Plan Review Details - Permit 02080610
Plan Review Stops For Permit 02080610
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By btrobaug Date 2002-08-27 Time 08:29 Rev Time 0.50
Received By btrobaug Date 2002-08-27 Time 07:25 Sent To R
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 13:07 Rev Time 0.00
Received By dpalmer Date 2002-10-31 Time 13:07 Sent To B
Notes
2002-10-31 00:00:00TO JULIO

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-20 Cont ID  
Sent By hmoser Date 2002-08-20 Time 19:42 Rev Time 0.50
Received By hmoser Date 2002-08-20 Time 19:41 Sent To  
Notes
2002-08-20 00:00:00PASS/PRIVISO
 1) TOTAL CFM.DONOT MATCH PLAN
 2) CHECK A/C SIZE
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-17 Cont ID  
Sent By jleech Date 2002-08-17 Time 13:09 Rev Time 0.33
Received By jleech Date 2002-08-17 Time 13:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-11-05 Cont ID  
Sent By jgomez Date 2002-11-05 Time 17:07 Rev Time 2.00
Received By jgomez Date 2002-11-05 Time 17:07 Sent To  
Notes
2002-11-05 00:00:00APPROVED WITH PROVISO:
 1-CLARIFY INFO. FOR STORM SHUTTERS:
 A)DESIGN PRESSURES SPECIFIED LIMIT THE
 STORM PANEL SPAN. SEE ARCHITECTURAL
 DWGS FOR CALCULATED DESIGN PRESSURES &
 REVISE AS REQUIRED.
 B)CLARIFY WHICH ANCHOR TO BE USED RAWL
 OR CAULK-IN.
 C)MARK ON DRAWINGS MOUNTING CONDITIONS &
 ANCHOR TYPE AND SPACING.
  
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY AS SHOWN
 ON PLANS.
 3-PROVIDE CLEAR/LEGIBLE PRODUCT APPROVAL
 FOR GLASS BLOCK.
 4-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO SIGN AND DATE FORM TOO.
  
 5-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP CATALOGUE ACCORDING TO NAIL USED.
 PROVIDE ENGINEERING CALCULATIONS FOR
 DIFFERENT VALUES. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 6-FOUNDATION PLAN AND FOOTING SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED. ALSO,
 WALL SECTIONS DIMENSIONS (L X W) DON'T
 MATCH LENGTH AND WIDTH AS SHOWN ON THE
 FOOTING SCHEDULE. REVISE AS REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-19 Cont ID  
Sent By btrobaug Date 2002-08-27 Time 08:29 Rev Time 3.00
Received By jgomez Date 2002-09-19 Time 15:22 Sent To  
Notes
2002-09-19 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS AND
 COMPLETE SECTIONS/DETAILS/SPECS FOR
 DESIGN OF GABLE END AT FRONT ELEVATION
 CONSIDERING THAT CENTER OF GABLE END
 IS MASONRY AND THE TWO SIDES ARE WOOD
 TRUSSES. CLARIFY HOW IS THE WALL PUT
 TOGETHER TO TRANSFER ALL LOADS. SEE
 SECTIONS 1604.2.4, 2105, 2107, 2117 &
 2313 FBC 2001.
 2-NEED RECORDED N.O.C.
 3-REVISE ATTIC ACCESS SIZE. NEED 36" MIN
 NOT 30". SEC. 2309.6 SBC 2001.
 4-34SH WINDOW DOESN'T PROVIDE 24" MIN.
 CLEAR HEIGHT OPENING. SEC. 1005.4.4
 5-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS. **NOTE: SEE LIMI-
 TATIONS ON PRODUCT APPROVAL.
 6-PROVIDE PRODUCT APPROVAL FOR SINGLE
 ENTRY DOOR WITH SINGLE SIDELITE AS
 SHOWN ON PLANS.
 7-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR ONE HOUR FIRE RATED GLASS BLOCK
 ASSEMBLY REQUIRED BY TABLE 600 FBC.
 **NOTE: GLASS BLOCK TO BE SAFETY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2.2 FBC 2001.
 8-REVISE GLASS BLOCK ASSEMBLY DETAIL TO
 MATCH UL SPECIFICATIONS SUBMITTED.
 **REVISE WINDOW SCHEDULE: SPECIFY ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY.
 9-SPECIFY SPACING FOR WWM SUPPORTS IN
 CONCRETE SLAB. SEC. 1909.3 FBC 2001.
 10-PROVIDE COMPLETE STRUCTURAL DETAIL
 FOR RECESSED WINDOWS TO ALLOW FOR
 STORM SHUTTERS INSTALLATION. ***NOTE:
 SEE STORM SHUTTERS PRODUCT APPROVAL
 FOR LIMITATIONS.
 11-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO DATE BOTTOM OF FORM.
 12-WALL SECTIONS NOTE #14 AND VENT CALCS
 DON'T MATCH. REVISE AS REQUIRED.
 13-SHEET S-2: A)UPDATE NOTE #2: SEMCO
 CONNECTOR IS NO LONGER IN THE INDUSTRY
 B)UPDATE NOTE #3: REFER TO FBC 2001 FOR
 140MPH, NOT ASCE 7-93 FOR 110MPH.
 C)CLARIFY WHY BLOCKING AT FRONT GABLE
 END IS SHOWN PARTIALLY AND NOT ALL THE
 WAY DOWN TO THE ENDS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 14-SHEET S-1:A) CLARIFY DIMENSION OF
 4'-1 1/2" ON SECTION 5.
 B)PROVIDE INSTALLATION DETAIL FOR LINTEL
 L-7 AT FRONT PORCH SHOWING CONTINUOUS
 VERTICAL REINFORCEMENT. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)REVISE LINTEL SCHEDULE TO MATCH PLANS.
 CHECK SIZES AND LINTEL SPECIFIED.
 15-IDENTIFY ROOF ZONES ON ROOF FRAMING
 PLAN. TABLE 2306.1 CITY AMENDMENTS.
 16-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP PUBLISHED VALUES. PROVIDE ENGINEE-
 RING CALCS FOR DIFFERENT VALUES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 17-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK REQUIREMENTS. REVISE
 DETAIL AS REQUIRED.
 **SPECIFY SIZE OF WASHER.
 18-UPDATE FOUNDATION NOTE ON SHEET C-1:
 NEED 0.006 MIL VISQUEEN MIN. SECTION
 1909.2 FBC 2001.
 19-REVIEW ALL FLOOR PLANS AND MAKE SURE
 KEYED DETAILS/SECTIONS MATCH THOSE
 SHOWN ON THE OTHER SHEETS.
 20-UPDATE GENERAL NOTE ON SHEET A-1:
 REFER TO FPC 2001, NOT SPC 1994.
 21-SHEET A-3: REVISE SECTION THRU ENTRY
 PORCH TO MATCH MASONRY GABLE END SPECS
 SEE SEC. 2117 FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-08 Cont ID  
Sent By sgraham Date 2002-08-08 Time 14:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved