Plan Review Details - Permit 02081383
Plan Review Stops For Permit 02081383
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-16 Cont ID  
Sent By jwitmer Date 2003-06-16 Time 14:18 Rev Time 0.45
Received By jwitmer Date 2003-06-16 Time 14:18 Sent To  
Notes
2003-06-16 00:00:00MASTER PLAN 02081383 UPDATE TRUSS ANCHOR
 SCHEDULE, LOAD REDUCTION 1609.4.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-19 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:28 Rev Time 2.00
Received By jwitmer Date 2002-09-19 Time 09:55 Sent To  
Notes
2002-09-19 00:00:00CONTINENTAL MASTER: C-B-B-COKJW
2002-09-09 00:00:00PROVIDE PRODUCT TESTING FOR FRONT ENTRY
 DOOR.
  
 STORM SHUTTERS: KEY PLAN & ATTACHMENT
 SCHEDULE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-05 Cont ID  
Sent By dpalmer Date 2002-09-05 Time 07:22 Rev Time 0.75
Received By dpalmer Date 2002-09-05 Time 07:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-28 Cont ID  
Sent By mcarsill Date 2002-08-28 Time 14:33 Rev Time 0.00
Received By mcarsill Date 2002-08-28 Time 14:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:28 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 15:28 Sent To B
Notes
2003-05-30 00:00:00JW DESK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-09-23 Cont ID  
Sent By pkrauss Date 2002-09-23 Time 11:37 Rev Time 0.35
Received By pkrauss Date 2002-09-23 Time 11:37 Sent To  
Notes
2002-09-23 00:00:00LETTER SUBMITTED IN RESPONSE TO H. MOSER
 PROVISO NOTES.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-19 Cont ID  
Sent By hmoser Date 2002-09-19 Time 12:47 Rev Time 1.00
Received By hmoser Date 2002-09-19 Time 12:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-09 Cont ID  
Sent By pkrauss Date 2002-09-09 Time 16:52 Rev Time 0.00
Received By pkrauss Date 2002-09-09 Time 16:52 Sent To  
Notes
2002-09-09 00:00:00MASTER PERMIT 02081383
  
 DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCS SHOWING
 COMPLIANCE WITH 2001 FBC(M) 402.2.
  
 2.OVERFLOW PROTECTION REQUIRED BY
 MEANS OF AUXILIARY DRAIN PAN WITH
 SECONDARY DRAIN OR FLOAT SWITCH AS
 PER 2001 FBC(M) 307.2.3 & 307.2.4.
  
 3.CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" AWAY FROM THE BUILDING
 STRUCTURE 2001 FBC 1503.4.4.
  
 4.APPLIANCES SHALL NOT BE INSTALLED
 IN A LOCATION WHERE SUBJECT TO
 MECHANICAL DAMAGE UNLESS PROTECTED
 BY APPROVED BARRIERS 2001 FBC(M)
 303.4.
  
 5.PROVIDE A MINIMUM OF 4" CLEARANCE
 AROUND AIR HANDLING UNIT AS PER
 2001 FBC(M) 603.1.3 #(3).
  
 PLEASE ADDRESS THE ABOVE COMMENTS ON
 THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-09 Cont ID  
Sent By kstevens Date 2002-09-09 Time 14:21 Rev Time 0.00
Received By kstevens Date 2002-09-09 Time 14:21 Sent To  
Notes
***NONE***