2002-09-17 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-PROVIDE ENGINEERING ANALYSIS/CALCS |
| SHOWING HOW THE MAIN WIND FORCE RESIS- |
| TING SYSTEM (MWFRS) WAS DESIGNED TO |
| TRANSFER LOADS THRU FLOOR AND CEILING |
| DIAPHRAGMS CONSIDERING THE DOUBLE |
| CEILING AREA AND THE PARTIAL FLOOR |
| DIAPHRAGM SUPPORTED ON WOOD COLUMNS |
| WITH CONNECTORS (TOP AND BOTTOM) THAT |
| DON'T PROVIDE SUPPORT FOR LATERAL |
| FORCES. SEE SEC. 1606.2.4 FBC 2001 AND |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 3-PROVIDE ENGINEERING ANALYSIS/CALCS |
| SHOW'G MASONRY WALLS LATERAL STABILITY |
| (SEE SEC. 2105 FBC 2001) AND LATERAL |
| SUPPORT (SEE SEC. 2107 FBC 2001) |
| CONSIDERING THE HIGH VOLUME AREA & THE |
| SINGLE BOND BEAM ONLY. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 4-PROVIDE FIREBLOCKING AT STAIRS. SEE |
| SEC. 2305.1.4 FBC 2001. |
| 5-A)SPECIFY FIREBLOCKING AT ALL WALL |
| SECTIONS. SEC. 2305.1.4 FBC 2001. |
| B)PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| AT ALL CONCEALED SPACES REQ'D BY SEC. |
| 2305.1.4 FBC 2001. |
| 6-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS. |
| 7-PROVIDE DETAIL/SPECS FOR ONE HR FIRE |
| RATED WALL ASSEMBLY @ FRAMED WALL AREA |
| ABOVE BOND BEAM AT ZERO LOT LINE WALL. |
| TABLE 600 FBC 2001. |
| 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| ARCHED WINDOWS AT FRAMED AREAS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 9-PROVIDE COMPLETE STRUCTURAL DETAILS & |
| SPECS FOR RECESSED WINDOW TO ALLOW FOR |
| INSTALLATION OF STORM SHUTTERS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 10-SEE PRODUCT APPROVAL FOR GARAGE DOORS |
| STRUCTURAL BUCK REQUIREMENTS. REVISE |
| DETAIL AS REQUIRED AND SPECIFY BOLT |
| SIZE AND WASHER. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 11-SPECIFY FIRECUT REQUIREMENTS ON THE |
| STRUCTURAL WALL SECTIONS. SEC. 2305.4 |
| 12-STAIR FLOOR PLAN, SHEET A-5: CLARIFY |
| NOTE #13. THERE IS NOT POST AT THIS |
| LOCATION. |
| 13-REVISE STAIR FRAMING PLANS WHEN WOOD |
| COLUMNS ARE CHANGED FOR STEEL COLUMNS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 14-SPECIFY SPACING FOR WWM IN CONCRETE |
| SLAB. SEC. 1909.3 FBC 2001. |
| 15-SHEET S-1: A)SOME INFORMATION IS OVER |
| LAPPING. B)COLUMN F6 DOESN'T MATCH THE |
| SCHEDULE. |
| 16-IDENTIFY ROOF ZONES IN PLANS. SEE |
| TABLE 2306.1 CITY AMENDMENTS TO FBC. |
| 17-REVISE TRUSS CONNECTOR SCHEDULE TO |
| MATCH USP PUBLISHED VALUES. PROVIDE |
| ENGINEERING CALCS FOR DIFFERENT VALUES |
| SEC. 104.2.1.2 CITY AMENDMENTS. |
| 18-A)ATTIC ACCESS TO BE 36" MIN. SEC. |
| 2309.6 FBC 2001. |
| B)PROVIDE ATTIC ACCESS ABOVE GARAGE AREA |
| AND ABOVE MORNING ROOM AREA IF CLEAR |
| HEIGHT IS MORE THAN 24". SEC. 2309.6 |
| 19-24SH & 34SH WINDOWS DON'T PROVIDE THE |
| MIN. CLEAR HEIGHT AND MIN. CLEAR OP'G |
| REQUIRED BY SEC. 1005.4.4 FBC 2001. |
| 20-UPDATE SHEET C-1. FOUNDATION NOTE TO |
| CALL FOR 0.006 MIL VISQUEEN, NOT 0.004 |
| SEC. 1909.2 FBC 2001. |
| 21-WHERE IS SEC/5 SHOWN ON SOME PLANS |
| BY GARAGE AREA. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 22-SHEET A-2: UPDATE GENERAL NOTE FOR |
| PLUMBING. REFER TO FPC 2001. |
| 23-SHEET A-3: A)SOME INFORMATION IS OVER |
| LAPPING. SEE FRONT ELEVATION. B)REVISE |
| NOTE #4 FOR FRAMING AT ARCHED OPENINGS |
| AND AT ONE HR FIRE RATED ASSEMBLIES AS |
| REQUIRED BY TABLE 600 FBC 2001. |
| 24-SHEET A-5: A)STAIR CALCS AREN'T CLEAR |
| B)UPDATE SEMCO STRAP. C)HANDRAIL |
| DIMENSION IS OVERLAPPING. D)KEY NOTE # |
| 14: DRAFSTOPPING IS NOT THE SAME AS |
| FIREBLOCKING. REVISE AS REQUIRED. |
| E)FIREBLOCKING SHOWN ON STAIR SECTION |
| IS INCORRECT. REVISE AS REQUIRED. SEE |
| SEC. 2305.1.4 FBC 2001. |
| 25-SHEET S-1: A)UPDATE SEMCO CONNECTORS. |
| B)WHERE IS COLUMN P3 SPECIFIED ON 2ND |
| FLOOR FRAMING PLAN?. |
| 26-SHEET S-2: A)REVISE SEMCO CONNECTORS. |
| B)SPECIFY DRAFSTOPPING LOCATION AND |
| MATERIAL NOT TO EXCEED 500 S.F. SEE |
| SEC. 2305.2.2 FBC 2001. C)CLARIFY SEC. |
| #2: USING 1#7 OR 1#5?. FLOOR PLAN TO |
| BE CALLED 2ND FL. FRAMING PLAN, NOT |
| GROUND FLOOR PLAN. |
| 27-PROVIDE SECTION/DETAIL SHOWING HOW IS |
| BEAM 2B-1 ANCHORED AT THE ENDS. SAME |
| APPLIES TO BEAM ABOVE MORNING ROOM |
| AREA. SEC. 104.2.1.2 CITY AMENDMENTS. |
| 28-UPDATE SEMCO CONNECTOR SPECIFIED ON |
| SECTION 5 OF SHEET S-2 AND ON NOTE #2 |
| ON SHEET S-2. |