Plan Review Details - Permit 02080491
Plan Review Stops For Permit 02080491
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-20 Cont ID  
Sent By dpalmer Date 2002-08-20 Time 06:38 Rev Time 0.00
Received By dpalmer Date 2002-08-20 Time 06:38 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-11 Cont ID  
Sent By rregueir Date 2003-03-11 Time 19:34 Rev Time 0.33
Received By rregueir Date 2003-03-11 Time 19:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-15 Cont ID  
Sent By hmoser Date 2002-08-15 Time 20:06 Rev Time 0.50
Received By hmoser Date 2002-08-15 Time 20:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By jleech Date 2002-08-06 Time 20:17 Rev Time 0.33
Received By jleech Date 2002-08-06 Time 20:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-22 Cont ID  
Sent By jgomez Date 2002-10-22 Time 18:47 Rev Time 3.00
Received By jgomez Date 2002-10-22 Time 18:47 Sent To  
Notes
2002-10-22 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT. NEED SITE SPECIFIC CONDITIONS
 USING THE CERTIFICATE OF COMPLIANCE
 METHOD AND INSTALLATION AFFIDAVIT. SEE
 CITY IMPLEMENTATION STANDARD FOR HURRI
 CANE MISSILE IMPACT PROTECTION.
 **SEE GENERAL NOTES ON PAGE 1 OF STORM
 SHUTTERS DRAWINGS FOR ADDITIONAL LIMI-
 TATIONS FOR THIS STORM SHUTTERS.
 2-PROVIDE SOIL TEST REPORT.
 3-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 4-GLASS BLOCK:
 A)PRODUCT APPROVAL IS NOT LEGIBLE.
 B)PROVIDE COMPLETE UL SPECS FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY.
 C)REVISE GLASS BLOCK DETAIL TO MATCH ONE
 HOUR FIRE RATED ASSEMBLY. SEE UL SPECS
 D)PROVIDE INFORMATION STATING THE FACE
 THICKNESS OF GLASS. NEED SAFETY GLASS
 IF FACE THICKNESS IS LESS THAN 0.25".
 SEC. 2405.2.2 FBC 2001.
 5-ENTRY DOOR PRODUCT APPROVAL REPORT IS
 MISSING SOME PAGES. RESUBMIT AS REQ'D.
 6-PROVIDE ENGINEERED CALCULATIONS FOR 1"
 WASHER USED AT GARAGE STRUCTURAL BUCK.
 NOTE: CONSIDER WOOD USED & REDUCTION
 FACTOR FOR P.T. WOOD. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-23 Cont ID  
Sent By jgomez Date 2002-09-23 Time 18:32 Rev Time 3.00
Received By jgomez Date 2002-09-23 Time 18:32 Sent To  
Notes
2002-09-23 00:00:00CHECKLIST:
 1-FLOOD ZONE A8. WILL NEED ELEVATION
 CERTIFICATE.
 2-PROVIDE SOIL TEST REPORT.
 3-NEED RECORDED N.O.C.
 4-SHEET C-1: UPDATE FOUNDATION NOTE.
 NEED 0.006 MIL VISQUEEN. SEC. 1909.2
 5-SHEET A-2: A)REVISE WINDOW SCHEDULE.
 24SH AND 34SH WINDOWS DON'T ALLOW THE
 24" MIN. CLEAR HEIGHT OPENING AND THE
 5.7 S.F. MIN. TOTAL CLEAR OPENING.
 SEC. 1005.4.4 FBC 2001.
 B)GLASS BLOCK TO BE 1 HR FIRE RATED
 ASSEMBLY. TABLE 600 FBC 2001.
 **NOTE A): SEE PRODUCT APPROVAL AND UL
 SPECS SUBMITTED BY CONTRACTOR & REVISE
 DETAIL AS REQUIRED. ALSO, NOTE THAT
 GLASS BLOCK SUBMITTED IS NOT BY P.C.
 **NOTE B)GLASS BLOCK TO BE SAFETY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25".SEC. 2405.2 FBC 2001.
 C)UPDATE PLUMBING INFORMATION ON NOTE #6
 6-SHEET A-4: A)REVISE STAIR KEY NOTE #1.
 HANDRAIL HEIGHT TO BE BET. 34" AND 38"
 SEE SEC. 1007.5.1 FBC 2001.
 B)NOTE #14: SPEC. FIREBLOCKING MATERIAL.
 (FIREBLOCKING AND DRAFSTOPPING ARE NOT
 THE SAME THING. REVISE NOTE AS REQ'D)
 **NOTE: SEE SEC. 2305.1.4 FOR LOCATIONS
 TO HAVE FIREBLOCKING AT STAIRS.
 ALSO, SEE SEC. 2305.1.2 FBC 2001.
 C)PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED AREAS AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-NOTE #14: VENT SIZE DOESN'T MATCH VENT
 CALCULATIONS. REVISE AS REQUIRED.
 8-SHEET S-1: A) SPECIFY SPACING FOR WWM
 SUPPORTS IN CONCRETE SLAB. SEC. 1909.3
 B)CLARIFY SIZE OF BUCKET SHOWN ON DETAIL
 S6. SEE SIZE OF GIRDER TRUSS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)DETAIL S21 DOESN'T MATCH CONDITIONS ON
 PLAN. PROVIDE DETAIL SHOWING ACTUAL
 CORNER CONDITION. SEC. 104.2.1.2 CITY
 D)CLARIFY WHY SOME TRUSS GIRDERS ON 2ND
 FLOOR PLAN ARE NOT RESTING ON COLUMNS.
 SEE PLAN.
 E)SPECIFY UPLIFT LOADS ON ROOF FRAMING
 PLAN AND KEY PROPER ANCHOR. SECTION
 104.2.1.2 CITY AMENDMENTS AND CHAPTER
 16 FBC 2001.
 F)SHOWNAILING ZONES IN ROOF PLAN. SEE
 TABLE 2306.1 CITY AMENDMENTS TO FBC.
 9-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP PUBLISHED VALUES. PROVIDE ENGINEE-
 RING CALCS FOR DIFFERENT VALUES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-SHEET S-3: A)PROVIDE FIRECUT SPECS IN
 WALL SECTIONS. SEC. 2305.4 FBC 2001.
 B)SECTION S2 HAS SOME INFORMATION OVER-
 LAPPING. REVISE AS REQUIRED.
 C)DETAIL F14: SPECIFY HOW LONG ARE THE
 ANCHOR BOLTS. SEC. 104.2.1.2 CITY
 11-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 FRAMED OPENING TO RECEIVE ARCHED WIND.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 12-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS.
 13-PROVIDE PRODUCT APPROVAL FOR: ENTRY
 DOOR, SINGLE HUNG WINDOW, FIXED WINDOW
 WINDOW MULLIONS, SLIDING GLASS DOORS
 AND GARAGE DOORS WITH LEGIBLE DRAWINGS
  
 NOTE: SEE REVIEWED SET OF PLANS FOR
 REFERENCE AND PLEASE RETURN THEM
 AFTER CORRECTIONS ARE DONE TO THE
 ORIGINAL DRAWINGS IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.
 THANK YOU.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-07 Cont ID  
Sent By sgraham Date 2002-08-07 Time 08:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***