Plan Review Details - Permit 02081062
Plan Review Stops For Permit 02081062
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-01-29 Cont ID  
Sent By lmartine Date 2003-01-29 Time 15:46 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-18 Cont ID  
Sent By pkrauss Date 2003-01-28 Time 09:43 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-22 Cont ID  
Sent By hpiskura Date 2002-08-22 Time 10:25 Rev Time 0.00
Received By hpiskura Date 2002-08-22 Time 10:25 Sent To  
Notes
2002-08-22 00:00:00SHEET 4 OF 5.IF THE TERM "INSTALL
 CONTACTS ON DOORS" IS INTENDED TO BE A
 HOLD OPEN DEVICE FOR THE STAIR SHAFT
 DOORS, PROVIDE SPECIFIC DESIGN
 INFORMATION DEMONSTRATING COMPLIANCE
 WITH FBC 705.1.3.2.3 AND THE APPLICABLE
 PORTIONS OF FBC 1012.1.11. ALSO, PROVIDE
 DOCUMENTATION THAT THE LISTING FOR THE
 EXISTING DOOR MAY BE ALTERED IN THIS
 FASHION
  
 WHAT CONTROLS OR PRECAUTIONS FOR THE
 CUTTING OF THE STRUCTURAL FLOOR SLAB,
 IF ANY, ARE TO BE TAKEN?DOES THE
 ARCHITECT HAVE KNOWLEDGE OF THE
 EXISTING CONDITIONS?SEE FBC 104.2.3.
  
 SHOW THE FIRE PROTECTION, (SPRINKLERS &
 ALARM) DESIGN ALTERATION ON THE PLANS.
 SEE FBC 104.3.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-11 Cont ID  
Sent By btrobaug Date 2003-08-11 Time 08:15 Rev Time 0.33
Received By btrobaug Date 2003-08-11 Time 07:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-11 Cont ID  
Sent By alange Date 2003-08-07 Time 14:32 Rev Time 1.00
Received By btrobaug Date 2002-10-11 Time 14:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-22 Cont ID  
Sent By dpalmer Date 2002-08-22 Time 07:33 Rev Time 0.75
Received By dpalmer Date 2002-08-22 Time 07:33 Sent To  
Notes
2002-08-22 00:00:00************* UNSAT ******************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
 PLEASE NOTE MISSING REQ`D RECEPTS IN
 MANY BATHS REQ`D PER 210-52D
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 4)NOTE: PLEASE NOTE OUTLET SPACING FOR
 KITCHEN OUTLETS TO MEET 210-52-C,1,2,3,
 ,4,5.
  
 5)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING PER 210-70, HALLWAY ETC.
  
 6) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 7))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 8)NOTE: PLEASE SHOW LOCATION OF EXISTING
 PANELS.
 PLEASE SUBMIT PANEL SCHEDULES.
  
 PLEASE NOTE THAT NO HANDWRITTEN CHANGES
 MAY BE ON PLANS, UNLESS EACH CHANGE IS
 SIGNED AND DATED BY THE ARCH OF RECORD.
 FS/FAC 481.221.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-18 Cont ID  
Sent By lmartine Date 2002-10-18 Time 11:09 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-10-18 00:00:00REVIEW PASSED BUILDING COMMENTS LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-28 Cont ID  
Sent By mcarsill Date 2002-08-28 Time 11:14 Rev Time 0.00
Received By mcarsill Date 2002-08-28 Time 11:14 Sent To  
Notes
2002-08-28 00:00:00SEE BUILDING PLAN REVIEW COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 14:31 Rev Time 0.00
Received By alange Date 2003-08-07 Time 14:31 Sent To E
Notes
2003-08-07 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-27 Cont ID  
Sent By btrobaug Date 2003-01-27 Time 13:04 Rev Time 0.00
Received By btrobaug Date 2003-01-23 Time 13:04 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-01-28 Cont ID  
Sent By pkrauss Date 2003-01-28 Time 09:43 Rev Time 0.40
Received By pkrauss Date 2003-01-28 Time 09:43 Sent To B
Notes
2003-01-28 00:00:00REVISION MECHANICAL PERMIT 02081084

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-16 Cont ID  
Sent By btrobaug Date 2003-01-27 Time 13:04 Rev Time 0.40
Received By pkrauss Date 2002-10-16 Time 10:00 Sent To  
Notes
2002-10-16 00:00:00PROVISO:MECHANICAL PERMIT 02081084
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A
 RETURNAIR (JUMPER).
  
 SPOKE WITH BRET FROM MARION CONSTRUCTION
 10-16-02 - DISCREPANCY ON PLAN SHEET #6
 TWO SEPARATE NOTES ONE INDICATES THE
 EXISTING UNITS ARE BEING REPLACED.
 SUBMITTAL LETTER TO FOLLOW FROM
 ARCHITECT INDICATING "CHANGE-OUT"
 SIZING OF OLD EQUIPMENT AS WELL AS NEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-07 Cont ID  
Sent By hmoser Date 2002-09-07 Time 08:28 Rev Time 0.50
Received By hmoser Date 2002-09-07 Time 08:27 Sent To  
Notes
2002-09-07 00:00:00PLAN DENIED
 NO PLANS,ENERGY CALCULATIONS,MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 16:16 Rev Time 0.25
Received By kstevens Date 2002-10-12 Time 16:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-30 Cont ID  
Sent By kstevens Date 2002-08-30 Time 16:36 Rev Time 0.00
Received By kstevens Date 2002-08-30 Time 16:36 Sent To  
Notes
2002-08-30 00:00:00PASSED/PROVISO - ALL CAPPED SANT.- VENT-
 WATER LINES SHALL BE INSPECTED PRIOR TO
 COVERING.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-10-18 Cont ID  
Sent By lmartine Date 2002-10-18 Time 11:10 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***