| BUILDING PLAN REVIEW |
| PERMIT: 02080923 |
| ADD:****LIBERTY BAY**** |
| *****MODEL "C"**** |
| CONT: HOME DYNAMICS CONSTRUCTION |
| TEL: (954)275-8569 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) SHEET A-1 NOTE: MONOLITHIC CONCRETE |
| FOUNDATION WITHOUT HOOK BARS DESIGNED |
| BY RATIONAL ANYLYSIS PER ACI318-89. |
| THE PLAN DOES NOT INDICATE WHAT DEPTH |
| THE BARS ARE TO BE EMBEDDED? ALSO ARE |
| THE REBARS TO BE EPOXIED INTO THE SLAB? |
| IF SO WHAT LENGHT? |
| ACI 530 8.5.2 EMBEDDMENT LENGHT MIN 12". |
| DETAIL 2/1 INDICATES WALL SEC THROUGH |
| THE GARAGE, SINCE NO HOOK ON VERTICAL |
| RODS, WILL THESE REBAR BE EMBEDDED AN |
| |
| |
| 2) 2105.1 SHEAR WALLS. WHERE THE STRUC- |
| TURE DEPENDS ON MASONARY WALLS FOR LATER |
| AL STABILITY, SHEAR WALLS SHALL BE PRO- |
| VIDED PARELLEL TO THE DIRECTION OF THE |
| LATERAL FORCES RESISTED. SHOW HOW THE |
| 2ND STORY FRAME STRUCTURE WILL BE TRANS- |
| FERED TO THE FRONT OF THE BUILDING, WIND |
| FROM THE SIDE PUSHING ONTO THE FRONT |
| PORCH AREA, NO SHEAR WALL SEGMENTS, NO |
| BLOCK WALLS ONLY MASONARY COLUMNS? |
| |
| 3) NO FLOOR DIAPHRAM INDICATED,2310.3.1 |
| NOR IS THERE IN FORMATION ON 2ND STORY |
| WOOD FRAME WALLS, HOW CONTINUOUS LOAD WI |
| LL BE TRANSFERRED FROM THE ROOF THROUGH |
| THE FRAME WALLS (TABLE 2310.2B) SHOW |
| RATIONAL ANALYSIS, CALCULATIONS. |
| |
| 4) SHEET A-3 BUILDING DATA, PLANS INDI- |
| CATE THAT THEY ARE DESIGNED TO 130 MPH, |
| REDESIGN FOR 140 MPH WIND ZONE. PROVIDE |
| ADDITIONAL INFO FOR REDESIGN. |
| |
| 5) SHEET A-3 MEAN ROOF HEIGHT < 25' |
| ROOF SHEATHING NAILING REQUIREMENTS |
| ZONES 1 & 28D COMMONS, |
| 6" O.C. EDGES & 6" O.C. INTERMEDIATES |
| ZONE 38D COMMONS |
| 4" O.C. EDGES & 6" O.C. INTERMEDIATES |
| |
| 6) IDENTIFY NAILING REQUIREMENTS FOR |
| 2ND STORY FRAME WALL SHEATHING, SEE |
| TABLE 2310.2A. |
| |
| 7) PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. **MISSING KEY PLAN** |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |