2002-09-10 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-PROVIDE ENGINEERING ANALYSIS/CALCS FOR |
| CLARIFICATION OF HOW THE MAIN WIND |
| FORCE RESISTING SYSTEM (MWFRS) WAS |
| DESIGNED TO RESIST AND TRANSFER ALL |
| LOADS TO FLOOR AND CEILING DIAPHRAGMS |
| CONSIDERING THE DOUBLE CEILING AREA |
| AND THE PARTIAL FLOOR DIAPHRAGM |
| SUPPORTED ON WOOD COLUMNS WITH |
| CONNECTORS (TOP AND BOTTOM) THAT DON'T |
| PROVIDE SUPPORT FOR LATERAL FORCES. |
| SEE SEC. 1606.2.4 FBC 2001. |
| 2-PROVIDE ENGINEERING ANALYSIS/CALCS FOR |
| CLARIFICATION OF MASONRY WALLS LATERAL |
| STABILITY (SEE SECTION 2105 FBC 2001) |
| AND LATERAL SUPPORT (SEE SECTION 2107) |
| CONSIDERING THE HIGH VOLUME AREA AND |
| SINGLE BOND BEAM ONLY. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 3-A)PROVIDE FIREBLOCKING AT STAIRS. |
| INCLUDING AT TOP AREA. SEC. 2305.1.4 |
| B)SPECIFY FIREBLOCKING AT WALL SECTIONS |
| AND PROVIDE GENERAL SPECIFICATIONS FOR |
| REQUIRED FIREBLOCKING AT ALL CONCEALED |
| SPACES. SEC. 2305.1.4 FBC 2001. |
| 4-AREA TABULATION ON SHEET C-1 AND A-1 |
| DON'T MATCH. REVISE AS REQUIRED. |
| 5-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS OR APPLY FOR A SEPA |
| RATE PERMIT. SEE CITY IMPLEMENTATION |
| STANDARD FOR HURRICANE MISSILE IMPACT |
| PROTECTION. |
| 6-PROVIDE DETAIL/SPECIFICATIONS FOR ONE |
| HOUR FIRE RATED WALL ASSEMBLY @ FRAMED |
| WALL AREA ABOVE BOND BEAM AT ZERO LOT |
| LINE AS REQUIRED BY TABLE 600 FBC 2001 |
| 7-PROVIDE COMPLETE DETAILS AND SPECS FOR |
| PRECAST LINTELS AT REAR PORCH. SPECIFY |
| ATTACHMENT TO COLUMNS AND TO WALL |
| SHOWING STEEL REINFORCEMENT THAT WILL |
| RESIST UPLIFT LOADS. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 8-SOME LINTELS SHOWN ON PLANS DON'T |
| MATCH OPENING SIZES SHOWN ON LINTEL |
| SCHEDULE. REVISE AS REQUIRED. |
| 9-SPECIFY SIZE & REINFORCEMENT FOR CON- |
| CRETE PAD AT REAR PORCH COLUMN. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 10-PROVIDE LEGIBLE PRODUCT APPROVAL FOR |
| ENTRY DOORS AND GARAGE DOORS. |
| 11-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| ARCHED WINDOWS AT FRAMED AREA. |
| **NOTE: NEED SPECS FOR ATTACHMENT TO |
| MASONRY WALL AS WELL. |
| 12-NOTE #2 ON SHEET A-1 CALLS FOR WINDOW |
| TO BE RECESSED TO ALLOW FOR STORM |
| SHUTTER INSTALLATION. PROVIDE COMPLETE |
| STRUCTURAL DETAIL/SPECS. |
| **NOTE: SEE STORM SHUTTERS INFORMATION |
| FOR TRACK AND MOUNTING CONDITIONS TO |
| BE USED CONSIDER'G THE "EDGE DISTANCE" |
| AND "GLASS SEPARATION". |
| 13-SEE PRODUCT APPROVAL FOR GARAGE DOOR |
| STRUCTURAL BUCK REQUIREMENTS & PROVIDE |
| DETAIL AS REQUIRED. SPECIFY ANCHOR |
| SIZE, SPACING AND WASHER TO BE USED. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 14-SPECIFY FIRECUT REQUIREMENTS ON THE |
