Plan Review Details - Permit 02080894
Plan Review Stops For Permit 02080894
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-28 Time 06:00 Rev Time 0.30
Received By dpalmer Date 2002-08-28 Time 06:00 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-11 Cont ID  
Sent By rregueir Date 2003-03-11 Time 19:03 Rev Time 0.50
Received By rregueir Date 2003-03-11 Time 19:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-24 Cont ID  
Sent By hmoser Date 2002-08-24 Time 12:29 Rev Time 0.50
Received By hmoser Date 2002-08-24 Time 12:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-24 Cont ID  
Sent By jleech Date 2002-08-24 Time 07:22 Rev Time 0.33
Received By jleech Date 2002-08-24 Time 07:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-25 Cont ID  
Sent By jgomez Date 2002-10-25 Time 13:37 Rev Time 2.50
Received By jgomez Date 2002-10-25 Time 13:37 Sent To  
Notes
2002-10-25 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A8. WILL NEED THE ELEVATION
 CERTIFICATE.
 2-STORM SHUTTERS: A)REVISE INSTALLATION
 SCHEDULE: 1)OPENINGS TO MATCH FLOOR
 PLANS. 2)CLARIFY DESIGN PRESSURES (SEE
 ARCHITECTURAL PLANS). 3)CLARIFY TYPE
 OF ANCHOR TO BE USED). 4)CLEARLY MARK
 ON STORM SHUTTER DRAWINGS THE SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED.
 3-PROVIDE COMPLETE UL SPECIFICATIONS FOR
 1 HOUR FIRE RATED GLASS BLOCK ASSEMBLY
 & PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 GLASS BLOCK.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By jgomez Date 2002-09-24 Time 17:48 Rev Time 3.00
Received By jgomez Date 2002-09-24 Time 17:48 Sent To  
Notes
2002-09-24 00:00:00CHECKLIST:
 1-FLOOD ZONE A8: WILL NEED THE ELEVATION
 CERTIFICATE.
 2-NEED RECORDED N.O.C.
 3-SHEET C-1: UPDATE FOUNDATION NOTE.
 NEED 0.006 MIL VISQUEEN. SEC. 1909.2
 4-SHEET A-2: A) REVISE WINDOW SCHEDULE.
 24SH & 34SH WINDOWS DON'T ALLOW THE
 24" MIN. CLEAR HEIGHT OPENING AND THE
 5.7 S.F. MIN. TOTAL CLEAR OPENING.
 SEC. 1005.4.4 FBC 2001.
 B)GLASS BLOCK TO BE 1 HR FIRE RATED
 ASSEMBLY. TABLE 600 FBC 2001.
 **NOTE A): SEE PRODUCT APPROVAL AND UL
 SPECS SUBMITTED BY CONTRACTOR & REVISE
 DETAIL AS REQUIRED. ALSO, NOTE THAT
 GLASS BLOCK SUBMITTED IS NOT BY P.C.
 **NOTE B) GLASS BLOCK TO BE SAFETY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2 FBC 2001.
 C)UPDATE PLUMBING INFORMATION ON NOTE #6
 5-SHEET A-4: A)REVISE STAIR KEY NOTE #1.
 HANDRAIL HEIGHT TO BE BET. 34" AND 38"
 SEE SEC. 1007.5.1 FBC 2001.
 B)NOTE #14: SPEC. FIREBLOCKING MATERIAL
 SEE SEC. 2305.1.4 FBC FOR LOCATION OF
 FIREBLOCKING AT STAIRS. ALSO, SEE SEC.
 2305.1.2 FBC 2001.
 C)PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED AREAS AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 6-NOTE #14: VENT SIZE DOESN'T MATCH VENT
 CALCULATIONS. REVISE AS REQUIRED.
 7-SHEET S-1: A) SPECIFY SPACING FOR WWM
 SUPPORTS IN CONCRETE SLAB. SEC. 1909.3
 B)CLARIFY SIZE OF BUCKET SHOWN ON DETAIL
 S6. SEE SIZE OF GIRDER TRUSS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)DETAIL S21 DOESN'T MATCH CONDITIONS ON
 PLAN. PROVIDE DETAIL SHOWING ACTUAL
 CORNER CONDITIONS. **NOTE: KEEP IN
 MIND SIZE OF POST. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 D)CLARIFY WHY SOME TRUSS GIRDERS ON 2ND
 FLOOR PLAN ARE NOT RESTING ON COLUMNS.
 SEE PLAN.SEC. 104.2.1.2 CITY AMENDM.
 E)SPECIFY UPLIFT LOADS ON ROOF FRAMING
 PLAN AND KEY PROPER ANCHOR. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 F)SHOW NAILING ZONES IN ROOF PLAN. SEE
 TABLE 2306.1 CITY AMENDMENTS TO FBC.
 8-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP PUBLISHED VALUES. PROVIDE ENGINEE-
 RING CALCS FOR DIFFERENT VALUES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 9-SHEET S-3: A)PROVIDE FIRECUT SPECS IN
 WALL SECTIONS. SEC. 2305.4 FBC 2001.
 B)SECTION S2 HAS SOME INFORMATION THAT
 IS OVERLAPPING. REVISE AS REQUIRED.
 C)DETAIL F14: SPECIFY HOW LONG ARE THE
 ANCHOR BOLTS. SEC. 104.2.1.2 CITY AM.
 10-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 FRAMED OPENING TO RECEIVE ARCHED WIND.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS. SEE LIMITATIONS
 ON PRODUCT APPROVAL.
 12-PROVIDE PRODUCT APPROVAL FOR: A)ONE
 HR FIRE RATED GLASS BLOCK ASSEMBLY W/
 LEGIBLE INFORMATION.
 B)GARAGE DOORS W/ LEGIBLE DRAWINGS.
  
  
 NOTE:
 SEE REVIEWED SET OF PLANS FOR REFERENCE
 AND PLEASE RETURN THEM AFTER CORRECTIONS
 ARE DONE TO THE ORIGINAL DRAINGS IN
 ORDER TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-13 Cont ID  
Sent By sgraham Date 2002-08-13 Time 15:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved