Plan Review Details - Permit 02080648
Plan Review Stops For Permit 02080648
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 10:08 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 10:08 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2002-08-21 Cont ID  
Sent By mcarsill Date 2002-08-21 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2002-08-21 Time 10:07 Sent To  
Notes
2002-08-21 00:00:001) NO FIRE DEPARTMENT CONNECTION SHOWN
 ON DRAWINGS. PLEASE PROVIDE A FIRE
 DEPARTMENT CONNECTION WITHIN 150 FEET
 OF A FIRE HYDRANT.
  
 2) UNDERGROUND PIPING TO BE RESTRAINED
 IN ACCORDANCE WITH NFPA 24.
  
 3) ALL UNDERGROUND PIPING TO BE PRESSURE
 TESTED AT 200 PSI FOR TWO HOURS.
  
 4) FIRE LINES ARE NOT ALLOWED TO BE RUN
 UNDERNEATH THE BUILDING UNLESS
 ABSOLUTLEY NECESSARY. PLEASE CLARIFY
 AND REVISE PLANS AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 10:08 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 10:08 Sent To  
Notes
***NONE***