Plan Review Details - Permit 02080900
Plan Review Stops For Permit 02080900
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-17 Cont ID  
Sent By dpalmer Date 2002-09-17 Time 13:33 Rev Time 0.50
Received By dpalmer Date 2002-09-17 Time 13:33 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:20 Rev Time 0.00
Received By dpalmer Date 2003-01-30 Time 14:20 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-01 Cont ID  
Sent By dpalmer Date 2002-11-01 Time 13:55 Rev Time 0.00
Received By dpalmer Date 2002-11-01 Time 13:55 Sent To R
Notes
2002-11-01 00:00:00TO JULIO./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-24 Cont ID  
Sent By hmoser Date 2003-02-24 Time 19:59 Rev Time 0.25
Received By hmoser Date 2003-02-24 Time 19:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-14 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:20 Rev Time 0.33
Received By jleech Date 2002-09-14 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-14 Cont ID  
Sent By jleech Date 2002-09-14 Time 08:01 Rev Time 0.25
Received By jleech Date 2002-09-14 Time 08:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-11-06 Cont ID  
Sent By jgomez Date 2002-11-06 Time 12:15 Rev Time 2.00
Received By jgomez Date 2002-11-06 Time 12:15 Sent To  
Notes
2002-11-06 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-STORM SHUTTERS: A)DESIGN PRESSURES ON
 SCHEDULE LIMITS THE SIZE OF PANELS.
 SEE PLANS FOR CALCULATED DESIGN PRE-
 SSURES AND REVISE AS REQUIRED.
 B)CLARIFY WHICH ANCHOR IS USED RAWL OR
 CAUL-IN.
 C)MARK ON DRAWINGS MOUNTING CONDITIONS &
 ANCHOR TYPE & SPACING USED.
  
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR W/ SINGLE SIDELITE ASSEMBLY AS
 SHOWN ON PLANS.
 3-PROVIDE UL SPECS FOR ONE HR FIRE RATED
 GLASS BLOCK ASSEMBLY REQ'D BY TABLE
 600 FBC 2001.
 **PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 GLASS BLOCK.
 **SAFETY GLASS BLOCK REQUIRED IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 4-FOUNDATION PLAN AND FOOTING SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED.
 **LENGTH & WIDTH SPECIFIED ON WALL SEC-
 TIONS/DETAILS DON'T MATCH LENGTH AND
 WIDTH SHOWN ON FOOTING SCHEDULE.
 REVISE AS REQUIRED.
 5-PROVIDE SOIL TEST REPORT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-19 Cont ID  
Sent By dpalmer Date 2002-11-01 Time 13:55 Rev Time 3.00
Received By jgomez Date 2002-09-19 Time 17:51 Sent To  
Notes
2002-09-19 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS AND
 COMPLETE SECTIONS/DETAILS/SPECS FOR
 DESIGN OF GABLE END AT FRONT ELEVATION
 CONSIDERING THAT CENTER OF GABLE IS
 MASONRY AND THE TWO SIDES ARE WOOD
 TRUSSES. CLARIFY HOW IS THE WALL PUT
 TOGETHER TO TRANSFER ALL LOADS. SEE
 SECTIONS 1604.2.4, 2105, 2107, 2117
 AND 2313 FBC 2001.
 2-NEED RECORDED N.O.C.
 3-REVISE ATTIC ACCESS SIZE. NEED 36" MIN
 NOT 30". SEC. 2309.6 FBC 2001.
 4-34SH WINDOW DOESN'T PROVIDE 24" MIN.
 CLEAR HEIGHT OPENING. SEC. 1005.4.4.
 5-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS.***NOTE SEE
 PRODUCT APPROVAL FOR LIMITATIONS.
 6-PROVIDE PRODUCT APPROVAL FOR:
 A)SINGLE ENTRY DOOR WITH SINGLE SIDELITE
 ONLY AS SHOWN ON PLANS.
 B)SINGLE HUNG WINDOWS.
 C)FIXED WINDOWS.
 D)WINDOW MULLIONS.
 E)SLIDING GLASS DOORS.
 F)GARAGE DOORS WITH LEGIBLE DRAWINGS.
  
 7-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR ONE HOUR FIRE RATED GLASS BLOCK
 ASSEMBLY REQUIRED BY TABLE 600 FBC.
 **NOTE: NEED SAFETY GLASS IF GLASS BLOCK
 UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2.2 FBC 2001.
 8-REVISE GLASS BLOCK ASSEMBLY DETAIL TO
 MATCH UL SPECIFICATIONS.SEE SUB-
 MITTAL PRESENTED BY CONTRACTOR.
 **NOTE: WINDOW SCHEDULE TO SPECIFY ONE
 HOUR FIRE RATED GLASS BLOCK ASSEMBLY.
 9-SPECIFY SPACING FOR WWM SUPPORTS IN
 CONCRETE SLAB. SEC. 1909.3 FBC 2001.
 10-PROVIDE COMPLETE STRUCTURAL DETAIL
 FOR RECESSED WINDOWS TO ALLOW FOR
 STORM SHUTTERS INSTALLATION. ***NOTE:
 SEE PRODUCT APPROVAL FOR LIMITATIONS
 AND REQUIRED ADDITIONAL ENGINEERING.
 11-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO DATE BOTTOM OF FORM TOO
 12-WALL SECTIONS NOTE #14 AND VENT CALCS
 DON'T MATCH. REVISE AS REQUIRED.
 13-SHEET S-2:A) UPDATE NOTE #2: SEMCO
 IS NOT LONGER IN BUSINESS.
 B)UPDATE NOTE #3 TO REFLECT FBC 2001.
 C)CLARIFY WHY BLOCKING AT FRONT GABLE
 END IS SHOWN PARTIALLY AND NOT ALL THE
 WAY DOWN TO THE ENDS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 14-SHEET S-1:A)CLARIFY DIMENSION OF
 4'-1 1/2" SHOWN ON SECTION 5.
 B)PROVIDE INSTALLATION DETAIL FOR LINTEL
 L-7 AT FRONT PORCH SHOWING CONTINUOUS
 VERTICAL REINFORCEMENT. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)REVISE LINTEL SCHEDULE TO MATCH PLANS.
 CHECK SIZES SPECIFIED.
 15-IDENTIFY ROOF ZONES ON ROOF FRAMING
 PLAN. TABLE 2306.1 CITY AMENDMENTS.
 16-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP PUBLISHED VALUES. PROVIDE ENGINEE-
 RING CALCS FOR DIFFERENT VALUES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 17-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK REQUIREMENTS. REVISE
 DETAIL AS REQUIRED.
 **SPECIFY SIZE OF WASHER.
 18-UPDATE FOUNDATION NOTE ON SHEET C-1:
 NEED 0.006 MIL VISQUEEN MIN. SECTION
 1909.2 FBC 2001.
 19-REVIEW ALL FLOOR PLANS AND MAKE SURE
 KEYED DETAILS/SECTIONS MATCH THOSE
 SHOWN ON THE OTHER SHEETS.
 20-UPDATE GENERAL NOTE ON SHEET A-1:
 REFER TO FPC 2001, NOT SPC 1994.
 21-SHEET A-3: REVISE SECTION THRU ENTRY
 PORCH TO MATCH MASONRY GABLE END SPECS
 SEE SECTION 2117 FBC 2001.
 22-SURVEY AND FLOOR PLANS DON'T MATCH.
 ZERO LOT WALL IS ON THE OPPOSITE SIDE.
 CLARIFY WHY.
 23-PROVIDE SOIL TEST REPORT.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-09 Cont ID  
Sent By sgraham Date 2002-09-09 Time 08:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***