Plan Review Details - Permit 02081521
Plan Review Stops For Permit 02081521
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-04 Cont ID  
Sent By ndenmark Date 2002-08-21 Time 15:29 Rev Time 2.00
Received By jwitmer Date 2002-09-04 Time 11:26 Sent To  
Notes
2002-09-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02081521
 ADD: 651 OKEECHOBEE BLVD/ SUITE 100
 CONT: CONSOLIDATED METAL WORK INC
 TEL: (954)484-8108
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ******PROVISO*******
  
  
 1) MECHANICAL EQUIPMENT HUNG FROM THE
 ROOF BAR JOIST SHALL REQUIRE THE
 ENGINEER OF RECORDFOR BUILDING ENVELOP
 TO APPROVE THE ADDITIONAL LOADS BEING
 ADDED TO THE ORIGINAL DESIGN. SIGNED/
 SEALED APPROVAL.
  
 2) THE MEZZANINE LEVEL, THE ENGINEER FOR
 THE SITE TO APPROVE LOADS AND ATTACH-
 MENT OF LOADS TO MEZZANINE DECK. SIGNED
 SEALED APPROVAL.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561)659-8096 X 8412

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-03 Cont ID  
Sent By mcarsill Date 2002-09-03 Time 11:45 Rev Time 0.00
Received By mcarsill Date 2002-09-03 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-21 Cont ID  
Sent By pkrauss Date 2002-08-26 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2002-08-21 Time 11:27 Sent To  
Notes
2002-08-21 00:00:001) PLEASE PROVIDE PRODUCT APPROVALS
 FOR SMOG HOG INFORMATION.
  
 2) SEPARATE FIRE SUPPRESSION SYSTEMS
 ARE REQUIRED FOR ANY SMOG HOGS
 INSTALLED.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ALL FIRE SUPPRESSION SYSTEMS
 PLANNED FOR USE.
  
 4) CLEAN-OUTS ARE TO BE PROVIDED IN
 ANY CHANGE OF DIRECTION OF GREASE DUCTS.
  
 5) NO DOWNGRADING OF EXHAUST DUCTS
 BEYOND THE SMOG HOGS ARE PERMITTED.
  
 6) PLEASE PROVIDE PRODUCT APPROVALS
 FOR ANY HOOD WRAPS PLANNED FOR THE SITE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-26 Cont ID  
Sent By pkrauss Date 2002-08-26 Time 10:57 Rev Time 0.30
Received By pkrauss Date 2002-08-26 Time 10:50 Sent To FIRE
Notes
2002-08-26 00:00:00PROVISO:
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR
 FIRE SUPRESSION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-21 Cont ID  
Sent By ndenmark Date 2002-08-21 Time 14:13 Rev Time 0.33
Received By ndenmark Date 2002-08-21 Time 14:13 Sent To B
Notes
2002-08-21 00:00:00DENIED:
 1. PROVIDE INFORMATION AS REQUIRED BY
 FIRE DEPARTMENT PLAN REVIEW.
  
 QUESTIONS CALL NANCY DENMARK CHIEF
 MECHANICAL INSPECTOR @ 561-659-8096 EXT
 8221