| STRUCTURAL WALL SECTIONS. SEC. 2305.4 |
| 15-STAIR FLOOR PLAN: CLARIFY NOTE #13. |
| THERE IS NOT A POST WHERE THE ARROW IS |
| POINTING. SEE PLAN ON SHEET A-5. |
| 16-IF WOOD COLUMNS ARE CHANGED TO STEEL |
| COLUMNS, THEN REMEMBER TO UPDATE STAIR |
| FRAMING PLANS AND SECTIONS AS REQUIRED |
| 17-SPECIFY SPACING FOR WWM IN CONCRETE |
| SLAB. SEE SEC. 1909.3 FBC 2001. |
| 18-SHEET S-1: SOME DETAILS ARE NOT SHOWN |
| OR INFORMATION IS OVERLAPPING. REVISE |
| AS REQUIRED. |
| 19-IDENTIFY ROOF ZONES IN ROOF FRAMING |
| PLAN FOR NAILING DIAPHRAGM. |
| TABLE 2306.1 CITY AMENDMENTS TO FBC. |
| 20-REVISE TRUSS CONNECTOR TO MATCH USP |
| PUBLISHED ENGINEERED VALUES. PROVIDE |
| ENGINEERING CALCS FOR DIFFERENT VALUES |
| OTHER THAN THOSE PUBLISHED BY USP. |
| **NOTE: TAKE INTO CONSIDERATION ACTUAL |
| SIZE OF NAILS SPECIFIED. SEE USP CAT. |
| 21-PROVIDE ATTIC ACCESS ABOVE GARAGE AND |
| MORNING ROOM IF CLEAR HEIGHT IS MORE |
| THAN 24". SEE. 2309.6 FBC 2001. |
| 22-24SH AND 34SH WINDOWS DON'T PROVIDE |
| THE MIN. CLEAR HEIGHT REQ'D FOR EGRESS |
| SEC. 1005.4.4 FBC 2001. |
| **NOTE: AFTER REVISING 24SH FOR 24+5SH |
| MAKE SURE THAT TOTAL WINDOW OPENING |
| IS 5.7S.F. MIN. SEC. 1005.4.4 FBC 2001 |
| 23-UPDATE SHHET C-1. FOUNDATION NOTE |
| CALLS FOR 0.004 MIL VISQUEEN. NEED |
| 0.006 MIL MIN. SEC. 1909.2 FBC 2001. |
| 24-A)SHT A-1. WHERE IS SEC/5 SHOWN ON |
| FLOR PLAN BY GARAGE ENTRY. |
| B)MAKE SURE THAT SECTIONS AND DETAILS |
| ARE KEYED FOR CORRECT NUMBER AND SHEET |
| 25-SHEET A-2: UPDATE GENERAL NOTE FOR |
| PLUMBING. NEED FBC 2001. |
| **ALSO, MAKE SURE THAT ALL DETAILS AND |
| SECTIONS ARE CORRECTLY KEYED. |
| 26-SHEET A3: THERE IS SOME INFORMATION |
| ON FRONT ELEVATION THAT IS OVERLAPPING |
| 27-SHEET A-5: A)STAIR CALCS AREN'T CLEAR |
| REVISE/CLARIFY AS REQUIRED. |
| B)UPDATE SEMCO STRAP. |
| C)HANDRAIL DIMENSION IS OVERLAPPING IN |
| STAIR SECTION. CLARIFY/REVISE. |
| D)STAIR KEY NOTE #14: DRAFSTOPPING IS NO |
| THE SAME AS FIREBLOCKING. NEED FIRE- |
| BLOCKING. SEE SEC. 2305.1.4 FBC 2001. |
| **ALSO, REVISE LOCATION OF FIREBLOCKING |
| AT MIDDLE OF STAIRS. THE WAY IT IS |
| SHOWN DOESN'T PROVIDE ANY FIREBLOCKING |
| 28-SHEET S-1: A)SOME INFORMATION IS OVER |
| LAPPING. SEE FOUNDATION PLAN. |
| EG: DET. 7/S2 AND SEC/5. |
| B)IF USING WOOD COLUMN DETAIL. REMEMBER |
| TO UPDATE SEMCO FASTENER. |
| C)WHERE IS COLUMN P3 SPECIFIED ON 2ND FL |
| FRAMING PLAN. |
| D)DRAWING SHALL BE NAMED 2ND FL. FRAMING |
| PLAN, NOT GROUND FLOOR FRAMING PLAN. |
| 29-SHEET S-2: A)UPDATE SECTION 5. REVISE |
| SEMCO CONNECTORS. |
| B)REVISE SEMCO CONNECTOR SPECIFIED ON |
| C)PROVIDE SECTION/DETAIL SHOWING HOW |
| IS BEAM 2B-1 ANCHORED TO THE COLUMNS |
| AT THE ENDS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| **SAME FOR BEAM AT MORNING ROOM. |