Plan Review Details - Permit 02081144
Plan Review Stops For Permit 02081144
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-10 Cont ID  
Sent By dpalmer Date 2002-09-10 Time 05:59 Rev Time 0.25
Received By dpalmer Date 2002-09-10 Time 05:59 Sent To B
Notes
2002-09-10 00:00:00*********** NOTE / REVISION ************
  
 PLEASE SEE ITEMS REDLINED ON PLANS,
  
 PLEASE NOTE MISSING RECEPTS PER
 210-52,210-52-H, 210-52-C-1
  
 PLEASE NOTE MISSING EQIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN DISC AND PANEL.
 SIZE PER 250-122
  
 PLEASE NOTE: ALL OPTIONS SHOWN ON PLANS
 THAT ARE INSTALLED, NEED TO BE RE-DRAWN
 AS PERMANENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-07 Cont ID  
Sent By jleech Date 2002-09-07 Time 10:32 Rev Time 0.50
Received By jleech Date 2002-09-07 Time 10:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-24 Cont ID  
Sent By jleech Date 2002-08-24 Time 10:24 Rev Time 0.33
Received By jleech Date 2002-08-24 Time 10:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-09-17 Cont ID  
Sent By lhatten Date 2002-09-17 Time 20:09 Rev Time 3.00
Received By lhatten Date 2002-09-15 Time 20:08 Sent To  
Notes
2002-09-17 00:00:00REVIEW & STAMPED PLAN & TRUSS ENG.
 09/15/2002
 CALC. FEES & PRINT CARD 09/17/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-19 Cont ID  
Sent By sgraham Date 2002-08-19 Time 09:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***