Plan Review Details - Permit 02080889
Plan Review Stops For Permit 02080889
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By dpalmer Date 2002-08-27 Time 18:48 Rev Time 0.25
Received By dpalmer Date 2002-08-27 Time 18:48 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-24 Cont ID  
Sent By lhatten Date 2002-08-24 Time 18:36 Rev Time 0.25
Received By lhatten Date   Time   Sent To  
Notes
2002-10-28 00:00:00OKED PER H. M. 08/24/2002

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-24 Cont ID  
Sent By jleech Date 2002-08-24 Time 09:24 Rev Time 0.33
Received By jleech Date 2002-08-24 Time 09:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By lhatten Date 2002-10-28 Time 18:31 Rev Time 3.00
Received By lhatten Date 2002-10-27 Time 18:30 Sent To  
Notes
2002-10-28 00:00:00REVIEW & STAMPED PLANS 10/27/2002
 CALC. FEES & PRINT CARDS 10/28/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-23 Cont ID  
Sent By jgomez Date 2002-09-23 Time 13:53 Rev Time 3.00
Received By jgomez Date 2002-09-23 Time 13:53 Sent To  
Notes
2002-09-23 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 EXTERIOR MASONRY WALL WITH VERTICAL
 REINFORCEMENT @ 8'-0" O.C. TIED TO A
 SINGLE BOND BEAM. SEE SEC. 1604.2.4,
 2105, 2117 FBC 2001.
 2-A)PROVIDE COMPLETE DETAILS/SPECS FOR
 INSTALLATION OF FRONT GABLE ENDS
 TRUSSES SHOWING HOW ARE THEY STRUCTU-
 RALLY CONTINUOUS AS REQ'D BY SECTION
 2313 FBC 2001.
 B)CLARIFY WHY BLOCKING AT FRONT GABLES
 IS SHOWN PARTIALLY AND NOT ALL THE WAY
 DOWN TO THE ENDS OF GABLES. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-NEED RECORDED N.O.C.
 4-SHEET A-1: A)UPDATE PLUMBING NOTE.
 B)REVISE ATTIC ACCESS SIZE. NEED 36" MIN
 SECTION 2309.6 FBC 2001.
 C)BATHROOM #2 WINDOW TO HAVE SAFETY
 GLASS. SEC. 2405.2. FBC 2001.
 D)SOME DETAILS/SECTIONS DON'T MATCH. EG:
 SECTION A/A-3 TO BE SEC. B/A3. REVISE
 5-SHEET A-2: NOTE #4 DOESN'T APPLY TO
 ARCHED OPENINGS OR GABLE ENDS. REVISE.
 6-SHEET A-4: A)REVISE SIZE OF FOOTING ON
 SEC. 2/A-4 TO MATCH FOUNDATION PLAN.
 B)DIMENSIONS ON DETAILS 3/A-4 AND 4/A-4
 AREN'T LEGIBLE. REVISE AS REQUIRED.
 7-SHEET S-1: A)STRUCTURAL NOTE #1 AND
 SOIL STATEMENT DON'T MATCH. REVISE.
 B)TYPICAL DETAIL AT BOND BEAM CALLS FOR
 BB W/1#7. CHECK BEAM SCHEDULE.
 C)PROVIDE STRUCTURAL DETAIL/SECTION AT
 FRONT PORCH SHOWING HOW IS PRECAST
 LINTEL INSTALLED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 D)SPECIFY SPACING FOR WWM SUPPORTS IN
 CONCRETE SLAB. SEC. 1909.3 FBC 2001.
 8-SHEET S-2: A) REVISE NOTE #2. SEE USP
 CATALOGUE FOR CORRECT CONNECTOR.
 B)UPDATE NOTE #3: SEE FBC 2001.
 C)ELEVATION "A" IS KEYED ON FRAMING PLAN
 AS A/S-2.1. REVISE AS REQUIRED.
 **NOTE A): COLUMNS SPECIFIED DON'T MATCH
 FOUNDATION PLAN.
 **NOTE B): WHERE ARE THE 2#% TOP & BOTT.
 SEE BEAM SCHEDULE.
 D)WHERE IS CONNECTOR A/S-2?
 E)PROVIDE NAILING DIAPHRAGM AND IDENTIFY
 ROOF NAILING ZONES IN PLAN. SEE TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001.
 F)SECTION 5 CALLS FOR BB W/ 1#7. CLARIFY
 G)REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP. PROVIDE ENGINEERING CALCS
 FOR DIFFERENT VALUES. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 H)WHERE IS SECTION 1/S-2 KEYED ON PLAN?
 9-PROVIDE STRUCTURAL DETAIL FOR 2X BUCK
 AT ARCHED OPENINGS TO RECEIVE ARCHED
 WINDOWS. ***NEED SPECS FOR WOOD FRAM'G
 AND FOR MASONRY INSTALLATION. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-PROVIDE PRODUCT APPROVAL FOR GARAGE
 SIDE DOOR AND PRODUCT APPROVAL WITH
 LEGIBLE DRAWINGS FOR GARAGE DOORS.
 11-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A SE-
 PARATE PERMIT. ***NOTE: CHECK LIMITA-
 TIONS ON PRODUCT APPROVAL.
 12-PROVIDE GENERAL SPECS FOR FIREBLOCK'G
 AT ALL CONCEALED SPACES. SEC. 2305.1.4
 13-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 STRUCTURAL BUCK REQUIREMENTS. REVISE
 DETAIL AS REQUIRED AND SPECIFY WASHERS
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 14-ENERGY CALCULATIONS: A)REVISE UNDER
 ATTIC AREA. SEE SEC. 602.1.ABC.1.2
 CHAPTER 13 FBC 2001.
 15-UPDATE SHEET C-1: FOUNDATION NOTE TO
 USE 0.006 MIL VISQUEEN, NOT 0.004 MIL.
 SEC. 1909.2 FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-13 Cont ID  
Sent By sgraham Date 2002-08-13 Time 15:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***