Plan Review Stops For Permit 02081322 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-10-30 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:06 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2002-10-30 |
Time |
08:50 |
Sent To |
|
|
Notes |
2002-10-30 00:00:00 | | | | | *** ISSUED MASTER*** | | -PLAN REVIEW HISTORY- | | | | PERMIT# 02081322 | | ADDRESS: LIBERTY ISLES | | MASTER "A" | | CONT: HOME DYNAMICS | | TELL # (954)275-8569 | | VICTOR GONZALEZ | | | | THE ATTACHED COMMENTS ARE PART OF THE | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | BUILDING PLAN REVIEW | | JIM WITMER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-09-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
18:03 |
Rev Time |
1.22 |
Received By |
jwitmer |
Date |
2002-09-08 |
Time |
10:47 |
Sent To |
|
|
Notes |
2002-09-08 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 02081322 | | ADD: *****LIBERTY ISLES***** | | ****MODEL "A"***** | | CONT: HOME DYNAMICS | | TEL: (954)275-8569 VICTOR GONZALEZ | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1)SHEET A-2 NOTE: MONOLITHIC CONCRETE | | FOUNDATION WITHOUT HOOKBARS DESIGN BY RA | | TIONAL ANAYLSIS, WHAT IS THE MINIMUM | | DOWEL EMBEDDMENT DEPTH WITH NO HOOK? | | GARAGE SECTION STEMWALL CONST. DO | | THE DOWELS REQUIRE EXTRA EMBEDMENT TO | | REACH THE FOUNDATION PORTION OF THE | | STEMWALL DESIGN? | | | | 2)2105.1 SHEARWALLS. WHERE THE STRUC- | | TURE DEPENDS UPON MASONARY WALLS FOR | | LATERAL STABILITY, SHEAR WALLS SHALL BE | | PROVIDED PARALLEL TO THE DIRECTION OF | | THE LATERAL FORCESRESISTED. | | 2105.1.2 IN EACH DIRECTION IN WHICH | | SHEAR WALLS ARE REQUIRED FOR LATERAL | | STABILITY, THE MINIMUM CUMULATIVE LENGTH | | OF SHEAR WALLS PROVIDED SHALL BE 0.4 | | TIMES THE LONG DIMENSION OF THE BUILD- | | ING. CUMULATIVE LENGTH OF SHEAR WALLS | | SHALL NOT INCLUDE OPENINGS. | | | | 3) DESIGN NOTES SHEET A-3 INDICATE 130 | | MPH, WE ARE LOCATED IN 140 WIND ZONE. | | ALSO WIND LOADS AS PER CHAP 16 NOT 6, | | AND ASCE 7-98. | | | | SHEET A-4 MEAN ROOF HEIGHT < 25' | | ROOF SHEATHING NAILING REQUIREMENTS | | PALM BEACH COUNTY AMENDMENTS!!!! | | TABLE 2306.1 | | ZONES 1 & 28D COMMON | | 6" EDGES & 6" INTERMEDIATES | | ZONE 3 8D COMMON | | 4" EDGES & 6" INTERMEDIATES | | | | 5) PROVIDE KEY PLAN FOR INSTALLATION | | SCHEDULE/ STORM SHUTTERS. | | JIM WITMER | | PLAN REVIEW | | (561) 659-8096 X 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-10-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
18:03 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-10-29 |
Time |
06:42 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-08-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-28 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-28 |
Time |
12:16 |
Sent To |
R |
|
Notes |
2002-08-28 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | PLEASE NOTE THAT THE #6 GROUND RAN | | BETWEEN THE METER AND THE FIRST MEANS | | OF DISCONNECT DOES NOT COMPLY WITH | | 250-6(B). | | | | ALSO PLEASE CLARIFY THE #6 SHOWN WITH | | THE FPL FEEDERS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-10-27 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-27 |
Time |
15:03 |
Sent To |
B |
|
Notes |
2003-10-27 00:00:00 | TO JW DESK/REV/MASTERED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2003-11-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-11-14 |
Time |
09:12 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2003-11-14 |
Time |
08:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2003-01-29 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:03 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2003-01-29 |
Time |
12:55 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2003-01-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-01-24 |
Time |
10:41 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2003-01-24 |
Time |
10:40 |
Sent To |
|
|
Notes |
2003-01-24 00:00:00 | REVISION TO MASTER DENIED.PLEASE | | ADDRESS THE FOLLOWING INFORMATION. | | | | 1.PLANS SUBMITTED WITH THE ORIGINAL | | APPROVED SET WERE SIGNED & SEALED BY | | ARCHITECT.REVISIONS NEED TO BE SIGNED, | | SEALED, AND DATED BY ARCHITECT (PER | | CHAPTER 481 OF THE FLORIDA STATUTES). | | | | 2.PLANS ARE NOT SPECIFIC.NOTES ON | | PLAN DUCTWORK TRUNK LINE & DROP LOCATION | | MAY VARY FROM PLAN - GRILLE SIZE OR FLEX | | MAY VARY TO EQUAL OR LARGER SIZES. | | TRIANGLE OR SQUARE BOX.AS PER 2001 | | FBC CHAPTER 1 AMENDMENTS SECTION 104.2.1 | | DRAWINGS SHALL BE SPECIFIC, & THE | | TECHNICAL CODES SHALL NOT BE CITED AS A | | WHOLE OR IN PART NOR SHALL THE TERM | | "LEGAL" OR ITS EQUIVALENT BE USED AS A | | SUBSTITUTE FOR SPECIFIC INFORMATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-10-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-10-26 |
Time |
06:27 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-10-26 |
Time |
06:27 |
Sent To |
|
|
Notes |
2002-10-26 00:00:00 | RE-STAMP |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-08-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-08-24 |
Time |
06:59 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2002-08-24 |
Time |
06:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-10-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-10-26 |
Time |
06:28 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2002-10-26 |
Time |
06:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-08-20 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-08-20 |
Time |
17:08 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-08-20 |
Time |
17:08 |
Sent To |
|
|
Notes |
2002-08-20 00:00:00 | PAGE P-2. BATH #2 SHALL COMPLY WITH SEC. | | 909.1. ONLY THE FIXTURES WITHIN THE | | BATHROOM GROUP SHALL CONNECT TO THE WET- | | VENTED HORIZONTAL BRANCH DRAIN. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-10-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-10-30 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|