Plan Review Details - Permit 02080977
Plan Review Stops For Permit 02080977
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-13 Cont ID  
Sent By pkrauss Date 2002-08-13 Time 15:39 Rev Time 0.35
Received By pkrauss Date 2002-08-13 Time 15:39 Sent To  
Notes
2002-08-13 00:00:00PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 AS PER 2001 FBC(M) 1108.1, REFRIGERANT
 LINES SHALL BE TESTED.TEST SHALL BE
 PERFORMED WITH AN INERT DRIED GAS
 INCLUDING, BUT NOT LIMITED TO, NITROGEN
 & CARBON DIOXIDE 2001 FBC(M) 1108.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.