Plan Review Stops For Permit 02081323 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-10-30 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:06 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2002-10-30 |
Time |
10:10 |
Sent To |
|
|
Notes |
2002-10-30 00:00:00 | | | | | *** ISSUED MASTER*** | | -PLAN REVIEW HISTORY- | | | | PERMIT# 02081323 | | ADDRESS: LIBERTY ISLES | | MASTER "B" | | CONT: HOME DYNAMICS | | VICTOR GONZALEZ | | TELL # (954)275-8569 | | | | THE ATTACHED COMMENTS ARE PART OF THE | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | BUILDING PLAN REVIEW | | JIM WITMER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-09-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
13:48 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2002-09-08 |
Time |
12:20 |
Sent To |
|
|
Notes |
2002-09-08 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 02081323 | | ADD:*****LIBERTY ISLES***** | | ****MASTER "B"**** | | CONT: HOME DYNAMICS VICTOR GONZALEZ | | TEL: (954)275-8569 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1) SHEET A-2 NOTE: MONOLITHIC CONCRETE | | FOUNDATION WITHOUT HOOKBARS DESIGNED BY | | RATIONAL ANAYLSIS, WHAT IS THE MINIMUM | | DOWEL EMBEDDMENT DEPTH WITH NO HOOK? | | GARAGE SECTION STEMWALL CONSTRUCTION, | | DO THE DOWELS REQUIRE EXTRA EMBEDDMENT | | TO REACH THE FOUNDATION PORTION OF THE | | STEMWALL CONSTRUCTION? | | | | 2) 2312.2 SHEARWALL WOOD FRAME SHEAR | | WALLS OR SEGMENTS INDICATE, OPENINGS | | IN SHEAR WALLS SHALL BE SHEATHED WITH | | STRUCTURAL SHEATHING2312.2.2 | | | | 3) SHEET A-3 DESIGN NOTE INDICATES WIND | | ZONE OF 130 SHOULD READ 140 MPH. ALSO | | ASCE &-98. | | | | 4) SHEET A-4 MEAN ROOF HEIGHT < 25' | | ROOF SHEATHING NAILING REQUIREMENT | | PALM BEACH COUNTY AMENDMENTS!!!!! | | ZONES 1 & 2 8D | | 6" EDGES & 6" INTERMEDIATES | | ZONE 3 | | 4" EDGES & 6" INTERMEDIATES | | | | 5) PROVIDE KEY PLAN FOR INSTALATION | | SCHEDULE/ STORM SHUTTERS. | | JIM WITMER | | PLAN REVIEW | | (561)659-8096 X 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-10-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
13:48 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2002-10-28 |
Time |
11:35 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-08-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-28 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-28 |
Time |
10:30 |
Sent To |
R |
|
Notes |
2002-08-28 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THAT THE #6 GROUND BETWEEN | | THE METER AND THE MAIN DISCONNECT | | CREATES A PARALLEL PATH TO THE | | GROUNDING ELECTRODE SYSTEM WITH THE | | NEUTRAL.ALSO CLARIFY THE #6 GROUND | | SHOWN BEING RAN WITH FPL SERVICE. | | | | THE SMOKE DETECTOR SHOWN IN THE HALLWAY | | UPSTAIRS IS TO BE LOCATED AT LEAST | | 5'FROM RETURN AIR DUCTS. | | | | REVISE THE PLANS AND RESUBMIT FOR | | REVIEW. | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-10-27 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-27 |
Time |
15:03 |
Sent To |
B |
|
Notes |
2003-10-27 00:00:00 | TO JW DESK/REV/MASTERED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2003-11-14 |
Time |
09:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2003-01-24 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:04 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2003-01-24 |
Time |
11:44 |
Sent To |
|
|
Notes |
2003-01-24 00:00:00 | REVISION TO MASTER DENIED.PLEASE | | ADDRESS THE FOLLOWING INFORMATION. | | | | 1.PLANS SUBMITTED WITH THE ORIGINAL | | APPROVED SET WERE SIGNED & SEALED BY | | ARCHITECT.REVISIONS NEED TO BE SIGNED, | | SEALED, AND DATED BY ARCHITECT (PER | | CHAPTER 481 OF THE FLORIDA STATUTES). | | | | 2.PLANS ARE NOT SPECIFIC.NOTES ON | | PLAN DUCTWORK TRUNK LINE & DROP LOCATION | | MAY VARY FROM PLAN, GRILLE SIZE OR FLEX | | MAY VARY TO EQUAL OR LARGER SIZES, | | TRIANGLE OR SQUARE BOX.AS PER 2001 | | FBC CHAPTER 1 AMENDMENTS SECTION 104.2.1 | | DRAWINGS SHALL BE SPECIFIC, & THE | | TECHNICAL CODES SHALL NOT BE CITED AS A | | WHOLE OR IN PART NOR SHALL THE TERM | | "LEGAL" OR ITS EQUIVALENT BE USED AS A | | SUBSITITUTE FOR SPECIFIC INFORMATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-10-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-10-26 |
Time |
07:35 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-10-26 |
Time |
07:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-08-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-08-24 |
Time |
07:50 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2002-08-24 |
Time |
07:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-10-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-10-26 |
Time |
07:36 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2002-10-26 |
Time |
07:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-08-20 |
Time |
18:33 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-08-20 |
Time |
18:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-10-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-10-30 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|