Plan Review Details - Permit 02081554
Plan Review Stops For Permit 02081554
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:26 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 08:26 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-03-25 Cont ID  
Sent By kstevens Date 2003-03-25 Time 07:01 Rev Time 0.50
Received By kstevens Date 2003-03-25 Time 07:01 Sent To  
Notes
2003-03-25 00:00:00REVISION OK - 2 LB SYSTEM -REGULATORS -
 CHANGE RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-07 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:26 Rev Time 0.50
Received By kstevens Date 2003-03-06 Time 11:53 Sent To  
Notes
2003-03-07 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) LINE TO RANGE (180,000 BTU) IS TOO
 SMALL @ 178' DEVELOPED LENGTH. EITHER
 1-1/4" PIPE IS REQUIRED OR A 2 LB.
 SYSTEM IS REQUIRED WITH A REGULATOR AT
 THE UNION PRIOR TO ENTERING THE BLDG.
 AND AT EACH BBQ AND THE POOL HEATER.
 IF 2 LB SYSTEM USED, PLEASE PROVIDE CUT
 SHEETS FOR REGULATORS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-21 Cont ID  
Sent By pschmitz Date 2002-08-21 Time 13:47 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-08-21 00:00:00PROVISO: APPR PER JIM MUNDY. PES