Plan Review Details - Permit 02080903
Plan Review Stops For Permit 02080903
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-28 Time 05:43 Rev Time 0.25
Received By dpalmer Date 2002-08-28 Time 05:43 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2003-01-30 Time 14:48 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-24 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:48 Rev Time 0.50
Received By hmoser Date 2002-08-24 Time 12:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-24 Cont ID  
Sent By jleech Date 2002-08-24 Time 08:43 Rev Time 0.33
Received By jleech Date 2002-08-24 Time 08:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By lhatten Date 2002-10-28 Time 19:16 Rev Time 3.00
Received By lhatten Date 2002-10-27 Time 19:16 Sent To  
Notes
2002-10-28 00:00:00REVIEW & STAMPED PLANS 10/27/2002
 CALC. FEES & PRINT CARD 10/28/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-17 Cont ID  
Sent By jgomez Date 2002-09-17 Time 09:30 Rev Time 3.00
Received By jgomez Date 2002-09-17 Time 09:28 Sent To  
Notes
2002-09-17 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE ENGINEERING ANALYSIS/CALCS
 SHOWING HOW THE MAIN WIND FORCE RESIS-
 TING SYSTEM (MWFRS) WAS DESIGNED TO
 TRANSFER LOADS THRU FLOOR AND CEILING
 DIAPHRAGMS CONSIDERING THE DOUBLE
 CEILING AREA AND THE PARTIAL FLOOR
 DIAPHRAGM SUPPORTED ON WOOD COLUMNS
 WITH CONNECTORS (TOP AND BOTTOM) THAT
 DON'T PROVIDE SUPPORT FOR LATERAL
 FORCES. SEE SEC. 1606.2.4 FBC 2001 AND
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-PROVIDE ENGINEERING ANALYSIS/CALCS
 SHOW'G MASONRY WALLS LATERAL STABILITY
 (SEE SEC. 2105 FBC 2001) AND LATERAL
 SUPPORT (SEE SEC. 2107 FBC 2001)
 CONSIDERING THE HIGH VOLUME AREA & THE
 SINGLE BOND BEAM ONLY. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE FIREBLOCKING AT STAIRS. SEE
 SEC. 2305.1.4 FBC 2001.
 5-A)SPECIFY FIREBLOCKING AT ALL WALL
 SECTIONS. SEC. 2305.1.4 FBC 2001.
 B)PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES REQ'D BY SEC.
 2305.1.4 FBC 2001.
 6-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS.
 7-PROVIDE DETAIL/SPECS FOR ONE HR FIRE
 RATED WALL ASSEMBLY @ FRAMED WALL AREA
 ABOVE BOND BEAM AT ZERO LOT LINE WALL.
 TABLE 600 FBC 2001.
 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOWS AT FRAMED AREAS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE COMPLETE STRUCTURAL DETAILS &
 SPECS FOR RECESSED WINDOW TO ALLOW FOR
 INSTALLATION OF STORM SHUTTERS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 STRUCTURAL BUCK REQUIREMENTS. REVISE
 DETAIL AS REQUIRED AND SPECIFY BOLT
 SIZE AND WASHER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 12-STAIR FLOOR PLAN, SHEET A-5: CLARIFY
 NOTE #13. THERE IS NOT POST AT THIS
 LOCATION.
 13-REVISE STAIR FRAMING PLANS WHEN WOOD
 COLUMNS ARE CHANGED FOR STEEL COLUMNS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 14-SPECIFY SPACING FOR WWM IN CONCRETE
 SLAB. SEC. 1909.3 FBC 2001.
 15-SHEET S-1: A)SOME INFORMATION IS OVER
 LAPPING. B)COLUMN F6 DOESN'T MATCH THE
 SCHEDULE.
 16-IDENTIFY ROOF ZONES IN PLANS. SEE
 TABLE 2306.1 CITY AMENDMENTS TO FBC.
 17-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED VALUES. PROVIDE
 ENGINEERING CALCS FOR DIFFERENT VALUES
 SEC. 104.2.1.2 CITY AMENDMENTS.
 18-A)ATTIC ACCESS TO BE 36" MIN. SEC.
 2309.6 FBC 2001.
 B)PROVIDE ATTIC ACCESS ABOVE GARAGE AREA
 AND ABOVE MORNING ROOM AREA IF CLEAR
 HEIGHT IS MORE THAN 24". SEC. 2309.6
 19-24SH & 34SH WINDOWS DON'T PROVIDE THE
 MIN. CLEAR HEIGHT AND MIN. CLEAR OP'G
 REQUIRED BY SEC. 1005.4.4 FBC 2001.
 20-UPDATE SHEET C-1. FOUNDATION NOTE TO
 CALL FOR 0.006 MIL VISQUEEN, NOT 0.004
 SEC. 1909.2 FBC 2001.
 21-WHERE IS SEC/5 SHOWN ON SOME PLANS
 BY GARAGE AREA. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 22-SHEET A-2: UPDATE GENERAL NOTE FOR
 PLUMBING. REFER TO FPC 2001.
 23-SHEET A-3: A)SOME INFORMATION IS OVER
 LAPPING. SEE FRONT ELEVATION. B)REVISE
 NOTE #4 FOR FRAMING AT ARCHED OPENINGS
 AND AT ONE HR FIRE RATED ASSEMBLIES AS
 REQUIRED BY TABLE 600 FBC 2001.
 24-SHEET A-5: A)STAIR CALCS AREN'T CLEAR
 B)UPDATE SEMCO STRAP. C)HANDRAIL
 DIMENSION IS OVERLAPPING. D)KEY NOTE #
 14: DRAFSTOPPING IS NOT THE SAME AS
 FIREBLOCKING. REVISE AS REQUIRED.
 E)FIREBLOCKING SHOWN ON STAIR SECTION
 IS INCORRECT. REVISE AS REQUIRED. SEE
 SEC. 2305.1.4 FBC 2001.
 25-SHEET S-1: A)UPDATE SEMCO CONNECTORS.
 B)WHERE IS COLUMN P3 SPECIFIED ON 2ND
 FLOOR FRAMING PLAN?.
 26-SHEET S-2: A)REVISE SEMCO CONNECTORS.
 B)SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL NOT TO EXCEED 500 S.F. SEE
 SEC. 2305.2.2 FBC 2001. C)CLARIFY SEC.
 #2: USING 1#7 OR 1#5?. FLOOR PLAN TO
 BE CALLED 2ND FL. FRAMING PLAN, NOT
 GROUND FLOOR PLAN.
 27-PROVIDE SECTION/DETAIL SHOWING HOW IS
 BEAM 2B-1 ANCHORED AT THE ENDS. SAME
 APPLIES TO BEAM ABOVE MORNING ROOM
 AREA. SEC. 104.2.1.2 CITY AMENDMENTS.
 28-UPDATE SEMCO CONNECTOR SPECIFIED ON
 SECTION 5 OF SHEET S-2 AND ON NOTE #2
 ON SHEET S-2.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-13 Cont ID  
Sent By sgraham Date 2002-08-13 Time 15:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***