Plan Review Stops For Permit 02080638 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-12-10 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-12-10 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-11-22 |
Time |
10:53 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-08-30 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-11-21 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-08-30 |
Time |
13:09 |
Sent To |
|
|
Notes |
2002-08-30 00:00:00 | THE LAND DESIGN SOUTH PLANS ARE REQUIRED | | TO BE SIGNED SEALED AND DATED.SEE | | FBC 104.2.2. | | | | SHOW THE ATTIC ACCESS REQUIRED BY FBC | | 2309.6 | | | | SHOW THE ATTIC VENTILATION REQUIRED BY | | FBC 2309.7 INCLUDE THE FREE AREA OF ANY | | SCREENED VENT TO BE USED. | | | | SHEET 3 OF 3 "DESIGN CHART" DECLARES | | ROOF ONLY, WHAT WAS USED FOR THE REST | | OF THE BUILDING?INCLUDE COMPONENTS | | AND CLADDING FOR THE WALLS. | | | | SEE FBC 104.2.1.1 FOR THE ROOF COVERING | | DESIGN INFORMATION TO BE PLACED ON THE | | PLANS. | | | | HOW WAS THE 0.18 +/- INTERNAL PRESSURE | | COEFFICIENT DETERMINED?SEE FBC | | 1606.1.4.2 FOR ENCLOSED BUILDING | | CRITERIA. | | | | SHEET 3 OF3 CALLS OUT A "USP DTC" | | CONNECTOR FOR THE TRUSSES.USP DOES | | NOT LIST A "DTC" CONNECTOR IN THEIR | | CATALOG.WHAT IS INTENDED TO BE USED? | | | | WHAT GROUT SPECIFICATION AND VARIOUS | | OTHER SIGNIFICANT DESIGN CRITERIA ARE | | TO BE USED FOR THE FILLED CELL MASONRY? | | SEE FBC 2103.1. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-08-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-08-28 |
Time |
20:18 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2002-08-28 |
Time |
20:15 |
Sent To |
|
|
Notes |
2002-08-28 00:00:00 | ************ NOTE ************* | | | | PLEASE NOTE , PLANS REDLINED AND NOTED | | THE NO MORETHAN 8' OF UNPROTECTED | | CONDUCTORS INSIDE BLDG PER 230-70A OF | | LOCAL AMENDMENTS. | | | | PLEASE NOTE ROOM FOR ELECTRICAL PANEL | | MUST MEET 110-26/ 384-7. SHOWN AS | | STORAGE AND EQUIPMENT ROOM.? | | | | NOTED ON PLANS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-12-10 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-12-10 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-12-11 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2002-12-11 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2002-12-11 |
Time |
16:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-08-22 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-12-10 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-08-22 |
Time |
12:04 |
Sent To |
|
|
Notes |
2002-08-22 00:00:00 | 1) ADDRESS REQUIRED TO BE INSTALLED ON | | BUILDING. SIX INCH NUMERALS REQUIRED. | | | | 2) THE FLOOR PLAN AND ELECTRICAL PLAN | | INDICATES TWO DIFFERENT ROOM NAMES FOR | | THE STORAGE AND EQUIPMENT ROOM. PLEASE | | REVISE. | | | | 3) SINCE NO FIRE SPRINKLER PROTECTION | | IS TO BE PROVIDED, THE STORAGE OR | | EQUIPMENT ROOM IS TO BE AT LEAST ONE | | HOUR FIRE RATED WITH THE PROPER | | OPENING PROTECTIVES. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-11-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-08 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-08 |
Time |
17:04 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-11-21 |
Time |
09:04 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-11-21 |
Time |
09:04 |
Sent To |
B |
|
Notes |
2002-11-21 00:00:00 | REVIEW FORBATHROOMS AT THE POOL HOUSE | | | | BATHROOMS ARE MECHANICALLY EXHAUSTED & | | WINDOWS ARE LOUVERED FOR FRESH AIR. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-09-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-11-12 |
Time |
17:16 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2002-09-07 |
Time |
08:02 |
Sent To |
|
|
Notes |
2002-09-07 00:00:00 | PLAN DENIDE | | NO PLANS,ENERGY CALCULATIONS,OR MANUAL | | (J) | | PLAN REVIEW BY HAROLD MOSER | | (561)659-8096 EXT.8390 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-12-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-12-14 |
Time |
20:20 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-12-14 |
Time |
20:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-11-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-11-12 |
Time |
17:09 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-11-12 |
Time |
17:09 |
Sent To |
|
|
Notes |
2002-11-12 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) FROM PREVIOUS REVIEW: SHEET #3, | | SANITARY RISER DIAGRAM DOES NOT REFLECT | | THE FLOOR PLAN. THE DRINKING FOUNTAIN | | IS NOT SHOWN. DRINKING FOUNTAINS SHALL | | NOT DRAIN THROUGH THE THE WET VENT OF | | THE BATHROOM GROUPS 909.1/909.1.2. | | DRINKING FOUNTAINS SHALL DRAIN DOWN- | | STREAM OF THE BATHROOM GROUP. | | 2) NEW COMMENT: PLEASE PROVIDE A WATER | | RISER DIAGRAM. WATER HAMMER ARRESTORS | | PER 604.9 AND LOCATED NEAR THE FIXTURES | | WHERE REQUIRED NOT AT TOP OF DROP IN THE | | CEILING. BACKFLOW REQUIRED ON WATER | | SERVICE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-08-31 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-08 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-31 |
Time |
11:53 |
Sent To |
M |
|
Notes |
2002-08-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) PLEASE ROUTE PLANS TO PALM BEACH | | COUNTY HEALTH UNIT 901 EVERNIA ST | | (561) 355-3018 X 1194 PRIOR TO RESUB- | | MITING. | | 2) SHT 3 SANITARY RISER DIAGRAM DOES NOT | | REFLECT FLOOR PLAN. DRINKING FOUNTAIN | | IS NOT SHOWN ON RISER DIAGRAM. DRINKING | | FOUNTAINS SHALL TIE IN DOWNSTREAM OF | | THE BATHROOM GROUP WET VENT. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-08-20 |
Time |
10:13 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|