFFERENCE BEFORE PERMIT PICKUP.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-09 Cont ID  
Sent By kstevens Date 2002-10-09 Time 09:31 Rev Time 0.50
Received By btrobaug Date 2002-10-09 Time 10:30 Sent To B
Notes
2002-10-09 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE ELECTRICAL SCHEMATIC DOES NOT
 INCLUDE A TIME CLOCK REQUIRED BY
 612.ABC.2.3.3. FLORIDA BUILDING
 CODE.THE TIME CLOCK MUST BE INSTALLED
 TO REGULATE PUMP ON/OFF TIMES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-07 Cont ID  
Sent By pschmitz Date 2002-11-07 Time 07:46 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-11-07 00:00:00REVISION APPR,PES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-09 Cont ID  
Sent By kstevens Date 2002-10-09 Time 09:31 Rev Time 0.00
Received By kstevens Date 2002-10-09 Time 09:31 Sent To E
Notes
2002-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 2) FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING. THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND RE-
 MOVAL. SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER FUN-
 CTION OF THE FILTRATION AND PIPING SYS-
 TEM. SEC 424.2.8.3 WHERE CHECK VALVES
 ARE INSTALLED THEY SHALL BE OF THE SWING
 OR VERTICAL CHECK PATTERNS. SEC 424.2.8.
 4 COMBINATION VALVES SHALL REQUIRE APP-
 ROVAL OF THE ADMINISTRATIVE AUTHORITY
 PRIOR TO THEIR INSTALLATION. VALVE MISS-
 ING FOR (1) MAIN DRAIN LINE.
 3) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-10-08 Cont ID  
Sent By sgraham Date 2002-10-08 Time 11:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***